ROOF TOP UNITS
– AXIAL FAN
RMXCA/RMXCBA
OPERATIONAL LIMITS
► COOLING MODE
KUBIC series
1402.2
1602.2
2002.2
2402.2
3002.2
3502.2
4002.2
4502.2
Outdoor max temperature. Interior 27º C BS /
19º C BH
ºC
48
46
50
47
45
47
47
45
Outdoor max temperature. In downloading
ºC
50
50
50
50
50
50
50
50
Outdoor max temperature. Indoor 20º C BS*
ºC
18
19
18
19
20
19
19
20
Max Temperature. Inlet Indoor battery.
Outdoor 38º C BS
ºC
33
34
32
33
34
33
33
34
Mín Temperature. Inlet indoor battery
.Outdoor 35º C BS
ºC
17
18
17
18
18
18
18
18
► HEATING MODE
KUBIC series
1402.2
1602.2
2002.2
2402.2
3002.2
3502.2
4002.2
4502.2
Outdoor min Temperature. Indoor 20º C BS
ºC
-8 BH
-7 BH
-8 BH
-7 BH
-6 BH
-7 BH
-7 BH
-6 BH
Min Temperature. Inlet indoor battery Outdoor
7º C BS
ºC
13
13
14
13
13
13
13
13
Units can work at maximum altitude of 1500 m.
For other conditions, please consult us.
*For lower temperatures it is necessary to use the condensation control, supplied as optional.
• The electrical power supply to the unit should agree with data on the plate. Unit start-up at incorrect voltage and
damages resulting from that are not covered by Hitecsa guarantee.
• When making electrical connections always use the unit’s wiring diagram.
• Verify that the compressor crankcase heater can be energized before unit start up.
• Unit current supply should be within ±5% of Voltage and Amperes indicated on the unit nameplate.
• Do not operate unit at different current from the one shown on unit plate
• The installer has to install line protection elements according to local laws and regulations.
•The interconnecting wires have to be in protection tube or inside groove channel.
Before to access inside the unit through the electric box, it is MANDATORY to
unplug the electrical supply hose that MUST BE FREE of voltage for this
operation.
ATTENTION