4 USER GUIDE
- 34 -
(4) Remote station (MELSEC) transmission/reception start address setup areas
The areas for setting the transmission/reception start address of the remote station (MELSEC)
are indicated below. Up to four areas can be specified for each of write and read. The
contents of these areas are merely used for the area check that is performed at the beginning of
communications (for checking whether the S10mini and MELSEC agree in bit/word area).
Therefore, the data will not be written to the areas specified as explained here and the data will
not be read from the areas specified as explained here. The areas used for transmissions from
the MELSEC and the areas used for the storage of data received by the MELSEC both depend
on the design of the MELSEC application program.
Register
number
Area name
Setting range
Remarks
BD020
Cyclic write area 1
*1
BD021
Cyclic write area 2
*1
BD022
Cyclic write area 3
*1
BD023
Cyclic write area 4
*1
BD024
Cyclic read area 1
*1
BD025
Cyclic read area 2
*1
BD026
Cyclic read area 3
*1
BD027
Cyclic read area 4
Bit registers: X, Y, M, B, and F
registers
Word registers: D, W, and R registers
*1
BD028
Reserved for future use
To be fixed at 0.
BD029
Reserved for future use
To be fixed at 0.
BD02A
Reserved for future use
To be fixed at 0.
BD02B
Reserved for future use
To be fixed at 0.
BD02C
Reserved for future use
To be fixed at 0.
BD02D
Reserved for future use
To be fixed at 0.
BD02E
Reserved for future use
To be fixed at 0.
BD02F
Reserved for future use
To be fixed at 0.
*1 The simultaneous use of bit and word registers is an allowable practice. For the procedure for
specifying the write/read areas, see item (7).
NOTE
Although the parameters are checked at startup, they are not checked for a
duplicate of the areas 1 through 4 and write/read areas. The user should
exercise area management so as to avoid area duplication.
The above area setting and the setting indicated under "Local station
transmission/reception start address setup areas" must agree in bit/word type.
If they do not agree, a parameter setting error occurs and SV.LINK stops its
communications.
Summary of Contents for S10Mini SV.Link
Page 1: ......
Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 11: ...1 BEFORE USE ...
Page 15: ...2 SPECIFICATIONS ...
Page 19: ...3 NAMES AND FUNCTIONS OF EACH PART AND CABLING ...
Page 24: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 25: ...4 USER GUIDE ...
Page 55: ...5 OPERATION ...
Page 58: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 59: ...6 MAINTENANCE ...
Page 70: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 71: ...7 APPENDIX ...