Table 6: 2nd level parameters
Parameter
Function
Default setting
Possible settings
P11
PROPORTlONAL BAND
2˚C
1.0….5.0˚C
P12
RH CONTROL MODE
0 = display only
0 = display only
1 = humidification
2 = dehumidification
3 = COOL + RH
P13
RH. PROPOR. BAND
5%
5….20%
P14
FULL RESET REG. TlME
6
0−200 (x 10”)
P15
AUXlLlARY OUTPUT
FUNCTlON
0 = electric heater
0 = electric heater
1 = humidifier/dehumidifier
2 = gate valve operation
3 = control of lights
P16
WlNTER ON
35.0˚C
20.0….50.0˚C
P17
SUMMER ON
15.0˚C
5.0….25.0˚C
P18
WlNTER FAN ON
35.0˚C
20.0….50.0˚C
P19
SUMMER FAN ON
15.0˚C
5.0….25.0˚C
P20
ANTlFREEZE ˚C
4.0˚C
0.0….10.0˚C
P21
FLOATlNG ACTUATOR
STROKE
150”
0….400”
P22
FlLTER FOULED
6 (x 300h)
0….20 (x 300h)
P23
SETPOlNT BOTTOM LlMlT
10.0˚C
10.0….30.0˚C
P24
SETPOlNT TOP LlMlT
30.0˚C
10.0….30.0˚C
P25
ROOM PROBE OFFSET
0.0˚C
−5.0….+5.0˚C
P26
HUMlDlTY PROBE OFFSET
0%
−20%....+20%
P27
FAN START DELAY lN
HEATlNG MODE
0”
0….250”
P28
FAN START DELAY WlTH
ELECTRlC HEATER
60”
10….600”
P29
FAN STOP DELAY
WlTH ELECTRlC HEATER
120”
10….600”
P30
WlNDOW CONTACT
0 = contact closed
0 = contact closed = window
open 1 = contact open =
window open
P31
ECONOMY CONTACT
0 = contact open
0 = contact open = room
occupied 1 = contact closed =
window occupied
P32
AUXlLlARY CONTACT
1 = contact closed
0 = contact open = input active
1 = contact closed = input
active