background image

Hitachi Universal V2 Rack accessories

The following table provides rack accessory information for VSP F series storage systems.

Table 25 Accessories for the Hitachi Universal V2 Rack

Front door

Rear door

Side panels

Optional, must be

ordered separately

(A3BF-DR).

Included with rack

Not included with rack, must be ordered

separately. A quantity of two must be

ordered per rack (A3BF-Z-PAN-1200).

Hitachi Universal V2 Rack accessories

Appendix F: Non-Hitachi racks

Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide

99

Summary of Contents for Virtual Storage Platform F350

Page 1: ... 0x Hardware Reference Guide This document provides information about the system hardware components and the mechanical and environmental specifications for the Hitachi Virtual Storage Platform F350 and F370 all flash arrays MK 97HM85016 05 January 2021 ...

Page 2: ... be held retrieved deleted or otherwise processed in accordance with relevant laws Notice on Export Controls The technical data and technology inherent in this Document may be subject to U S export control laws including the U S Export Administration Act and its associated regulations and may be subject to export or import regulations in other countries Reader agrees to comply strictly with all su...

Page 3: ...ntroller front panel LEDs without bezel 15 CBSS controller rear panel LEDs 16 CBSS controller power supply unit LEDs and connectors 18 Host Network and Drive Tray Ports and LEDs 18 Front end modules 18 10 Gbps iSCSI board LEDs and connectors optical 19 10 Gbps iSCSI board LEDs and connectors copper 19 8 Gbps 16 Gbps or 32 Gbps Fibre Channel 4 port board LEDs and connectors 21 16 Gbps Fibre Channel...

Page 4: ... specifications 54 Environmental specifications 55 Shared memory 61 Appendix C Network access 63 TCP IP port assignments 63 Controller connections 66 Physical service processor connections 66 Appendix D Data and power cables 68 Required cables 68 Fibre Channel cables 70 iSCSI cables 73 iSCSI standards 76 iSCSI specifications 76 Managing cables 79 AC power cables 82 Power cable assemblies 82 AC con...

Page 5: ...16A 15C13 3C19CE P 94 APAC and EMEA three phase PDU 3P32A 24C13 6C19CE P 95 Americas APAC and EMEA three phase PDU 3P30A 243 69CE UL P 96 Appendix F Non Hitachi racks 98 Non Hitachi rack support 98 Hitachi Universal V2 Rack rail kits 98 Hitachi Universal V2 Rack accessories 99 Appendix G Warning labels on the storage system 100 CBSS controller 101 CBSL controller 102 Small form factor drive tray 1...

Page 6: ...e the UEFI Development Kit website http sourceforge net apps mediawiki tianocore index php title UDK2010 2004 Intel Corporation All rights reserved Redistribution and use in source and binary forms with or without modification are permitted provided that the following conditions are met Redistributions of source code must retain the above copyright notice this list of conditions and the following ...

Page 7: ... document revision applies to VSP F350 F370 firmware 88 07 0x or later Release notes Read the release notes before installing and using this product They may contain requirements or restrictions that are not fully described in this document or updates or corrections to this document Release notes are available on Hitachi Vantara Support Connect https knowledge hitachivantara com Documents Changes ...

Page 8: ... optional values Example a b indicates that you can choose a b or nothing braces Indicates required or expected values Example a b indicates that you must choose either a or b vertical bar Indicates that you have a choice between two or more options or arguments Examples a b indicates that you can choose a b or nothing a b indicates that you must choose either a or b This document uses the followi...

Page 9: ...s 1 terabyte TB 1 000 GB or 1 0004 bytes 1 petabyte PB 1 000 TB or 1 0005 bytes 1 exabyte EB 1 000 PB or 1 0006 bytes Logical capacity values for example logical device capacity cache memory capacity are calculated based on the following values Logical capacity unit Value 1 block 512 bytes 1 cylinder Mainframe 870 KB Open systems OPEN V 960 KB Others 720 KB 1 KB 1 024 210 bytes 1 MB 1 024 KB or 1 ...

Page 10: ... support hitachivantara com en_us contact us html Hitachi Vantara Community is a global online community for Hitachi Vantara customers partners independent software vendors employees and prospects It is the destination to get answers discover insights and make connections Join the conversation today Go to community hitachivantara com register and complete your profile Comments Please send us your ...

Page 11: ...the storage system can remain operational if a component fails Adding and replacing components along with firmware upgrades can be conducted while the storage system is active and without interruption of data availability to the hosts A hot spare drive can be configured to replace a failed data drive automatically securing the fault tolerant integrity of the logical drives Self contained hardware ...

Page 12: ...mponents are configured with redundancy to maintain continued service RAID 1 RAID 5 and RAID 6 support RAID 6 including 14D 2P Provides data security by transferring data to cache flash memory at the time of a power outage Scalability and versatility Supports small form factor drive trays DBS DBSE requiring 2U of rack space and up to 24 2 5 inch HDDs and or flash drives can be installed Supports s...

Page 13: ... chassis with small form factor drive bays CBSS The CBSS controller chassis houses controllers backup fan modules power supplies and provides twenty four slots at the front for loading large form factor 2 5 inch data drives The chassis also includes specific functional LEDs located on the front and rear of controller to provide its operating status The following table lists the controller board sp...

Page 14: ...e requires maintenance Note When System Option Mode 1097 is set to ON the WARNING LED does not blink even if the following failure service information messages SIM are issued 452xxx 462xxx 3077xx 4100xx and 410100 LED might turn off during user maintenance 4 ALARM LED Off Normal operation Red Processor failure system might be down For assistance contact customer support https support hitachivantar...

Page 15: ...ollowing table describes the definitions of the CBSS controller front panel LEDs Number Item Description 1 ACT LED Green Normal operation Blink green Drive is being accessed 2 ALM LED Red Drive stopped due to a failure and can be replaced 3 POWER READY WARNING and ALARM LEDs Note When System Option Mode 1097 is set to ON the WARNING LED does not blink even if the following failure service informat...

Page 16: ...controller rear panel LEDs Number Item Description 1 Controllers Controller 1 left and Controller 2 right 2 Front end module N A 3 CTL ALM LED Red Controller can be removed Blink red Failure with the power supply unit of the controller Amber LAN reset switch was pressed 4 BACKUP STTS LED Green Power restoration in progress following power outage Fast blink green Restoring CBSS controller rear pane...

Page 17: ...D for cache flash memory Red Cache flash memory can be removed 11 Backup module N A 12 STATUS Green Charging of the battery in the backup module is complete Blink green Battery in the backup module is charging or discharging Red Backup module can be removed Blink red Backup module can be removed Off Battery is not installed failure occurred or firmware is being upgraded 13 SAS port N A 14 Port LED...

Page 18: ...th specific interfaces for connecting powering configuring and managing the storage system The component LEDs display the operating status of the storage system Front end modules The front end modules FEMs also called channel boards CHBs control the transfer of data between the host and cache memory VSP G130 G F350 G F370 G F700 G F900 storage systems support Fibre Channel FC and iSCSI FEMs for at...

Page 19: ...ORT LED Red Small form factor SFF pluggable can be removed Blue Normal link status Blue Blinking Front end module is in communication status 3 iSCSI connectors Connect to Ethernet cables 10 Gbps iSCSI board LEDs and connectors copper 10 Gbps iSCSI board LEDs and connectors optical Chapter 2 System controllers Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 19 ...

Page 20: ...Green 10 Gbps link Off No link connection 3 PORT LED Green Link connection is established Blinking Communication is in progress Off No link connection or not ready to communicate 4 iSCSI connectors Connect to Ethernet cables 10 Gbps iSCSI board LEDs and connectors copper Chapter 2 System controllers Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 20 ...

Page 21: ...oved Blue Normal link status at 8 Gbps Green Normal link status at 2 Gbps or 4 Gbps Table 2 32 Gbps 16 Gbps Fibre Channel Number Item Description 1 Fibre Channel connectors Connect to Fibre Channel cables 2 STATUS LED Green Front end module is in power on state Red Front end module can be removed safely 3 PORT LED Red Small form factor SFF pluggable can be removed 8 Gbps 16 Gbps or 32 Gbps Fibre C...

Page 22: ...ight Port 1 Port 2 Port 3 Port 4 CHB 1A 1A 3A 5A 7A CHB 1B 1B 3B 5B 7B CHB 1C 1C 3C 5C 7C CHB 1D 1D 3D 5D 7D CHB 1E 1E 3E 5E 7E CHB 1F 1F 3F 5F 7F CHB 1G 1G 3G 5G 7G CHB 1H 1H 3H 5H 7H CHB 2A 2A 4A 6A 8A CHB 2B 2B 4B 6B 8B CHB 2C 2C 4C 6C 8C CHB 2D 2D 4D 6D 8D CHB 2E 2E 4E 6E 8E CHB 2F 2F 4F 6F 8F CHB 2G 2G 4G 6G 8G CHB 2H 2H 4H 6H 8H 8 Gbps 16 Gbps or 32 Gbps Fibre Channel 4 port board LEDs and c...

Page 23: ...able can be removed Blue Normal link status at 16 Gbps Green Normal link status at 4 Gbps or 8 Gbps 3 Fibre Channel connectors Connect to Fibre Channel cables Port assignments CHB number 16 Gbps Fibre Channel ports left to right Port 1 Port 2 CHB 1A 1A 3A CHB 1B 1B 3B 16 Gbps Fibre Channel 2 port board LEDs and connectors Chapter 2 System controllers Hitachi Virtual Storage Platform F350 F370 Hard...

Page 24: ...HB 2D 2D 4D CHB 2E 2E 4E CHB 2F 2F 4F CHB 2G 2G 4G CHB 2H 2H 4H Back end modules The back end modules BEMs also called disk boards DKBs control the transfer of data between the drives and cache memory The back end module LEDs indicate the operating status of the module Back end modules Chapter 2 System controllers Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 24 ...

Page 25: ...em Description 1 PATH 1 connector Connects to a drive tray 2 PORT LED Blue Normal link status Back end modules Chapter 2 System controllers Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 25 ...

Page 26: ...n ports conventional hard disk drives HDD are not included or configurable with all flash arrays Small form factor drive tray DBS DBSE The following describes the physical specifications of the small form factor drive tray Name Model name Height Number of drive slots Drive type DBS DW F800 DBSC 2U 88 2 mm 24 2 5 inch SFF DBSE DW F800 DBSE 2U 88 2 mm 24 2 5 inch SFF SFF with front panel bezel Numbe...

Page 27: ...l Number Item Description 1 POWER READY and LOCATE LEDs Green Drive tray is powered on Green Drive tray is operational Amber Indicates the location of the chassis Can be turned on or turned off by the maintenance utility 2 ALM LED Red Drive stopped due to a failure and can be replaced 3 ACT LED Green Normal operation SFF front panel without bezel Chapter 3 Drive trays Hitachi Virtual Storage Platf...

Page 28: ...escription 1 ENC N A 2 POWER LED Green ENC is in the power on state 3 Locate LED Amber Indicates the location of the chassis Can be turned on or turned off by the maintenance utility 4 ALARM LED Red ENC can be replaced 5 PATH IN LED Blue IN side port is linked up 6 PATH IN connector Connects to a controller or drive tray SFF rear panel Chapter 3 Drive trays Hitachi Virtual Storage Platform F350 F3...

Page 29: ...operation AC power supply unit LEDs and connectors Both SFF and LFF drive trays are equipped with AC power supply units The AC power supply units include LEDs to display its operating status Note The DBS and DBL power supply has a Silver efficiency rating The DBSE and DBLE power supply has a Platinum efficiency rating Number Item Description 1 RDY LED Green Normal operation 2 ACI IN LED Green AC i...

Page 30: ...mber Item Description 3 ALM LED Red Power supply unit can be replaced AC power supply unit LEDs and connectors Chapter 3 Drive trays Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 30 ...

Page 31: ... you begin Ensure that all software specific shutdown procedures have been completed Refer to the applicable user manuals for details Ensure that all I O activity to the storage system has stopped You can vary paths offline and shut down the attached hosts Procedure 1 Press the main switch on the controller chassis for approximately three seconds until the POWER LED on the front of the chassis cha...

Page 32: ...e storage system in a place where the ambient temperature is 86 F 30 C or less on average Periodic parts replacement is required If you have a maintenance service contract parts are replaced periodically according to the terms of the contract Note The battery protects the data in the cache memory in an emergency such as a sudden power failure In these cases follow the normal power down procedure I...

Page 33: ... representative VSP F350 parts list The VSP F350 includes the following standard and optional components Table 4 CBSS controller components Model number Part description Quantity DW800 CBSS 2U chassis 1 AC power supply unit 2 Backup module BKM 2 Front bezel 2U 1 Binder 1 SAS cable label 2 DW F800 RRCB Rail kit 1 Appendix A Storage system parts list Hitachi Virtual Storage Platform F350 F370 Hardwa...

Page 34: ... 12 Gbps SFF flash drive 0 24 DKC F810I 960MGM 960 GB MLC 12 Gbps SFF flash drive 0 24 DKC F810I 1R9MGM 1 9 TB MLC TLC 12 Gbps SFF flash drive 0 24 DKC F810I 1T9MGM 1 9 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 3R8MGM 3 8 TB MLC TLC 12 Gbps SFF flash drive 0 24 DKC F810I 7R6MGM 7 6 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 15RMGM 15 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 30RMGM 30 T...

Page 35: ...ntity DKC F810I 480MGM 480 GB MLC 12 Gbps SFF flash drive 0 24 DKC F810I 960MGM 960 GB MLC 12 Gbps SFF flash drive 0 24 DKC F810I 1R9MGM 1 9 TB MLC TLC 12 Gbps SFF flash drive 0 24 DKC F810I 1T9MGM 1 9 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 3R8MGM 3 8 TB MLC TLC 12 Gbps SFF flash drive 0 24 DKC F810I 7R6MGM 7 6 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 15RMGM 15 TB TLC 12 Gbps SFF flash...

Page 36: ...lash drive 0 24 DKC F810I 1T9MGM 1 9 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 3R8MGM 3 8 TB MLC TLC 12 Gbps SFF flash drive 0 24 DKC F810I 7R6MGM 7 6 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 15RMGM 15 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 30RMGM 30 TB TLC 12 Gbps SFF flash drive 0 24 Table 10 Optional service processor Model number Part description Quantity HDW2 F850 SVP P Servic...

Page 37: ...CBSS 7 192 VSP F370 parts list The VSP F370 includes the following standard and optional components Table 11 CBSS controller components Model number Part description Quantity DW800 CBSS 2U chassis 1 AC power supply unit 2 Backup module BKM 2 Front bezel 2U 1 Binder 1 SAS cable label 2 DW F800 RRCB Rail kit 1 VSP F370 parts list Appendix A Storage system parts list Hitachi Virtual Storage Platform ...

Page 38: ...flash memory CFM 2 DKC F810I 600JCMC 600 GB 2 5 inch 10kmin 12 Gbps SAS drive 0 24 DKC F810I 1R2JCMC 1 2 TB 2 5 inch 10kmin 12 Gbps SAS drive 0 24 DKC F810I 1R8JGM 1 8 TB 2 5 inch 10kmin 12 Gbps SAS drive 0 24 DKC F810I 2R4JGM 2 4 TB 2 5 inch 10kmin 12 Gbps SAS drive 0 24 DKC F810I 480MGM 480 GB MLC 12 Gbps SFF flash drive 0 24 DKC F810I 960MGM 960 GB MLC 12 Gbps SFF flash drive 0 24 DKC F810I 1R9...

Page 39: ...Longwave 0 16 DW F800 1PL32 SFP for 32 Gbps Longwave 0 16 Note 1 A DIMM of a particular capacity cannot be mixed with different capacities or DIMM types in a storage system configuration Table 13 DBS drive tray components Model number Part description Quantity DW F800 DBSC 2U chassis 1 ENC 2 AC Power supply unit 2 Front bezel 2U 1 DW F800 RRDB Rail kit 1 VSP F370 parts list Appendix A Storage syst...

Page 40: ...h drive 0 24 DKC F810I 15RMGM 15 TB TLC 12 Gbps SFF flash drive 0 24 DKC F810I 30RMGM 30 TB TLC 12 Gbps SFF flash drive 0 24 Table 15 DBSE drive tray components Model number Part description Quantity DW F800 DBSE 2U chassis 1 ENC 2 AC Power supply unit 2 Front bezel 2U 1 DW F800 RRDB Rail kit 1 Table 16 DBSE optional drive tray components Model number Part description Quantity DKC F810I 480MGM 480...

Page 41: ...ber Part description Quantity HDW2 F850 SVP P Service processor Windows 10 Enterprise 1 Drive tray and drive configuration The following table lists the supported maximum installable drive trays and data drives for the VSP F370 storage system Controller chassis Maximum number of mountable drive trays Maximum number of mountable drives DBS DBSE Solid state drive CBSS 11 288 Data and power cable mod...

Page 42: ...15 A A F6516 P620 Power cable for PDU 1 A F6516 P630 Power cable for PDU 1 Table 19 SAS cables Model number Specification DW F800 SCQ1 1 m SAS cable including omega clip 2 DW F800 SCQ1F 1 5 m SAS cable including omega clips 2 DW F800 SCQ3 3 m SAS cable including omega clips 2 DW F800 SCQ5 5 m SAS cable including omega clips 2 DW F800 SCQ10A 10 m SAS optical cable DW F800 SCQ30A 30 m SAS optical ca...

Page 43: ... optical cable for optical A 6515 HM10L 10 m LC LC optical cable for optical A 6515 HM20L 20 m LC LC optical cable for optical A 6515 HM30L 30 m LC LC optical cable for optical A 6515 HM50L 50 m LC LC optical cable for optical A 6515 HM100L 100 m LC LC optical cable for optical A 6515 HM200L 200 m LC LC optical cable for optical A 6515 HM300L 300 m LC LC optical cable for optical A 6515 JM5L 5 m L...

Page 44: ...mber Specification A 6515 JM300L 300 m LC LC optical cable for optical Data and power cable model list Appendix A Storage system parts list Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 44 ...

Page 45: ... Heat output W 218 W Power consumption VA 226 VA Air flow m3 min 3 4 0 m3 min Notes 1 The start up time might be longer in proportion to the number of drive trays connected With a maximum configuration 1 controller chassis and 19 drive trays start up time is approximately 8 minutes 2 Can be mounted on the RKU rack For the mounting special rails for the rack and decoration panels are required separ...

Page 46: ...proportion to the number of drive trays connected With a maximum configuration 1 controller chassis and 19 drive trays start up time is approximately 8 minutes 2 Can be mounted on the RKU rack For the mounting special rails for the rack and decoration panels are required separately depending on the number of the mounted storage systems 3 The value is at maximum level VSP F350 mechanical specificat...

Page 47: ...s the maximum mountable quantity unit may vary 2 Available as spare or data disks Host interface Item Specification Interface type 16 32 Gbps FC Optical 10 Gbps iSCSI Optical 10 Gbps iSCSI Copper Data transfer speed Max speed for transfer to host 400 Mbps FC 800 Mbps FC 1600 Mbps FC 3200 Mbps FC 1000 Mbps iSCSI Optical 1000 Mbps iSCSI Copper Number of ports 16 32 Gbps FC Optical 16 10 Gbps iSCSI O...

Page 48: ... 2P 14D 2P Maximum number of parity groups 64 Maximum volume size 3 TB when using the LDEVs of other Storage Systems 4TB Maximum volumes host groups and iSCSI targets 2048 Maximum volumes parity groups 2048 A storage system configured with RAID6 RAID 5 or RAID 1 provides redundancy and enhances data reliability However there is still a possibility of losing data caused by unforeseeable hardware or...

Page 49: ...o a nonvolatile memory Non volatile data in the cache memory is protected against sudden power failure The backup operation writes data into a cache even if a power interruption occurs and transferred to the cache flash memory Insulation performance Item Specification Insulation withstand voltage AC 1 500 V 100mA 1min Insulation resistance DC 500 V 10 MΩ or more VSP F370 mechanical specifications ...

Page 50: ...chassis and 19 drive trays start up time is approximately 8 minutes 2 Can be mounted on the RKU rack For the mounting special rails for the rack and decoration panels are required separately depending on the number of the mounted storage systems 3 The value is at maximum level DBS DBSE drive chassis Item Specification Physical dimension W x D x H mm 482 565 88 2 mm Weight Mass kg Approximate 17 kg...

Page 51: ...t maximum level Drive type Item Specification Supported data capacity 472 61 945 23 1890 46 3780 92 7561 85 15048 49 30095 00 GB Maximum storage system capacity physical capacity 3 941 TiB using 15 TB 2 5 inch SFF SSD 7 882 TiB using 30 TB SSD Maximum mountable quantity unit 1 24 total per chassis 288 maximum per system Maximum number of spare drives2 24 Note 1 When mounting storage system and DBS...

Page 52: ...s iSCSI Optical 8 10 Gbps iSCSI Copper 8 Transferred block size bytes 512 Maximum number of hosts via FC switch 255 Maximum number of hosts via network switch 255 Battery life Storage system intake temperature CBSS Up to 75 2º F 24º C 5 years Up to 86º F 30º C 5 years Up to 93 2º 34º C 4 years Up to 104º 40º C 3 years VSP F370 mechanical specifications Appendix B System specifications Hitachi Virt...

Page 53: ...or RAID 1 provides redundancy and enhances data reliability However there is still a possibility of losing data caused by unforeseeable hardware or software failure Users should always follow recommended best practices and back up all data Internal logic specifications CBSS Item Specification Control memory Flash memory 32 MB L3 cache memory 4 MB SDRAM 1 GB Data assurance method Data bus Parity Ca...

Page 54: ...nsulation performance Item Specification Insulation withstand voltage AC 1 500 V 100mA 1min Insulation resistance DC 500 V 10 MΩ or more Electrical specifications The electrical input power specifications for the storage systems are described in the following table Item Controller Drive tray Input voltage operable voltage range V AC 100 120 200 240 6 11 SFF LFF and dense intermix drive tray AC 200...

Page 55: ...one power unit can provide the total capacity for two power units 3 This table shows the power requirement 100 V or 200 V for the maximum configuration The actual required power might exceed the value shown in the table when the tolerance is included Environmental specifications The environmental specifications for the storage systems are described in the following table Temperature Caution The fo...

Page 56: ...mage to product 9 8 1 0 G Ensure own safety with fall prevention Within 5 seconds resonance point 10 Hz or less Transport packed m s2 5 0 m s or less Impact State CBSS controller DBS DBSE drive tray Operating m s2 20 or less 10 ms half sine wave Non operating m s2 50 or less 10 ms half sine wave Transport packed m s2 80 or less Tipping angle Storage system tips over 15 or less To be measured when ...

Page 57: ...ambient temperature and the altitude is from 35ºC at an altitude of 950m 3000 feet to 28ºC at an altitude of 3050m 1000 feet The allowable ambient temperature is decreased by 1ºC for every 300m increase in altitude above 950m Gaseous contaminant Avoid areas exposed to corrosive gas and salty air State Controller tray Operating Gaseous contamination should be within ANSI ISA S71 04 2013 G1 classifi...

Page 58: ...5m in the rack Measurement position 1m away from the front rear left or right side of the storage system and 1 5m high at four points Measurement value Energy average value of the four points front rear left and right The recommendation is to install the storage system in a computer room in a data center It is possible to install the storage system in a general office however take measures against...

Page 59: ...suppression systems and acoustic noise Some data center inert gas fire suppression systems when activated release gas from pressurized cylinders that moves through the pipes at very high velocity The gas exits through multiple nozzles in the data center The release through the nozzles could generate high level acoustic noise Similarly pneumatic sirens could also generate high level acoustic noise ...

Page 60: ...ces such as emergency sirens 4 If it can be safely done without risk of personal injury shut down the storage systems to avoid data loss and damages to the hard disk drives in the storage systems Damage to the hard disk drives from fire suppression systems or pneumatic sirens will void the hard disk drive warranty Mechanical environmental conditions Item Operating Non operating Guaranteed value to...

Page 61: ...y capacity required for adding shard memory function vary depending on storage system models Software Items affected by shared memory capacity ShadowImage TrueCopy Universal Replicator global active device The number of pairs that can be created For more information refer to the specific software user guide Volume Migration Volume Migration V2 The number of migration plans that can be executed con...

Page 62: ...emory function to shared memory capacity Table 22 Shared memory function and shared memory capacity Shared Memory Function VSP F350 VSP F370 Base 34 0 GiB 72 0 GiB Extension1 42 5 GiB 94 0 GiB Extension2 54 5 GiB 110 0 GiB Extension3 Table 23 Minimum cache memory capacity required for shared memory function Shared Memory Function VSP F350 VSP F370 Base 64 GiB 128 GiB Extension1 128 GiB 128 GiB Ext...

Page 63: ...nd Suite or Hitachi Ops Center Administrator Allow communication to the storage system from the SVP TCP IP port assignments When you install your storage system default ports must be opened to allow for incoming and outgoing requests Review the following ports before you install the storage system to avoid conflicts between the TCP IP port assignments used by the storage system and those used by o...

Page 64: ...that Device Manager Storage Navigator uses refer to the Device Manager Storage Navigator online help 5989 Used by SMI S 10995 TCP Device Manager Storage Navigator and Hitachi suite components 23015 Used for Web browser communications 23016 Used for Web browser communications via SSL 28355 TCP Device Manager Storage Navigator Secure 31001 Used for communication by Hitachi Command Control Interface ...

Page 65: ...oade r RMI 51099 No RMIClassLoade rHttps RMI SSL 5443 No RMIIFRegist RMI 1099 No PreRMIServer RMI 51100 513551 No Automatic allocation 88 02 0x xx 00 or later DKCManPrivate RMI 11099 N A 88 02 0x xx 00 or later SMI S SLP SLP 427 Yes only if SMI S is not used SMIS_CIMOM SMI S 5989 62441 Yes only if SMI S is not used 88 02 0x xx 00 or later Automatic allocation 88 02 0x xx 00 or later CommonJettySt ...

Page 66: ... available for host connections vary based on the controller model Fibre Channel SFP adapters are used to connect to your Fibre Channel switch and hosts iSCSI ports come in optical and copper RJ 45 interfaces and are used to connect to your Ethernet switch and hosts Each controller also has A SAS port for connection to an external drive tray An RJ 45 10 100 1000 bps user LAN port for performing ma...

Page 67: ...rk segment as the SVP and storage system Note The SVP running Windows 10 operating system does not provide a way to disable Spanning Tree Protocol STP If your network has BPDU enabled to prevent loops connect the user LAN port on controllers 1 and 2 to an Ethernet switch instead of connecting them to SVP LAN 3 and LAN 4 ports Virtual SVP connectivity requires all of the following ESX Server VMware...

Page 68: ... for storage system installation vary according to the specific storage system and network configuration Fibre Channel and iSCSI cables are used to connect the controllers to a switch or host Serial attached SCSI SAS cables are used to connect drive trays to controllers and other drive trays Appendix D Data and power cables Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 68 ...

Page 69: ... the iSCSI 10 Gb RJ 45 ports on each controller to a host computer direct connection or to several host computers via an Ethernet switch SAS SAS optical Connects the controller to a drive tray or a drive tray to another drive tray Two SAS cables are provided with each drive tray Ethernet RJ 45 Four shielded Category 5e or 6a Ethernet cables are required for connecting the SVP to the controllers ma...

Page 70: ...ts Fiber Channel connections to hosts For details about configuring FC host connections see the Provisioning Guide Note Due to high speed serial data transfer via Fibre Channel use high quality FC cables that comply with the Fibre Channel PH standard The following figure shows FC direct connection and FC connection through a switch Fibre Channel cables Appendix D Data and power cables Hitachi Virt...

Page 71: ...ps 984 25 ft 300 m 1640 4 ft 500 m 3280 8 ft 10 km 4 Gbps 493 ft 150 m 1246 72 ft 380 m 1312 3 ft 400 m 8 Gbps 164 04 ft 50 m 493 ft 150 m 623 36 ft 190 m 16 Gbps 114 8 ft 35 m 328 08 ft 100 m 410 1 ft 125 m 32 Gbps 65 62 ft 20 m 229 7 ft 70 m 328 08 ft 100 m Fibre Channel cables Appendix D Data and power cables Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 71 ...

Page 72: ...nt to DXLC 2P PC xxM GC50 125 2SR OMx 50 125 μm 62 5 125 μm Multimode Wavelength 850 nm LC connector LC connector LC LC cable longwave DXLC 2PS SPC xxM SMC 10 125 2SR 9 125 μm Singlemode Wavelength 1300 nm The following figure shows the connector used for optical interfaces Fibre Channel cables Appendix D Data and power cables Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 72 ...

Page 73: ...ns to hosts For details about configuring iSCSI host connections see the Provisioning Guide Cable specifications for iSCSI optical interface Cable type Interface Cable mode name Nominal Cable Connector One side Other side LC LC cable Optical Equivalent to DXLC 2P PC xxM GC50 125 2SR OMx 50 125 mm Multimode Wavelength 850 nm LC connector LC connector iSCSI cables Appendix D Data and power cables Hi...

Page 74: ... that connects the storage system optical iSCSI ports LC connector type Connector type LC duplex receptacle connector Interval 6 25 mm flat type two rows Cable specifications for 10 Gbps iSCSI copper interface iSCSI cables Appendix D Data and power cables Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 74 ...

Page 75: ...s 1000BASE T STP use an STP cable that suppresses radio noise RJ 45 Category 6a LAN cable 50 m 10 Gbps 10GBASE T STP use an STP cable that suppresses radio noise RJ 45 The following figure shows a 10 Gbps iSCSI cable iSCSI cables Appendix D Data and power cables Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 75 ...

Page 76: ...1 MIB II RFC 1757 RMON RFC 1901 SNMPv2 iSCSI specifications Item Specification Comments iSCSI target function Supported N A iSCSI target function Supported TrueCopy only iSCSI ports 2 per interface board Maximum 24 per iSCSI system Connection methods Direct and switch connections Host connections 255 maximum per iSCSI port With Linux software initiator the maximum number decreases Path failover HD...

Page 77: ... A Tagged VLAN Supported N A IPv4 Supported N A IPv6 Supported Note the following precautions When iSCSI Port IPv6 is set to Enabled if the IPv6 global address is set to automatic the address is determined by acquiring a prefix from an IPv6 router If the IPv6 router does not exist in the network the address cannot be determined As a result an iSCSI connection might be delayed When an iSCSI Port IP...

Page 78: ...torage system from communicating through the new port number iSCSI name Both iqn3 and eui4 types are supported The unique iqn value is automatically set when a target is made iSCSI name is configurable Error recovery level 0 zero Error recovery by retrying from host Does not support Level 1 and Level 2 Header digest Supported Detects header error or data error with iSCSI communication The storage ...

Page 79: ...k Manager Pass switching is achieved Not supported on Windows Vista and Windows 7 operating systems 2 IP Security Authentication and encryption of IP packets The storage system does not support IPsec 3 iqn iSCSI Qualified Name The iqn consists of a type identifier iqn a date of domain acquisition a domain name and a character string given by the individual who acquired the domain Example iqn 1994 ...

Page 80: ...eyond their recommended bend radius The following table provides general guidelines for minimum bend radius values but you should consult the recommendation of your cable manufacturer Cable type Minimum bend radius values Fibre Channel 40 mm 1 73 inch iSCSI optical 40 mm 1 73 inch Category 5 Ethernet Four times the outside diameter of the cable SAS 40 mm 1 73 inch Managing cables Appendix D Data a...

Page 81: ...cables over time Therefore do not allow cables to sag through gaps in your supports Place drop points in your supports that permit cables to reach racks without bending or pulling Unintentional unplugging or unseating of a power cable can have a serious impact on the operation of an enterprise storage system Unlike data cables power connectors do not have built in retention mechanisms to prevent t...

Page 82: ...des a variety of power cables that facilitate using storage systems around the world Hitachi power cables meet the safety standards for the country for which they are intended Power cable assemblies For information about racks and power distribution units PDUs refer to the Hitachi Universal V2 Rack Reference Guide Hitachi power cables consist of three parts Plug Male connector for insertion into t...

Page 83: ... 240 10 16 CEI 23 50 Italy 200 240 10 16 CEI 23 50 7 Argentina 200 240 10 15 IRAM 2073 Australia 200 240 10 15 AS 3112 China 200 240 10 16 GB 1002 New Zealand 200 240 10 15 AS 3112 8 Denmark 200 240 10 DK 2 5 Israel 200 240 10 16 SI 32 94 Europe 200 240 CEE 7 7 105 India 200 240 6 16 IS 1293 South Africa 200 240 10 16 SABS 164 11 Switzerland 200 240 10 SEV 1011 126 International 200 240 20 IEC 309...

Page 84: ...land for a true 16 A application 7 4 wire three phase and earth Physical variations connector size and color indicate amperage rating 8 5 wire three phase earth and neutral Physical variations connector size and color indicate amperage rating AC connections The following table shows and describes the types of AC connections on your storage system Description Receptacle Input rating Reference stand...

Page 85: ...rating Reference standards BS 1363 200V 240V 5 BS 1365 3 IEC 83 AS 3112 200V 240V 6 AS C112 Cable and connector AC connections Appendix D Data and power cables Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 85 ...

Page 86: ...ny given time the voltage across the hot and neutral conductors can be anywhere between its peak maximum and zero Electrical conductors must be large to meet high amperage requirements Three phase power uses three cycles that are 120 degrees out of phase which never allows the voltage to drop to zero The more consistent voltage derived from the three hot conductors results in smoother current flow...

Page 87: ...e device into the PDU Balance the electrical current load between available PDUs Americas single phase PDU 1P30A 8C13 3C19UL P The following figure and table describe the specifications of the PDU Figure 1 Americas PDU for the Hitachi Universal V2B Rack Single phase PDU 1P30A 8C13 3C19UL P Part Number Region Quantity Power input per PDU Power output per PDU Total rack amperage available 1P30A 8C1 ...

Page 88: ... phase PDU 1P30A 15C13 3C19UL P Part number Region Quantity Power input per PDU Power output per PDU Total rack amperage available 1P30A 15C 13 3C19UL P Americas 4 rack 2 side Single phase 208V 30A 24A rated 60Hz Delta wYe N A NEMA L6 30P input power plug 4 5 m 14 76 feet cable 15 IEC C13 3 IEC C19 sockets Max allowable current 24A 5kVA 48A 10kVA Americas single phase PDU 1P30A 15C13 3C19UL P Appe...

Page 89: ...C1 3 3C19UL P Americas 6 rack 3 side Three phase 208V 3P 30A 24A rated 60Hz Delta wYe Delta NEMA L15 30P input power plug 4 5 m 14 76 feet cable 8 IEC C13 3 IEC C19 sockets Max allowable current 38 4A 8kVA 115A 24kVA Americas three phase PDU 3P30A 15C13 3C19UL P The following figure and table describe the specifications of the PDU Americas three phase PDU 3P30A 8C13 3C19UL P Appendix E Power distr...

Page 90: ...30A 24A rated 60Hz Delta wYe Delta NEMA L15 30P input power plug 4 5 m 14 76 feet cable 15 IEC C13 3 IEC C19 sockets Max allowable current 38 4A 8kVA 77A 16kVA Americas three phase PDU 3P30A 24C13 6C19UL P The following figure and table describe the specifications of the PDU Americas three phase PDU 3P30A 24C13 6C19UL P Appendix E Power distribution units for Hitachi Universal V2B Rack Hitachi Vir...

Page 91: ...4A rated 60Hz Delta wYe Delta NEMA L15 30P input power plug 4 5 m 14 76 feet cable 24 IEC C13 6 IEC C19 sockets Max allowable current 38 4A 8kVA 38 4A 8kVA APAC and EMEA single phase PDU 1P32A 9C13 3C19CE P The following figure and table describe the specifications of the PDU APAC and EMEA single phase PDU 1P32A 9C13 3C19CE P Appendix E Power distribution units for Hitachi Universal V2B Rack Hitac...

Page 92: ... 6A rated 50Hz 60Hz Delta wYe N A IEC309 P N E input power plug 4 5 m 14 76 feet cable 9 IEC C13 3 IEC C19 sockets Max allowable current 25 6A 5 9kVA 77A 17 6kVA APAC and EMEA single phase PDU 1P32A 18C13 3C19CE P The following figure and table describe the specifications of the PDU APAC and EMEA single phase PDU 1P32A 18C13 3C19CE P Appendix E Power distribution units for Hitachi Universal V2B Ra...

Page 93: ...25 6A rated 50Hz 60Hz Delta wYe N A IEC309 P N E input power plug 4 5 m 14 76 feet cable 18 IEC C13 3 IEC C19 sockets Max allowable current 38 4A 8 8kVA 77A 17 6kVA APAC and EMEA three phase PDU 3P16A 9C13 3C19CE P The following figure and table describe the specifications of the PDU APAC and EMEA three phase PDU 3P16A 9C13 3C19CE P Appendix E Power distribution units for Hitachi Universal V2B Rac...

Page 94: ...8A rated 50Hz 60Hz Delta wYe wYe IEC309 3P N E input power plug 4 5 m 14 76 feet cable 9 IEC C13 3 IEC C19 sockets Max allowable current 38 4A 8 8kVA 115A 26 4kVA APAC and EMEA three phase PDU 3P16A 15C13 3C19CE P The following figure and table describe the specifications of the PDU APAC and EMEA three phase PDU 3P16A 15C13 3C19CE P Appendix E Power distribution units for Hitachi Universal V2B Rac...

Page 95: ... 8A rated 50Hz 60Hz Delta wYe wYe IEC309 3P N E input power plug 4 5 m 14 76 feet cable 15 IEC C13 3 IEC C19 sockets Max allowable current 38 4A 8 8kVA 77A 17 6kVA APAC and EMEA three phase PDU 3P32A 24C13 6C19CE P The following figure and table describe the specifications of the PDU APAC and EMEA three phase PDU 3P32A 24C13 6C19CE P Appendix E Power distribution units for Hitachi Universal V2B Ra...

Page 96: ...ed 50Hz 60Hz Delta wYe wYe IEC309 3P N E input power plug 4 5 m 14 76 feet cable 24 IEC C13 6 IEC C19 sockets Max allowable current 77A 17 6kVA 77A 17 6kVA Americas APAC and EMEA three phase PDU 3P30A 243 69CE UL P The following figure and table describe the specifications of the PDU Americas APAC and EMEA three phase PDU 3P30A 243 69CE UL P Appendix E Power distribution units for Hitachi Universa...

Page 97: ...as APAC and EMEA 2 rack 1 side Three phase 400 415V max 30 32A 24A rated 50Hz 60Hz Delta wYe wYe IEC309 3P N E input power plug 4 5 m 14 76 feet cable 24 IEC C13 6 IEC C19 sockets Max allowable current 77A 17 6kVA 77A 17 6kVA Americas APAC and EMEA three phase PDU 3P30A 243 69CE UL P Appendix E Power distribution units for Hitachi Universal V2B Rack Hitachi Virtual Storage Platform F350 F370 Hardw...

Page 98: ...es must face toward the back not toward each other The area behind the storage system and between the vertical 19 inch mounting posts must be free of PDUs and cable loops Hitachi Universal V2 Rack rail kits Use rail kits to mount the Hitachi Virtual Storage Platform family storage system in a Hitachi Universal V2 Rack The following tables list the rail kit information for the specified storage sys...

Page 99: ...hi Universal V2 Rack Front door Rear door Side panels Optional must be ordered separately A3BF DR Included with rack Not included with rack must be ordered separately A quantity of two must be ordered per rack A3BF Z PAN 1200 Hitachi Universal V2 Rack accessories Appendix F Non Hitachi racks Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 99 ...

Page 100: ...rk Explanation Do not disassemble the equipment Be careful when handling heavy equipment Use caution when handling electrostatic sensitive equipment and microcircuitry Avoid placing any non essential objects or equipment onto the storage system Use caution when handling the equipment Use caution when handling equipment with movable parts Use caution when handling equipment with hot surfaces Use ca...

Page 101: ...CBSS controller CBSS controller Appendix G Warning labels on the storage system Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 101 ...

Page 102: ...CBSL controller CBSL controller Appendix G Warning labels on the storage system Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 102 ...

Page 103: ...Small form factor drive tray CBSS CBSL controller Small form factor drive tray Appendix G Warning labels on the storage system Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 103 ...

Page 104: ...Battery Battery Appendix G Warning labels on the storage system Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 104 ...

Page 105: ...oduct Recycling A nickel metal hydride battery is used in the Cache Backup Battery A nickel metal hydride battery is a resource that can be recycled When you want to replace the Cache Backup Battery call the service personnel They will dispose of it for you This nickel metal hydride battery which is designated as recycling product by a recycling promotion low must be recycled The mark posted on th...

Page 106: ...egulatory compliance This equipment has been tested and certified for compliance with the following standards Appendix I Regulatory compliance Hitachi Virtual Storage Platform F350 F370 Hardware Reference Guide 106 ...

Page 107: ...emission certifications EN55022 2010 CE marking EU EN55024 2010 EN61000 3 2 2006 A1 A2 EN61000 3 3 2013 Safety certifications UL and CSA 60950 1 2007 cTuVus United States of America and Canada EN60950 1 2006 A1 1 A1 A12 A2 TUV Germany IEC60950 1 2005 A 1 A2 N A All CB countries IEC60950 1 2005 A 1 A2 S_Mark Argentina TP TC 004 2011 EAC Russia CNS 14336 1 BSMI Taiwan EN60950 1 2006 A1 1 A1 A12 A2 C...

Page 108: ...red to correct the interference at his own expense Testing was done with shielded cables Therefore in order to comply with the FCC regulations you must use shielded cables with your installation If trouble occurs in another configuration a user might be requested to take appropriate preventative measures RKU CBSS dense intermix drive tray flash module drive tray 2 small form factor drive trays 1 l...

Page 109: ...antara Corporate Headquarters 2535 Augustine Drive Santa Clara CA 95054 USA HitachiVantara com community HitachiVantara com Contact Information USA 1 800 446 0744 Global 1 858 547 4526 HitachiVantara com contact ...