![Hitachi SJ700 Series Software Instruction Manual Download Page 120](http://html.mh-extra.com/html/hitachi/sj700-series-software/sj700-series-software_instruction-manual_140536120.webp)
Chapter 8 Appendix
8 - 4
(2) A parameters
Display
code
Function name
Range of setting
Minimum
unit
Setting during
operation
(allowed or not)
Updating during
operation
(allowed or not)
A098 Deceleration curve setting
0 (linear), 1 (S curve), 2 (U curve),
3 (inverted-U curve), 4 (EL-S curve)
−
×
×
A101
[OI]-[L] input active range start
frequency
0 to 40000
0.01 (Hz)
×
○
A102
[OI]-[L] input active range end
frequency
0 to 40000
0.01 (Hz)
×
○
A103
[OI]-[L] input active range start
current
0 to "[OI]-[L] input active range end current"
1 (%)
×
○
A104
[OI]-[L] input active range end
current
"[OI]-[L] input active range start current" to 100
1 (%)
×
○
A105
[OI]-[L] input start frequency
enable
0 (external start frequency), 1 (0 Hz)
−
×
○
A111
[O2]-[L] input active range start
frequency
-40000 to 40000
0.01 (Hz)
×
○
A112
[O2]-[L] input active range end
frequency
-40000 to 40000
0.01 (Hz)
×
○
A113
[O2]-[L] input active range start
voltage
-100 to 02 end-frequency rate
1 (%)
×
○
A114
[O2]-[L] input active range end
voltage
"02 start-frequency rate" to 100
1 (%)
×
○
A131
Acceleration curve constants
setting
1 (smallest swelling) to 10 (largest swelling)
−
×
○
A132
Deceleration curve constants
setting
1 (smallest swelling) to 10 (largest swelling)
−
×
○
A141
Operation-target frequency
selection 1
0 (digital operator), 1 (keypad potentiometer), 2 (input
via O), 3 (input via OI), 4 (external communication),
5 (option 1), 6 (option 2), 7 (pulse-string frequency input)
−
×
○
A142
Operation-target frequency
selection 2
0 (digital operator), 1 (keypad potentiometer), 2 (input
via O), 3 (input via OI), 4 (external communication), 5
(option 1), 6 (option 2), 7 (pulse-string frequency input)
−
×
○
A143 Operator
selection
0 (addition: A141 + A142), 1 (subtraction: A141 - A142),
2 (multiplication: A141 x A142)
−
×
○
A145 Frequency to be added
0 to 40000
0.01 (Hz)
×
○
A146
Sign of the frequency to be
added
0 (frequency c A145),
1 (frequency command - A145)
−
×
○
A150 EL-S-curve acceleration ratio 1
0 to 50
1 (%)
×
×
A151 EL-S-curve acceleration ratio 2
0 to 50
1 (%)
×
×
A152 EL-S-curve
deceleration ratio 1
0 to 50
1 (%)
×
×
A153 EL-S-curve
deceleration ratio 2
0 to 50
1 (%)
×
×
*1
Display
code
Inverter
capacity
Setting range
Under 55(kW)
0 to 100
75 to 132(kW)
0 to 80
A054/A057
Over 160(kW)
0 to 35
*2
Display
code
Inverter
capacity
Setting range
Under 55(kW)
5 to 150
75 to 132(kW)
5 to 100
A059
Over 160(kW)
5 to 30
Summary of Contents for SJ700 Series Software
Page 8: ...Contents vii ...
Page 10: ......
Page 16: ...Chapter 1 Introduction 1 6 ...
Page 18: ......
Page 24: ...Chapter 2 Creation and Execution of a User Program 2 6 ...
Page 26: ......
Page 30: ...Chapter 3 Syntax 3 4 ...
Page 32: ......
Page 54: ......
Page 102: ......
Page 110: ...Chapter 6 Interface with the Inverter 6 8 ...
Page 112: ......
Page 115: ...Chapter 8 Appendix 8 1 Inverter Parameters and Available Settings 8 1 ...
Page 116: ......