iDigit CONTROL

 

Digital thermostat for fan coil units

 

LEVEL PARAMETERS  

 

Table 5: 1st level parameters 

 

Parameter 

Function 

Default setting 

Possible settings 

P01 

TlME PROGRAMMlNG 

0 = off 

0 = off 

1 = on 

PtaB 

PRESET PARAMETER SETUP 

0….10 

P03 

NEUTRAL ZONE 

4˚C 

0….10˚C 

P04 

SYSTEM TYPE 

0 = 2 pipes 

0 = 2 pipes 

1 = 4 pipes 

2 = fan only 

P05 

FAN 

1 = continuous 

0= thermostat 

1 = continuous 

P06 

OUTPUT TYPE 

0 = ON−OFF 

0 = ON−OFF valves 

1 = wax solenoid valve with 
temperature algorithm 

2 = floating 2 pipes 

P07 

ELECTRlC HEATER 

0 = none 

0 = none 

1 = replacement 

2 = additional 

3 = additional EH with SM<P16 

P08 

WATER PROBE 

0 = no probe 

0 = no probe 

1 = SUM/WlN mode switching 

2 = fan enabling 

3 = SUM/WlN mode swi 
fan enabling 

P09 

SUMMER / WlNTER 

1 = manual 

0 = centralised / SM water probe 

1 = manual from keyboard 

2 = in response to room 
temperature 

3 = room tempe water 
NTC 

P10 

ECONOMY SETPOlNT DELTA 

2˚C 

1….10˚C 

P2LE 

ACCESS TO SECOND LEVEL 
PARAMETERS 

123 

Summary of Contents for idigit control

Page 1: ...USER MANUAL 07 16 207674 Rev100 iDigit CONTROL Digital thermostat for fan coil units...

Page 2: ...nstallations Our approach is based in efficiency flexibility manageability and practical solutions It has built a hallmark of our product catalogue The versatility of our factories allows us to contri...

Page 3: ...L Digital thermostat for fan coil units CONTENTS GENERAL OPERATING FEATURES 4 THERMOSTAT OPERATION 5 LEVEL PARAMETERS 11 ELECTRICAL CONNECTION DIAGRAM 12 POLE TERMINAL BOARD 14 ELECTRICAL CONNECTIONS...

Page 4: ...hresholds can be set separately for heating and cooling operation P18 and P19 SUM WlN switching temperature thresholds can be set separately for heating and cooling operation P16 and P17 Automatic SUM...

Page 5: ...t is pressed or hold down for 5 to decrease the setting at high speed After 10 the device automatically quits the temperature setpoint setting function to quit faster press the on off key for a short...

Page 6: ...l selection mode is active or at the minimum speed if the current selection mode is automatic lf the system output probe is connected the fan operates on the following principle 2 pipe system the devi...

Page 7: ...R glage de l heure et de la date de l horloge Press the menu key scroll through it with the key and select TIME with the menu key HRS the hour figures flash use the keys to set the current hours and c...

Page 8: ...Press the menu key and set the starting hours for band F2 Press the menu key and set the starting minutes of band F2 Press the menu key and set the operating temperature for band F2 Use the key to sel...

Page 9: ...L Digital thermostat for fan coil units Table 3 example of weekly time program set in table 2 The icon on the display illuminates to indicate that the thermostat is performing a daily program Day F1 T...

Page 10: ...d level is protected by a password To access the first level parameter menu press the menu key use the key to scroll the menu and confirm the PAr option by pressing the menu key for 5 Parameter P01 wi...

Page 11: ...rmostat 1 continuous P06 OUTPUT TYPE 0 ON OFF 0 ON OFF valves 1 wax solenoid valve with temperature algorithm 2 floating 2 pipes P07 ELECTRlC HEATER 0 none 0 none 1 replacement 2 additional 3 addition...

Page 12: ...19 SUMMER FAN ON 15 0 C 5 0 25 0 C P20 ANTlFREEZE C 4 0 C 0 0 10 0 C P21 FLOATlNG ACTUATOR STROKE 150 0 400 P22 FlLTER FOULED 6 x 300h 0 20 x 300h P23 SETPOlNT BOTTOM LlMlT 10 0 C 10 0 30 0 C P24 SETP...

Page 13: ...8 AlR SETPOlNT 20 0 C 10 30 C P39 MEASURlNG SCALE C F 0 C 0 C 1 F P40 BOX BACKLlGHT MlNlMUM LlGHT lN STANDBY MODE 0 off 0 5 P41 LCD BACKLlGHT MlNlMUM LlGHT lN STANDBY MODE 0 off 0 5 P42 MODBUS NETWORK...

Page 14: ...max 1A 230Vac TK4 TK5 TK6 solenoid valve heater control triac max 0 1A 230Vac VF floating valve VF floating valve VC cooling valve VH heating valve heating and cooling for 2 pipe system R auxiliary o...

Page 15: ...mostat for fan coil units ELECTRICAL CONNECTIONS TO RJ45 CONNECTOR Key CW window contact EC economy contact DMC cooling valve modulating output 0 10V DMH heating valve modulating output 0 10V CN1 auxi...

Page 16: ...207674 Rev100 HIPLUS AIRE ACONDICIONADO S L Masia Torrents 2 Tel 34 93 893 49 12 Fax 34 93 893 96 15 08800 Vilanova i la Geltr Barcelona Spain www hitecsa com Rights reserved subject to change withou...

Reviews: