Hitecsa Verne WPHA HE 091 Installation, Operation And Maintenance Manual Download Page 31

 

 

 

 

 

31 

IOM_WPHBA HE-WPHA HE_091a1201_207815_180701_EN

 

HORIZONTAL WATER-AIR COMPACT PACKAGED UNITS 

WPHA HE / WPHBA HE

 

 

MAINTENANCE 

 

 

 

It is advisable to do maintenance works every 1.000 operating hours as well as at the beginning of each cooling season. 

 

Refrigeration  circuit: 

Check  for  oil  or  refrigerant  leaks,  noises  or  system’s  vibration.  Take  measurements  of 

temperatures and pressures of components and record them on the maintenance form. 

 

Electrical  circuit: 

Make  sure  that  all  electrical connections 

–wires, contactors and terminals- are properly tight. 

Record the readings for volts and amperes of each compressor and fan motor. Verify the starting current. Check 
the good operation of all relays, pressure switches and phase sequence relay of Scroll compressor

 

Fans:

 Check the direction of rotation of the fans and examine the support of them. Verify the operating status.

 

Before  handling  the  fan,  make  sure  that  it  is  completely  stopped  and  disconnected  from  the  mains,  even  if  it  is 
already stopped and no one can start it during the intervention. 

Regular inspection of the device is necessary. The frequency of  it, must be taken based on the degree of dirt in 
propellers, turbines or impellers. The dirt in impellers (propellers or turbines), motors and grids can  involve risks 
and shortens significantly the life of the fan. 

Keep the fan's air circulation paths clear of obstacles - danger due to shot out objects! 

It  is  necessary  to  check the free  passage  of condensation water  evacuation holes  (if  they  exist)  suitable  for the 
assembly position. 

In cleaning operations be very careful not to unbalance the propeller or turbine. 

If the cleaning work is carried out improperly, in the case of non-painted / painted fans, no guarantee is assumed 
as regards the formation of corrosion or adhesion of the paint. 

To prevent humidity accumulation in the motor, before the cleaning process, the fan must operate for at least 1 hour 
between 80 and 100% of the maximum number of revolutions! 

After  the  cleaning  process,  the  fan  must  work  for  2  hours  between  80  and  100%  of  the  maximum  number  of 
revolutions to dry! 

Check the fan for mechanical vibrations at regular intervals (recommended every 6 months). Be aware of the limit 
values  indicated  in  ISO  14694  and  carry  out  relief  measures  in  case  of  exceeding  these  (e.g.,  the  subsequent 
balancing by expert personnel). 

Check if there are cracks in the impeller (propeller or turbine), especially in the welding seams. 

Motors and fans do not need any additional lubrication "thanks" to the use of lubrication for life. After the useful life 
of the grease expires (30-40,000 h approx.) a change of bearings is required. In view of that, as for any fault (e.g. 
in the winding or in electronic systems), please contact our technical assistance department. 

 

Air filters

: Clean air filters after 4 hours of system operation and every 3 months (or more depending on application). 

Filters can be cleaned by immersion in warm water with soap, later washed in clean water and dry. 

 

Coils

: At least once a year, clean condenser coils with water and detergent, then dry with air at low pressure. Never 

clean with a wire brush, water and/or air at high pressure. 

 

Drainage system

: Verify condition and good operation of the drainage tray and drain trap. It is necessary to clean 

the condensates trays after the first day of operation. Then, clean it at least  once a year. Take into account the 
meteorological conditions, e.g. in places where falling leaves or the flight of seeds can plug the drain trap, it will 
also be necessary to clean them at mid and late spring and autumn. The dates are approximate and will depend on 
the blooming, falling leaves, seeds, etc. of the plants of the zone or the human activity or any other cause. 

 

Hydraulic Circuit: 

Check for water leaks, as well as noise and vibrations of the system elements. Record water 

pressure values at the inlet and outlet of the pump. 

Clean the filter and the flow switch, it should be done frequently enough to avoid deposits that could block them. 

Make sure you know and comply with all local laws and regulations that affect the maintenance of water facilities.  

 

 

Before performing any service or maintenance operation it is mandatory to turn off the main power switch of 

the system to avoid any personal injuries. Locked it so that nobody other than a qualified technician can 

switch on electrical power.  

Read the SAFETY PRECAUTIONS! 

 

WARNING! 

Summary of Contents for Verne WPHA HE 091

Page 1: ...A HE WPHA HE WPHBA HE Cooling only Heat pump HORIZONTAL WATER AIR COMPACT PACKAGED UNITS INSTALLATION OPERATION AND MAINTENANCE MANUAL IOM_WPHBA HE WPHA HE_091a1201_207815_180701_EN Models 091 121 141...

Page 2: ...stallations for over 35 years Our approach is based on efficiency adaptability usability and practical solutions This has been the hallmark of our product catalogue The versatility of our factory allo...

Page 3: ...ion 22 Components 22 Safety elements 22 Risk of frost 22 Glycol additions 22 WPHA WPHBA HYDRAULIC CIRCUIT AND ITS COMPONENTS 23 ELEMENTS AND HYDRAULIC CONNECTIONS OF THE INSTALLATION DIAGRAM 24 ELECTR...

Page 4: ...Supply Check that the electrical network features are in accordance to data shown in the data nameplate of the unit Local Safety Regulations Observe and analyse all possible causes of accidents that m...

Page 5: ...Modifications The manufacturer will not respond to the warranty and to the possible damages of the unit in case of electrical and or mechanical modifications The unauthorized manipulation reparation...

Page 6: ...lation from the supply using a two pole voltage detector Even after disconnecting the main voltage life threatening charges can appear between the protective ground PE and the main connection Units wi...

Page 7: ...complete standstill before approaching it In the AC external rotor motor the external rotor turns during operation For brazing operations use a quenching cloth and take precautions to have at close di...

Page 8: ...CITIES 3 Heating capacity 3 kW 2 26 3 16 3 86 4 56 5 75 Power input Heat 3 kW 0 68 0 85 1 12 1 04 1 44 COP Coefficient 3 kW kW 3 31 3 72 3 46 4 37 4 0 SCOP Coefficient 3 kW kW 2 87 3 22 2 99 3 78 3 22...

Page 9: ...kW 0 2 0 2 0 2 0 5 0 5 Nominal speed r p m 2500 2924 3365 1368 1640 Power supply V Hz 230 I 50 INDOOR HEAT EXCHANGER Type Coil with aluminium fins and copper pipes Frontal area m 0 165 0 165 0 165 0 1...

Page 10: ...ITIES 3 Heating capacity 3 kW 7 47 11 61 13 44 15 22 Power input Heat 3 kW 1 71 3 33 3 08 3 17 COP Coefficient 3 kW kW 4 38 3 48 4 36 4 8 SCOP Coefficient 3 kW kW 3 8 3 02 3 77 4 16 s h 3 144 112 9 14...

Page 11: ...upply V Hz 230 1 50 400 3 50 INDOOR HEAT EXCHANGER Type Coil with aluminium fins and copper pipes Frontal area m 0 252 0 252 0 252 0 45 Fin spacing mm 1 8 3 8 1 8 1 8 3 8 2 1 3 8 Oil type PVE PVE PVE...

Page 12: ...3 Heating capacity 3 kW 18 57 24 79 32 42 37 9 Power input Heat 3 kW 3 96 5 63 7 27 8 59 COP Coefficient 3 kW kW 4 69 4 41 4 46 4 41 SCOP Coefficient 3 kW kW 4 07 3 82 3 86 3 81 s h 3 154 9 144 7 146...

Page 13: ...2 4 2 0 2 0 Nominal speed r p m 1242 1509 1476 1643 Power supply V Hz 400 3 50 INDOOR HEAT EXCHANGER Type Coil with aluminium fins and copper pipes Frontal area m 0 45 0 45 0 84 0 84 Fin spacing mm 2...

Page 14: ...of that model similar to the one shown below Be sure to hoist the machine through the points indicated in the diagram Make sure that the unit is balanced stable and without any deformations when it is...

Page 15: ...oughout the installation to prevent the transmission of noise and vibration Check that the direction of the sound level is not going to disturb anyone UNIT SETTLEMENT Be sure unit is correctly balance...

Page 16: ...WEIGHT Models 091 141 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 091 60 75 121 62 77 141 65 80 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filt...

Page 17: ...AND WEIGHT Models 171 201 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 171 75 90 201 77 92 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6 M...

Page 18: ...els 251 451 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 251 90 105 351 110 115 401 115 130 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6 M...

Page 19: ...els 501 751 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 501 160 175 701 160 175 751 180 195 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6...

Page 20: ...Models 1001 1201 APROX WEIGHT Kg MODEL Net Weight Packaged Weight 1001 230 245 1201 250 265 Legend 1 Power supply input 2 Water inlet 3 Outdoor water drain 3 4 male 4 Water outlet 5 Air filter 6 Mano...

Page 21: ...ing wire to avoid water freezing and tube damage It is convenient to install the drain trap with proper dimensions see diagram AIR DUCTS Air duct dimensions will be determined according to the airflow...

Page 22: ...may be necessary to install one or more additional tanks even when the unit has already one Safety elements The installation of the following safety elements is MANDATORY when they ARE NOT incorporat...

Page 23: ...lower value Suspended solids Variable Can deteriorate the material No effects are observed Conductivity 500 s cm No effects are observed 500 s cm Not recommended NH3 Must be between 2 and 20 Not recom...

Page 24: ...Drainage Expansion tank Air duct Conducto de aire It is mandatory to install the flow switch in the water inlet of the machine with a previous section which length is 6 times the of the inlet and 2 t...

Page 25: ...hase Neutral 2 Ground 3 Delayed action fuses or circuit breaker D curve 4 Main switch 5 Th TUNE Control Thermostat connections Th TUNE CONNECTION Two power supply cables 230 VAC L N A shielded twisted...

Page 26: ...AL CONNECTIONS Electrical connection of the hydraulic accessories for maneuver with TH TUNE and PC Do not forget that at least one of the safety devices must be installed and the terminals of the unus...

Page 27: ...t be within 10 of the voltage indicated on the serial plate Check the correct rotation direction of the fans The installer must place line protection elements in accordance with current legislation Wi...

Page 28: ...ling cycle INPUT TEMPERATURE MINIMUM MAXIMUM Dry indoor air 19 C 31 C Wet indoor air 15 C 21 C Water inlet 15 C 45 C For water inlets lower than 25 C it is necessary to install the presostatic valve a...

Page 29: ...ing the Auto mode If the machine does NOT have condensation control then it could stop due to the activation of an alarm Beware of always leaving Auto mode active The conditions that lead to the previ...

Page 30: ...ply temperature ALb3 Alarm B3 probe disconnected Discharge temperature comp 1 ALb5 Alarm B5 probe disconnected Return humidity ALb6 Alarm B6 probe disconnected Return humidity ALb7 Alarm B7 probe disc...

Page 31: ...heck the fan for mechanical vibrations at regular intervals recommended every 6 months Be aware of the limit values indicated in ISO 14694 and carry out relief measures in case of exceeding these e g...

Page 32: ...circuit must be cleaned with a large amount of water to remove traces of acid Put new water and start Compressor Check regularly the lubricant oil level the presence of vibrations or noises and the i...

Page 33: ...signal no power supply etc the motor control does not intervene if the fan rotates in the opposite direction due for example to an air flow If we put the fan in operation while turning in the opposite...

Page 34: ...at the fan will not start up The fan rotates very slowly Rotor blade drags rubs Remove foreign bodies dirt on the fan if necessary Temperature management activated Effective motor or electronic system...

Page 35: ...CLOSED Correct operation without failures 1x CLOSED No release OFF 2x CLOSED Temperature management activated 3x OPEN HALL IC failure 4x OPEN Phase failure only with type 3 5x OPEN Motor blocked 6x O...

Page 36: ...of high temperatures flames burning surfaces and excess humidity Hazardous Reactions Contact with certain red hot metals may result in exothermic or explosive reactions and yield toxic and or corrosi...

Page 37: ...37 IOM_WPHBA HE WPHA HE_091a1201_207815_180701_EN HORIZONTAL WATER AIR COMPACT PACKAGED UNITS WPHA HE WPHBA HE We reserve the right to add modifications without prior notice...

Reviews: