CHAPTER 5 LONWORKS COMMUNICATION FUNCTION
11
Example (2) : nviInvSetFreq = 0 to 400
When nviInvSetFreq is at 60Hz and nviDrvSpeedScale is 100%, the inverter is in forward run at 60Hz.
Valid Range: -163.84 to163.83%
Default Value: Is defined by nciDrvSpeedScale (Refer to 5.4.14).
Scaling: See chapter 6.1.4
5.2.5 Emergency Override (SNVT_hvac_emerg nviEmergOverride)
When EMERG_SHUTDOWN command is inputted, the inverter executes the deceleration stop and also the
value in EMERG_SHUTDOWN is supported but the other values are not supported.
(Deceleration time is dependant on Ramp Down Time (Refer to chapter 5.4.10))
Value
Definition
Contents
Support
0
EMERG_NORMAL
No emergency mode
Yes
1
EMERG_PRESSURIZE
Emergency pressurize
No
2
EMERG_DEPRESSURIZE
Emergency depressurize
No
3
EMERG_PURGE
Emergency purge mode
No
4
EMERG_SHUTDOWN
Emergency shutdown
Yes
5
EMERG_FIRE
−
No
0xFF
EMERG_NUL
Value not available
No