Fieldbus Specific Mailbox Commands
3-4
Set PCP Object (SET_PCP_OBJECT)
The object dictionary of the Anybus-S Interbus module can be changed to better suit the needs of a spe-
cial implementation which uses the module. After setting a start index, new objects can be downloaded
to the module. This mailbox can only be sent after the SET_START_INDEX mailbox has been sent.
Note:
It is not recommended to download a new object dictionary without knowledge of the PCP-pro-
tocol.
Parameter
Description
Command initiator
Application
Command Name
SET_PCP_OBJECT
Message type
02h
Command number
0004h
Fragmented
No
Extended Header data
-
Command data
Contains information about the PCP object.
Response data
The message data contains the requested PCP-object.
If error code Fh is returned please see the Extended word 8 for further information.
0001h - No start index given.
0002h - Index out of bounds.
0003h - Not a supported index type.
0004h - Error with the selection of IN/OUT buffer and the access rights.
0005h - Object outside the specified memory area length.
0006h - Too many characters in object name.
0007h - PCP-object 6 is larger than the PDU size.