![Hitecsa Verne WPHA HE 091 Installation, Operation And Maintenance Manual Download Page 8](http://html1.mh-extra.com/html/hitecsa/verne-wpha-he-091/verne-wpha-he-091_installation-operation-and-maintenance-manual_2140043008.webp)
8
IOM_WPHBA HE-WPHA HE_091a1201_207815_180701_EN
HORIZONTAL WATER-AIR COMPACT PACKAGED UNITS
WPHA HE / WPHBA HE
TECHNICAL SPECIFICATIONS
VERNE HE SERIES
091
121
141
171
201
WPHA / WPHBA
COOLING CAPACITIES (1)
Nominal cooling capacity (1)
kW
2.36
3.18
3.86
4.82
5.83
Power input (1)
kW
0.72
0.94
1.06
1.11
1.56
EER Coefficient (1)
kW / kW
3.3
3.37
3.64
4.35
3.75
SEER Coefficient (1)
kW / kW
2.94
3.06
3.03
3.74
3.35
η
s,c
(1)
109.5
114.4
113.3
141.8
126.1
Water flow
m
³/h
0.5
0.67
0.81
1.01
1.23
Differential pressure
kPa
8.3
14.3
20.3
17.3
24.9
COOLING CAPACITIES (2)
Nominal cooling capacity (2)
kW
2.64
3.56
4.33
5.38
6.51
Power input (2)
kW
0.52
0.68
0.76
0.83
1.12
EER Coefficient (2)
kW / kW
5.11
5.24
5.69
6.49
5.82
SEER Coefficient (2)
kW / kW
3.7
3.87
3.82
4.55
4.23
η
s,c
(2)
139.8
146.7
144.6
174.2
161.2
Water flow
m
³/h
0.56
0.75
0.91
1.13
1.37
Differential pressure
kPa
10.3
17.6
25.2
21.3
30.4
WPHBA (Heat pump units)
HEATING CAPACITIES (3)
Heating capacity (3)
kW
2.26
3.16
3.86
4.56
5.75
Power input Heat (3)
kW
0.68
0.85
1.12
1.04
1.44
COP Coefficient (3)
kW / kW
3.31
3.72
3.46
4.37
4.0
SCOP Coefficient (3)
kW / kW
2.87
3.22
2.99
3.78
3.22
η
s,h
(3)
106.7
120.8
111.5
143.4
130.7
Water flow
m³/h
0.47
0.66
0.8
0.96
1.23
Differential pressure
kPa
7.4
13.9
19.9
15.8
24.9
HEATING CAPACITIES (4)
Heating capacity (4)
kW
1.76
2.47
3.03
3.57
4.49
Power input Heat (4)
kW
0.6
0.75
0.99
0.96
1.28
COP Coefficient (4)
kW / kW
2.91
3.27
3.05
3.72
3.52
SCOP Coefficient (4)
kW / kW
2.52
2.83
2.63
3.22
3.05
η
s,h
(4)
%
92.8
105.2
97.1
120.7
113.9
Water flow
m³/h
0.36
0.51
0.62
0.75
0.97
Differential pressure
kPa
4.5
8.6
12.4
10.0
16.1
1)
Nominal conditions. Refrigeration tower
: Indoor air 27/19 ºC. Condenser water: inlet 30 ºC / outlet 35 ºC (Inlet
partial loads 26/22/18).
2)
Geothermal conditions
: Indoor air 27/19 ºC. Condenser water: inlet 10 ºC / outlet 15 ºC (Inlet partial loads
10/10/10).
3)
Underground water conditions
: Indoor air 20 ºC. Evaporator water: inlet 10 ºC, unit water flow 100 % outlet 7
ºC.
4)
Brine conditions