iDigit CONTROL
Digital thermostat for fan coil units
LEVEL PARAMETERS
Table 5: 1st level parameters
Parameter
Function
Default setting
Possible settings
P01
TlME PROGRAMMlNG
0 = off
0 = off
1 = on
PtaB
PRESET PARAMETER SETUP
0
0….10
P03
NEUTRAL ZONE
4˚C
0….10˚C
P04
SYSTEM TYPE
0 = 2 pipes
0 = 2 pipes
1 = 4 pipes
2 = fan only
P05
FAN
1 = continuous
0= thermostat
1 = continuous
P06
OUTPUT TYPE
0 = ON−OFF
0 = ON−OFF valves
1 = wax solenoid valve with
temperature algorithm
2 = floating 2 pipes
P07
ELECTRlC HEATER
0 = none
0 = none
1 = replacement
2 = additional
3 = additional EH with SM<P16
P08
WATER PROBE
0 = no probe
0 = no probe
1 = SUM/WlN mode switching
2 = fan enabling
3 = SUM/WlN mode swi
fan enabling
P09
SUMMER / WlNTER
1 = manual
0 = centralised / SM water probe
1 = manual from keyboard
2 = in response to room
temperature
3 = room tempe water
NTC
P10
ECONOMY SETPOlNT DELTA
2˚C
1….10˚C
P2LE
ACCESS TO SECOND LEVEL
PARAMETERS
0
123