TEST RUNNING
6.5 Safety and Control Device Setting
Table 3. Safety and Control Device Setting
Models
RUA-13AT3S
RUA-15AT3S
RUA-20AT3S
RUA-30AT3S
For Compressor
Models
500DH/750EL
750EL
1000EL
1000EL
High Pressure Switch
Automatic Reset, Non-Adjustable
Cut-Out
kg/cm
2
G
30
30
30
30
kPa
3,040
3,040
3,040
3,040
Cut-In
kg/cm
2
G
24
24
24
24
kPa
2,470
2,470
2,470
2,470
Overcurrent Relay
Automatic Reset, Non-Adjustable
220V 60Hz
A
32/41
41
52
60
Discharge Gas Thermostat
Cut-Out
°C
130
130
130
130
Cut-In
°C
100
100
100
100
Crankcase Heater
Capacity
W
40/60
60
60
---
CCP Timer
Non-Adjustable
For Compressor
min.
3
3
3
3
3.5
min.
4
4
4
4
For Evaporator Fan Motor
Manual Reset, Adjustable
Overcurrent Relay
220V 60Hz
A
9
9
14
21
For Condenser Fan Motor
Internal Thermostat
Automatic Reset, Non-Adjustable
Cut-Out
°C
160
160
160
160
Cut-In
°C
125
125
125
125
For Control Circuit Fuse
Capacity
A
5
5
5
5
Pressure Control Valve
Cut
–
out
Cut-in
kg/cm
2
G
kPa
kg/cm
2
G
kPa
---
---
---
---
---
---
---
---
---
---
---
---
30
3,040
24
2,470