ENGLISH
8 ELECTRICAL AND CONTROL SETTINGS
8.1 INTRODUCTION
The YUTAKI M Remote control box is an extension of the
hydraulic control box of the YUTAKI M.
With the Remote control box activated, the system separates
the water generation control (hot or cold) from the water
distribution and consumption control. Water generation control
is performed on YUTAKI M unit PCB, while the water distribution
and consumption control is done through the Remote control
box.
The system comprised of a YUTAKI M and the Remote control
box operates as a single YUTAKI M for all function unless it is
specifically indicated that the function is not enabled.
YUTAKI M
Water pipes
Remote
control box
Example:
H-Link
Water pipes
Control wiring
Communication wiring
Zone 1
Zone 2
8.2 MIRROR FUNCTION
8.2.1 Function activation
To activate the Mirror function the following settings of the DSW and SSW are required
Required DSW & SSW settings to enable the mirror function
Dip switch
YUTAKI M PCB2
Remote control box PCB3
(ATW-YMM-01)
DSW4
8
7
(New setting is required)
8
7
(Factory setting)
SSW1
Remote
Local
(New setting is required)
Remote
Local
(Factory setting)
When DSW4 pin 1 and SSW1 are set accordingly to this table,
AUOP
is shown in the 7-segment display of YUTAKI M PCB2.
!
C A U T I O N
Model capacity setting through DSW2 in the Remote control box PCB3 is required according to the YUTAKI M model.
ELECTRICAL AND CONTROL SETTINGS
PMML0345A rev.1 - 08/2016
5