Part
Number
Region
Quantity
Power
input per
PDU
Power output
per PDU
Total rack
amperage
available
NEMA
L6-30P
input
power plug
4.5 m
(14.76 feet)
cable
Americas single-phase PDU 1P30A-15C13-3C19UL.P
The following figure and table describe the specifications of the PDU.
Figure 2 Americas PDU for the Hitachi Universal V2B Rack (Single-phase PDU
1P30A-15C13-3C19UL.P)
Part
number
Region
Quantity
Power input
per PDU
Power
output per
PDU
Total rack
amperage
available
1P30A-15C
13-3C19UL.
P
Americas
4/rack
2/side
Single phase
208V, 30A (24A
rated) 60Hz
Delta/wYe: N/A
NEMA L6-30P
input power
plug
4.5 m (14.76
feet) cable
15 IEC C13
+ 3 IEC C19
sockets
Max
allowable
current:
24A
5kVA
48A (10kVA)
Americas single-phase PDU 1P30A-15C13-3C19UL.P
Appendix E: Power distribution units for Hitachi Universal V2B Rack
Hitachi Virtual Storage Platform F350, F370 Hardware Reference Guide
88