CHAPTER 5 LONWORKS COMMUNICATION FUNCTION
16
5.4.12 Parameter value, Write (UNVT_sj300 nciWriValue)
This nci is used as a value input for the user selected parameter nciWriAdr. The SCPT uses the following
format:
struct{
unsigned long int lowWord; //Used for byte and word data
unsigned long int highWord; //Used for highWord when
transmitting 4 byte data
}UNVT_sj300
Scaling is defined in SJ300/L300P user’s manual.
5.4.13 Generic Parameter address setting, Read (SNVT_count nciRdAdr)
Chooses the parameter address (16 bits) to be read from the drive. Addresses in the 0xFFFF**** area can
not be reached.
Default value: 0x0070
Valid range: See SJ300/L300P manual.
5.4.14 Speed setpoint scaling default value (SNVT_lev_percent)
This parameter is used for setting its value to nviDrvSpeedScale (see chapter5.1.3) on every startup.
Default value : 0
Valid range : -163-163%
5.4.15 Power Up Out Time (SNVT_time_sec nciPwUpOutTm)
When the power is ON, the inverter and PC do not communicate each other during setting time.
This setting is used for avoiding data collision, when the power is ON.