2 SPECIFICATIONS
- 7 -
2.2.2 Line
specifications
Item Specification
Transmission method
Serial (bit serial) transmission
Electrical interface
Conforming to IEEE 802.3 (conforming to CSMA/CD)
standard
Coding system
Manchester
Protocol
UDP/IP or high-speed I/O communication protocol
Maximum number of connectable units 10BASE-5: 1 per segment
10BASE-T: 1 per hub
Maximum number of stations
2 per network (one unit of S10mini and MELSEC each)
Connection cable
10BASE-5 coaxial cable
: Up to 500 m per segment
10BASE-5 transceiver cable : Up to 50 m
10BASE-T twisted-pair cable: Up to 100 m per segment
Data transmission rate
10 Mbps
2.2.3 High-speed I/O communication specifications
Item Specifications
Communication style
Peer-to-peer communication (between the S10mini and
MELSEC)
Applicable Mitsubishi sequencer
Sequencer or motion controller in which the MELSEC
A Series Ethernet interface unit (Model AJ71E71 or
equivalent) is mounted
Port number used
Fixed at 34100 (decimal notation; for both the S10mini
and MELSEC)
IP address used
Any address is usable. However, the S10mini and
MELSEC must agree with each other in network
address.
Supported communication function
Cyclic communication based on the MELSEC's fixed-
buffer communication function (asynchronous)
S10mini communication areas
Bit registers: X, Y, J, Q, R, M, G, and E registers
Word registers: DW and FW registers
Up to four areas can be specified for transmission and
reception each.
Transmission/reception
communication word count
Bit register: 40 words max.
Word register: 256 words max.
(256 words maximum for a total of four areas)
Communication cycle
Determined according to the transmission/reception
word count, communication delay time, and MELSEC
response time. See Section 4.11, "Communication
Cycle."
I/O data consistency guarantee unit
One word
Note: For the fixed-buffer communication function (asynchronous) of MELSEC, refer to the
MELSEC documentation.
Summary of Contents for S10Mini SV.Link
Page 1: ......
Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 11: ...1 BEFORE USE ...
Page 15: ...2 SPECIFICATIONS ...
Page 19: ...3 NAMES AND FUNCTIONS OF EACH PART AND CABLING ...
Page 24: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 25: ...4 USER GUIDE ...
Page 55: ...5 OPERATION ...
Page 58: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 59: ...6 MAINTENANCE ...
Page 70: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 71: ...7 APPENDIX ...