CHAPTER5 OPERATING
13
5.3 PZD-part
In this chapter the process data part (PZD) of a PPO is discussed.
The PZD part consists of a fixed part (PZD1-2, all PPO’s) and a parameterable part (PZD 3-10, shaded grey
above, PPO 2, 4 and 5).
In the fixed part, control word and speed reference are transferred to the inverter while status word and actual
output frequency are transferred from the inverter.
In the parameterable part, PZD word 3-10, the user can configure what parameters that should be transferred
to/from the inverter every bus-cycle (see chapter 5.3.3 and Appendix).
5.3.1 Control- / status word (STW/ZSW)
This section describes how to operate the inverter with the control-/status word. With the control word the
Profidrive state-machine (Figure 5-2) is controlled, the status word is reflecting the state of the inverter.
Profidrive Control Word (STW):
The control word is used to send control commands to the inverter (PLC->Inverter).
Control word
Bit
Value
Meaning
Remark
1
On1
Inverter can be started if all other start conditions are fulfilled.
0
0
OFF1
Normal stop; uses deceleration time specified in “1
st
Deceleration time” (F003).
1
ON2
Inverter can be started if all other start conditions are fulfilled.
1
0
OFF2
Inverter coast to stop. Returns to
Switch-on inhibit
state.
1
ON3
Inverter can be started if all other start conditions are fulfilled.
2
0
OFF 3
Quick stop that uses deceleration time specified in “2
nd
deceleration time”
(F203).
1
Operation enabled
Inverter can be started if all other start conditions are fulfilled.
3
0
Operation disabled
Inverter coast to stop (Enter
Inhibit operation
state).
1
Condition for operation
Inverter can be started if all other start conditions are fulfilled.
4
0
Ramp generator disabled
Output frequency is set to zero. Inverter remains in the running state.
1
Ramp generator enabled
Inverter can be started if all other start conditions are fulfilled.
5
0
Stop ramp generator
Actual output frequency is frozen. A change to frequency set-point has no
effect.
1
Enable set-point
Inverter can be started if all other start conditions are fulfilled,
using “1
st
Acceleration time” (F002).
6
0
Inhibit set-point
Normal stop that uses deceleration time specified in “1
st
deceleration time”.
1
Acknowledge
Fault is acknowledged on positive edge, i.e. bit 7=0 then 1
(
Enter Switch-on inhibited
state).
7
0
No function
1
Inching 1 ON
Inverter accelerates to inching set-point 1.
Profidrive must be in “Enable o
peration
” state.
Parameter “Jogging frequency” specifies the jogging set-point (A038).
8
0
Inching 1 OFF
Inverter brakes as fast as possible and goes into the “
Enable operation”
state.
9
Not used
1
Data valid
The control word and frequency set-point (from Profibus) are activated.
Please refer to chapter 2.2.4.
10
0
Data invalid
The control word and frequency set-point (from Profibus) are not valid.
Please refer to chapter 2.2.4.
1
REV
Inverter will operate in reverse motion.
Please note that a negative reference and reverse selected will result in inverter
running forward.
11
0
FWD
Inverter will operate in forward motion.
1
Commands invalid
The fieldbus module will not write any commands to the inverter. This makes it
possible to operate motor via the terminal input (if A002 is set to “Terminal”).
12
0
Commands valid
The fieldbus module can write commands to the inverter (if A002 is set to
“Terminal”).
1
Reference invalid
The fieldbus module will not write any reference to the inverter.
13
0
Reference valid
The fieldbus module can write reference to the inverter (if A001 is set to
“Operator”).
14,
15
Not used