TECHNICAL SPECIFICATIONS 

  

VERNE  HE SERIE 

091 

121 

141 

171 

201 

  

REFRIGERANT 

Type 

 

R-410A 

Global warming potential (GWP) (5) 

 

2088 

Refrigerant  load WPHA 

kg 

0.4 

0.4 

0.4 

0.5 

0.55 

Refrigerant load WPHBA 

kg 

0.7 

0.6 

0.9 

1.5 

1.2 

  

COMPRESSOR 

  

Type 

 

Rotary 

Quantity 

 

Voltage 

V / ~ / Hz 

230 / I / 50 

Oil type 

 

ESTER 

VG74 

ESTER 

VG74 

POE 

ESTER 

VG74 

ESTER 

VG74 

Oil quantity in compressor 

0.35 

0.40 

0.44 

0.48 

0.62 

  

EVAPORATOR FAN 

Type 

 

Radial with EC motor 

Quantity 

 

Size 

mm 

190 

190 

190 

250 

250 

Nominal air flow 

m

³/h

 

500 

600 

700 

900 

1100 

Static pressure available 

Pa 

25 

25 

25 

25 

25 

Maximum pressure available 

Pa 

515 

410 

300 

760 

700 

Motor nominal Capacity 

kW 

0.2 

0.2 

0.2 

0.5 

0.5 

Nominal speed 

r.p.m. 

2500 

2924 

3365 

1368 

1640 

Power supply 

V / ~ / Hz 

230 / I / 50 

  

INDOOR HEAT EXCHANGER 

Type 

 

Coil with aluminium fins and copper pipes  

Frontal area 

m

²

 

0.165 

0.165 

0.165 

0.188 

0.188 

Fin spacing 

mm - (") 

2.1 - 3/8

” 

  

OUTDOOR HEAT EXCHANGER 

Type 

 

Brazed plates 

Quantity 

 

Water connections (gas male screw) 

(") 

¾” 

Number of plates 

 

16 

16 

16 

22 

22 

  

ELECTRICAL DATA 

Voltage 

V / ~ / Hz 

230 / I + N / 50 

Maximum current input  

5.78 

7.18 

8.28 

9.63 

12.63 

Start-up current 

20.98 

22.98 

35.68 

28.13 

45.03 

  

DIMENSIONS AND WEIGHT 

Length 

mm 

1055 

1055 

1055 

1055 

1055 

Width 

mm 

560 

560 

560 

560 

560 

Height 

mm 

410 

410 

410 

470 

470 

Conduit 

mm x 

mm 

225x225 

225x225 

225x225 

236x296 

236x296 

Weight 

kg 

60 

62 

65 

75 

77 

  

SOUND LEVEL 

Sound pressure at 2 m 

dB (A) 

55 

55 

56 

57 

59 

Total sound power (Lw) 

dB (A) 

71.5 

72 

72.5 

73.5 

75.5 

5) 

GWP:

 Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO2, calculated in terms 

of 100-year warming potential. 

Summary of Contents for Verne WPHA HE 091

Page 1: ...A HE WPHA HE WPHBA HE Cooling only Heat pump HORIZONTAL WATER AIR COMPACT PACKAGED UNITS INSTALLATION OPERATION AND MAINTENANCE MANUAL IOM_WPHBA HE WPHA HE_091a1201_207815_180701_EN Models 091 121 141...

Page 2: ...stallations for over 35 years Our approach is based on efficiency adaptability usability and practical solutions This has been the hallmark of our product catalogue The versatility of our factory allo...

Page 3: ...ion 22 Components 22 Safety elements 22 Risk of frost 22 Glycol additions 22 WPHA WPHBA HYDRAULIC CIRCUIT AND ITS COMPONENTS 23 ELEMENTS AND HYDRAULIC CONNECTIONS OF THE INSTALLATION DIAGRAM 24 ELECTR...

Page 4: ...Supply Check that the electrical network features are in accordance to data shown in the data nameplate of the unit Local Safety Regulations Observe and analyse all possible causes of accidents that m...

Page 5: ...Modifications The manufacturer will not respond to the warranty and to the possible damages of the unit in case of electrical and or mechanical modifications The unauthorized manipulation reparation...

Page 6: ...lation from the supply using a two pole voltage detector Even after disconnecting the main voltage life threatening charges can appear between the protective ground PE and the main connection Units wi...

Page 7: ...complete standstill before approaching it In the AC external rotor motor the external rotor turns during operation For brazing operations use a quenching cloth and take precautions to have at close di...

Page 8: ...CITIES 3 Heating capacity 3 kW 2 26 3 16 3 86 4 56 5 75 Power input Heat 3 kW 0 68 0 85 1 12 1 04 1 44 COP Coefficient 3 kW kW 3 31 3 72 3 46 4 37 4 0 SCOP Coefficient 3 kW kW 2 87 3 22 2 99 3 78 3 22...

Page 9: ...kW 0 2 0 2 0 2 0 5 0 5 Nominal speed r p m 2500 2924 3365 1368 1640 Power supply V Hz 230 I 50 INDOOR HEAT EXCHANGER Type Coil with aluminium fins and copper pipes Frontal area m 0 165 0 165 0 165 0 1...

Page 10: ...ITIES 3 Heating capacity 3 kW 7 47 11 61 13 44 15 22 Power input Heat 3 kW 1 71 3 33 3 08 3 17 COP Coefficient 3 kW kW 4 38 3 48 4 36 4 8 SCOP Coefficient 3 kW kW 3 8 3 02 3 77 4 16 s h 3 144 112 9 14...

Page 11: ...upply V Hz 230 1 50 400 3 50 INDOOR HEAT EXCHANGER Type Coil with aluminium fins and copper pipes Frontal area m 0 252 0 252 0 252 0 45 Fin spacing mm 1 8 3 8 1 8 1 8 3 8 2 1 3 8 Oil type PVE PVE PVE...

Page 12: ...3 Heating capacity 3 kW 18 57 24 79 32 42 37 9 Power input Heat 3 kW 3 96 5 63 7 27 8 59 COP Coefficient 3 kW kW 4 69 4 41 4 46 4 41 SCOP Coefficient 3 kW kW 4 07 3 82 3 86 3 81 s h 3 154 9 144 7 146...

Page 13: ...2 4 2 0 2 0 Nominal speed r p m 1242 1509 1476 1643 Power supply V Hz 400 3 50 INDOOR HEAT EXCHANGER Type Coil with aluminium fins and copper pipes Frontal area m 0 45 0 45 0 84 0 84 Fin spacing mm 2...

Page 14: ...of that model similar to the one shown below Be sure to hoist the machine through the points indicated in the diagram Make sure that the unit is balanced stable and without any deformations when it is...

Page 15: ...oughout the installation to prevent the transmission of noise and vibration Check that the direction of the sound level is not going to disturb anyone UNIT SETTLEMENT Be sure unit is correctly balance...

Page 16: ...WEIGHT Models 091 141 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 091 60 75 121 62 77 141 65 80 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filt...

Page 17: ...AND WEIGHT Models 171 201 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 171 75 90 201 77 92 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6 M...

Page 18: ...els 251 451 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 251 90 105 351 110 115 401 115 130 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6 M...

Page 19: ...els 501 751 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 501 160 175 701 160 175 751 180 195 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6...

Page 20: ...Models 1001 1201 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 1001 230 245 1201 250 265 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6 Mano...

Page 21: ...ing wire to avoid water freezing and tube damage It is convenient to install the drain trap with proper dimensions see diagram AIR DUCTS Air duct dimensions will be determined according to the airflow...

Page 22: ...may be necessary to install one or more additional tanks even when the unit has already one Safety elements The installation of the following safety elements is MANDATORY when they ARE NOT incorporat...

Page 23: ...lower value Suspended solids Variable Can deteriorate the material No effects are observed Conductivity 500 s cm No effects are observed 500 s cm Not recommended NH3 Must be between 2 and 20 Not recom...

Page 24: ...Drainage Expansion tank Air duct Conducto de aire It is mandatory to install the flow switch in the water inlet of the machine with a previous section which length is 6 times the of the inlet and 2 t...

Page 25: ...hase Neutral 2 Ground 3 Delayed action fuses or circuit breaker D curve 4 Main switch 5 Th TUNE Control Thermostat connections Th TUNE CONNECTION Two power supply cables 230 VAC L N A shielded twisted...

Page 26: ...AL CONNECTIONS Electrical connection of the hydraulic accessories for maneuver with TH TUNE and PC Do not forget that at least one of the safety devices must be installed and the terminals of the unus...

Page 27: ...t be within 10 of the voltage indicated on the serial plate Check the correct rotation direction of the fans The installer must place line protection elements in accordance with current legislation Wi...

Page 28: ...ling cycle INPUT TEMPERATURE MINIMUM MAXIMUM Dry indoor air 19 C 31 C Wet indoor air 15 C 21 C Water inlet 15 C 45 C For water inlets lower than 25 C it is necessary to install the presostatic valve a...

Page 29: ...ing the Auto mode If the machine does NOT have condensation control then it could stop due to the activation of an alarm Beware of always leaving Auto mode active The conditions that lead to the previ...

Page 30: ...ply temperature ALb3 Alarm B3 probe disconnected Discharge temperature comp 1 ALb5 Alarm B5 probe disconnected Return humidity ALb6 Alarm B6 probe disconnected Return humidity ALb7 Alarm B7 probe disc...

Page 31: ...heck the fan for mechanical vibrations at regular intervals recommended every 6 months Be aware of the limit values indicated in ISO 14694 and carry out relief measures in case of exceeding these e g...

Page 32: ...circuit must be cleaned with a large amount of water to remove traces of acid Put new water and start Compressor Check regularly the lubricant oil level the presence of vibrations or noises and the i...

Page 33: ...signal no power supply etc the motor control does not intervene if the fan rotates in the opposite direction due for example to an air flow If we put the fan in operation while turning in the opposite...

Page 34: ...at the fan will not start up The fan rotates very slowly Rotor blade drags rubs Remove foreign bodies dirt on the fan if necessary Temperature management activated Effective motor or electronic system...

Page 35: ...CLOSED Correct operation without failures 1x CLOSED No release OFF 2x CLOSED Temperature management activated 3x OPEN HALL IC failure 4x OPEN Phase failure only with type 3 5x OPEN Motor blocked 6x O...

Page 36: ...of high temperatures flames burning surfaces and excess humidity Hazardous Reactions Contact with certain red hot metals may result in exothermic or explosive reactions and yield toxic and or corrosi...

Page 37: ...37 IOM_WPHBA HE WPHA HE_091a1201_207815_180701_EN HORIZONTAL WATER AIR COMPACT PACKAGED UNITS WPHA HE WPHBA HE We reserve the right to add modifications without prior notice...