無論是大室、中室、小室、極小室對於洩漏冷媒量皆以 2

0kg

來計算。

Maximum permissible concentration (kg / m

3

R410A(

 (0.3k /   

)

 

 

 

 

 

1)  Fully open the gas line stop valve. 
2)  After cooling operation starts, connect the gauge manifold 

using charging hoses with a refrigerant charging cylinder   
to the check joints of the liquid line stop valve to charge 
refrigerant. (Refrigerant charging quantity error tolerance:   
±0.5kg around.) In the meantime, the liquid line stop valve 

   is slightly open. 
3)  Fully open the liquid line stop valve after completing 

refrigerant charge. 

4)  Please be sure to perform the air-tight test. 

 
 
 
 
 
 
 
 

 

5)  The check joints on the accumulator is used to fill 

refrigeration oil, do not use for other purposes. 

(10) Caution of The Refrigerant Leakage 

When an air conditioner is installed in a room, in case of refrigerant leakage, refrigerant concentration must not exceed the 
maximum permissible concentration. 

The products use non-flammable, non-toxic safe refrigerant R410A. If leakage occurs and gas fills a room, it may cause 
suffocation. Especially for multiple indoor units and outdoor units with long-distance piping connection, the amount of 
refrigerant is more than individual air-conditioner. So make sure the indoor unit installed in the room, 

even in case of 

refrigerant leakage, the refrigerant concentration should never exceed the maximum permissible concentration. 

Please calculate the refrigerant concentration by the following formula

 

 

The total amount of charged refrigerant (kg)

 

     

Room space for each indoor unit (m

3

 

If a room’s refrigerant concentration is more than the maximum permissible concentration and the air conditioner still need 
to be installed, please choose a treatment method according to the following

 

1.Set refrigerant leakage detector alarm and link it to mechanical ventilation devices. (See below) (Cooling capacity per ton 

should be more than 0.4 m

3

/min ventilation capacity. Cooling capacity is shown in following table according to the outdoor 

unit capacity.)   

2.Set the effective ventilation outlet between adjacent rooms (The outlet area need to be more than 0.15% floor area on the 

upper and lower of the door), so that the leakage of refrigerant concentration can drop less than the maximum permissible 
concentration. 

 

                       

 
 
 
 
   

New refrigerant R410A product notes

Since R410A is a non-azeotropic refrigerant, when leakage occurs, the proportion of 
mixture will change. Do not charge new refrigerant directly; the whole system must 
be re-processed.

 

Outdoor 

Unit 

Cooling 

Capacity 

R410A 

 

冷媒配管作業要領圖 

Outdoor Unit

Gas Piping

Liquid Piping

Branch Pipe

Refrigerant

 

Piping Work Diagram

 

Indoor Unit 

Indoor Unit

Pipe connection part 
union and flare nut, be 
sure to do insulation 
process.

 

Nitrogen Bottle (Use 
for Brazing and 
Air-Tight Test) 

(Note

1) Whether it is a large room, medium room, small room or tiny small room, 

the amount of refrigerant leakage is all 30kg. 

(Note

2) The concentration must not exceed the maximum permissible concentration 

0.3kg / m

3

.

The total amount of refrigerant within the system: 30kg

Example 

Indoor

Outdoor

Large Room 

Medium Room

Small Room 

Ventilation
Outlet 

Refrigerant Pipe 

mechanical ventilation devices

refrigerant 

leakage detector alarms devices 

Excess or insufficient additional refrigerant will result in 
compressor failure or other abnormal conditions, be sure 
to charge refrigerant according to the calculated values. 

Liquid piping must be insulated. (To prevent poor 
performance and low pressure pipe surfaces condensation.)

Be sure to check the refrigerant leakage. If a large amount of 
refrigerant leaks, it will cause the following phenomena

 

1. Lack of oxygen. 
2. Harmful gases would occur if a fire was being used in the 

room.

Liquid Line Stop Valve

Gas Line Stop Valve

Manifold Gauge 

Vacuum Pump

Refrigerant 
Cylinder (R410A)
 
Weight Scale 

Thermal Insulation 
Material Wrapping 
 

Outdoor Unit 

Capacity (HP) 

Cooling Capacity 

(ton) 

R410A 

8~12 4.11 

14~16 6.48 

18 6.54 
20 8.22 

22~26 10.59 
28~32 12.96 

24 13.02 
26 13.08 

28~40 14.70 

42 14.76 

44~46 17.13 

48 17.19 

50~52 19.56 

54 19.62 

 

Summary of Contents for RAM-10MQ

Page 1: ...al and user s manual to customers Meaning of symbols DANGER Indicates a hazardous situation which If not avoided may result in death or serious injury Mandatory Symbol indicate instructing behavior of general users Mandatory Symbol indicate grounding must be performed for machine with grounding terminal Indicate prohibited item About Electrical Works DANGER z Assign an authorized dealer to perform...

Page 2: ...AM 14MQ D RAM 16MQ D RAM 12MQ D RAM 12MQ D RAM 12MQ D RAM 12MQ D RAM 10MQ D RAM 12MQ D RAM 10MQ D RAM 12MQ D HP 42 44 46 48 50 52 Model RAM 16MQ D RAM 18MQ D RAM 18MQ D RAM 18MQ D RAM 18MQ D RAM 18MQ D RAM 14MQ D RAM 14MQ D RAM 14MQ D RAM 16MQ D RAM 18MQ D RAM 18MQ D RAM 12MQ D RAM 12MQ D RAM 14MQ D RAM 14MQ D RAM 14MQ D RAM 16MQ D HP 54 Model RAM 18MQ D RAM 18MQ D RAM 18MQ D For 20 54HP please re...

Page 3: ...ain When hanging outdoor unit please do not tie the ropes on wooden base or the inside of hanging square holes Example RAM 8MQ D 2 Transportation and Handling 木台 吊掛孔 錯誤 吊掛孔 繩索 繩索 正確 繩索位置 錯誤 繩索 CORRECT INCORRECT INCORRECT Rope Wooden Base Rope Rope Square Hole Square Hole Corrugated Paper Frame Do not remove corrugated paper and plastic bands Do not apply any force to this place Both Sides Rope Woo...

Page 4: ...onnect Bending Expanding Tool If using the 1 2H pipe it can not be processed Please use the elbow welding to connect Expanding Tubes Torque Wrench R410A forΦ12 7 Φ15 88 spanner size is up 2mm existent products can not be used Connection of Flare Nut For Φ6 35 Φ9 53 Φ19 05 spanner size is the same Brazing Tool Perform correct brazing work Brazing for Tubes Nitrogen Gas Strict control against contam...

Page 5: ... of joints With the design pressure changes the connection pipe elbow etc thickness are also changes When using 1 2H material the bending and flaring can not be processed so please follow the table below to choose the minimum thickness that appropriate to the connecting pipe Please note that there are several changes in flare nut size Connection minimum thickness mm Diameter R410A Diameter R410A 6...

Page 6: ...ar the unit it may result in fire 11 Do not install the outdoor unit where there is a high concentration of oil spray salty air or harmful gases such as sulfurous gas 12 Do not install the outdoor unit where the electromagnetic wave directly radiates to the electrical box 13 To avoid the influence of electromagnetic waves wave generating machines such as radio should be kept 3 meters from electrom...

Page 7: ...d the limits add h1 2mm and h2 2mm on the front side and air inlet side respectively For the multiple installation one group allows 6 outdoor units max The required space between each set is at least 1m The walls should be partially open if the unit is surrounded by walls in four directions Note If the distance between unit and obstacles ceilings is less than 1 500mm or the space is closed set up ...

Page 8: ...oot of the outdoor unit deformation 4 Anchor Bolt Installation Dimensions RAM 8 12MQ D RAM 14 18MQ D Unit mm 5 Confirmation of drainage 1 When Defrosting operate the condensation water will be discharged Select the best area for drainage The drain hole position is shown below RAM 8MQ D 12MQ D RAM 14MQ D 18MQ D Refrigerant Gas Piping Connection Hole 60 Refrigerant Liquid Piping Connection Hole 47 C...

Page 9: ... gas liquid pipes from the Piping Connection Kit 1 to the First Multi kit should be increased one size with the reducer field supplied 3 The size of multi kit between the indoor units should be the same as the size of the indoor unit pipes 4 When the liquid piping length is longer than 15m please useφ9 53 pipe field supplied 5 Keep the straight line distance longer than 500mm or more after the pip...

Page 10: ...nit is higher than outdoor unit H 1 40m Height difference between Each indoor unit H 2 15m Height difference between Each outdoor unit H 5 0 1m Multi kit and Piping First Multi kit Outdoor Unit HP Gas Liquid Piping Diameter mm L 1 100m Gas Liquid Piping Diameter mm L 1 100m Multi Kit Type 8 19 05 9 53 22 2 12 7 E NP282S 10 22 2 9 53 25 4 12 7 12 14 25 4 12 7 28 6 15 88 E NP452S 16 28 6 12 7 31 75 ...

Page 11: ...22 2 25 4 28 6 31 75 Liquid Piping 12 7 15 88 19 05 a 100m Gas Piping 19 05 22 2 25 4 28 6 Liquid Piping 9 53 12 7 15 88 HP 20 20 22 24 26 28 30 32 Combination Model Master A 10MQ D 12MQ D 14MQ D 14MQ D 14MQ D 14MQ D 16MQ D 16MQ D Slave B 10MQ D 8MQ D 8MQ D 10MQ D 12MQ D 14MQ D 14MQ D 16MQ D Piping Connection Kit E NP692S E NP902S Piping Size a 100m Gas Piping 31 75 34 9 Liquid Piping 19 05 22 2 a...

Page 12: ... a 100m Gas Piping 34 9 41 3 Liquid Piping 22 2 a 100m Gas Piping 31 75 38 1 Liquid Piping 19 05 b Gas Piping 28 6 31 75 Liquid Piping 15 88 19 05 c Gas Piping 25 4 28 6 Liquid Piping 12 7 15 88 d Gas Piping 25 4 28 5 Liquid Piping 12 7 15 88 e Gas Piping 22 2 25 4 22 2 25 4 28 6 Liquid Piping 9 53 12 7 9 53 12 7 15 88 Please follow the requirement when performing multi kit piping Remove the spare...

Page 13: ...e piping connection kit is placed higher than the outdoor unit piping connection keep 300mm max between the piping connection kit and the bottom of the outdoor unit Also provide an oil trap min 200mm between the piping connection kit and the outdoor unit 分歧管 室外機 各室外機間高度差 連接至室內機 L L Piping Length LA LB LC 10m Master A Slave B Slave C L HP Master A Slave B Slave C 0 1m 以 Indoor Unit Side Piping Conn...

Page 14: ...n oil trap min 200mm should be provided for the gas pipe so that accumulation of refrigerant oil may not occur 4 Ensure the direction of outdoor unit pipes is horizontal or with downward gradient towards the indoor unit side to avoid accumulating refrigerant oil in the pipe 5 For maintenance if the pipe is placed in front of the outdoor unit secure at least 500mm between the outdoor units and the ...

Page 15: ...d Supplied Piping Connection Kit 1 Gas Piping Connection Kit 2 Gas Piping Connection Kit 1 Liquid Piping Connection Kit 2 Liquid Gas Line Refrigerant Piping Connection Liquid Line Refrigerant Piping Connection Downward Piping Connection 3 Pipe Connection Position Model A B C D Gas Line Refrigerant Piping Connection Liquid Line Refrigerant Piping Connection Gas Line Refrigerant Piping Connection Li...

Page 16: ...ranch and the indoor units Only one main branch is allowed and total indoor unit capacity should be in the range of 40 to 60 for each route after the first main branch Indoor Unit Total Capacity 50 Indoor Unit Total Capacity 50 71Type 71Type 71Type 71Type y 71Type 71Type Indoor Unit Total Capacity 33 Indoor Unit Total Capacity 67 140Type 71Type 71Type 71Type 140Type 140Type 第 3 分歧 第 2 主分歧 Best ins...

Page 17: ... to connect in five directions front rear left right or bottom side from bottom base 2 Please weld the flange combination and connection pipe in advance and then lock with the gas stop valve 3 In order to prevent rainwater and insects from entering into the unit please fill the gap between piping hole and pipes with insulator Pipe Size Φ22 2 Φ25 4 Max Interval 1 0m 1 5m 傾斜角度 15 以內 15 傾斜角度 底座 底面側 下...

Page 18: ...reasing performance and dewing on the surface of the pipe Required Torque 8 Vacuum Work About the details of stop valve operation please refer to the nameplate inside service cover 1 Connect a manifold gauge to the check joints at the both sides Continue vacuum pumping work until the pressure reaches 0 1MPa or lower for one to two hours After vacuum pumping work shut the manifold valve stop the va...

Page 19: ...itional Refrigerant kg Additional Amount of Refrigerant for Liquid Pipe W1 kg Pipe Size Pipe Length m The Amount of Refrigerant Per Meter Additional Amount of Refrigerant W1 kg Total Amount of Additional Refrigerant for Liquid Pipe Additional Amount of Refrigerant for Indoor Unit W2 kg 8HP 10HP each indoor unit needs addition 1 kg of refrigerant There is no addition of refrigerant for the unit les...

Page 20: ...is shown in following table according to the outdoor unit capacity 2 Set the effective ventilation outlet between adjacent rooms The outlet area need to be more than 0 15 floor area on the upper and lower of the door so that the leakage of refrigerant concentration can drop less than the maximum permissible concentration New refrigerant R410A product notes Since R410A is a non azeotropic refrigera...

Page 21: ...pacity A RAM 8MQ 230V 24 3 30 40 60 35 8 3 5 2 Core Shielded Twist Pair Cable 0 75 mm2 Total Length Below 1000m RAM 10MQ 29 50 RAM 12MQ 40 100 75 100 50 14 5 5 RAM 14MQ 49 100 60 22 RAM 16MQ 55 RAM 18MQ 59 RAM 8MQD 380V 15 4 30 30 30 20 5 5 2 0 RAM 10MQD 17 RAM 12MQD 23 40 60 30 8 3 5 RAM 14MQD 28 50 45 14 RAM 16MQD 31 RAM 18MQD 34 100 60 Note 1 Please refer to the table above to select earth leak...

Page 22: ...電斷路器 1 230V ELB 主開關 保險絲 漏電斷路器 3 230V ELB 控制器線 遙控器 0 號室內機 控制器線 遙控器 1 號室內機 接地 保險絲 主開關 室外機 1 3 親機 R S T 1 3 2 4 接地 室外機 2 3 子機 R S T 1 3 2 4 漏電斷路器 3 230V ELB 保險絲 主開關 現地配線 現地準備 端子台 基板 另購品 TB PCB 操作回路連接電線 DC5V 漏電斷路器 1 230V ELB 主開關 保險絲 漏電斷路器 3 4W 380V ELB 控制器線 遙控器 0 號室內機 配電箱 控制器線 遙控器 1 號室內機 配電箱 接地 保險絲 主開關 室外機 1 3 親機 1 3 2 4 接地 室外機 2 3 子機 1 3 2 4 漏電斷路器 ELB 保險絲 主開關 現地配線 現地準備 端子台 基板 另購品 TB PCB 操作回路連接電線 DC5V...

Page 23: ...are wrong connected transmission circuit fuse on the PC board will be cut off Therefore make the terminal board wiring correct and set the DSW10 Pin 2 switch on the PC board to ON It can restore the circuit that has been cut off If the 230V or 380V in the terminal board are wrong connected again the PC board will break L L L L L L L L L L L L L L N L L N L L N L L N L L N 1 2 Master A 4 3 No 0 No ...

Page 24: ... tightening torque please refer the following table Size Tightening Torque N m M4 1 0 1 3 M5 2 0 2 4 M6 4 0 5 0 M8 9 0 11 0 M10 18 0 23 0 Completely seal the conduit tube after wiring to avoid entering water Example RAM 8MQD PCB 1 TB 2 TB 1 Earth Wire Terminal Electric Box Earth Wire Transmission Cable Terminal Board Power Supply Terminal Board Power Supply Power Supply Connection Port Φ52 Transmi...

Page 25: ...peration maintenance Setting of the outdoor unit test operation Factory Setting Cooling Test Operation Compressor Is Forced To Stop Emergency test Operation maintenance When setting the following items please set the following PIN to ON Factory Setting Setting Items Outdoor Unit No Setting Master A Slave B Slave C When the outdoor unit is a combination unit please be sure to do this setting Cautio...

Page 26: ...tdoor unit The unit before leaving the factory No 1 pin of DSW 10 is set at the ON side In the case that the outdoor units quantity in the same H link or H link ll is 2 or more set No 1 pin of DSW 10 at the OFF side from the 2 nd unit Mean that the number of end terminal resistance required only one If only one outdoor unit is used no setting is required Indoor Indoor Indoor Indoor Outdoor Outdoor...

Page 27: ... control switch When cooling operation test run it should be at room temperature DB 21 C WB 15 5 C outside air temperature DB 5 C or more Outside air temperature below DB 5 C air conditioner can not be operated Using a remote controller to operate more than one indoor unit check the connected number of indoor unit is indicated on LCD If no indication appears or the number of the units indicated is...

Page 28: ...id pipe thermistor 25 Abnormal heat exchanger gas pipe thermistor 29 Abnormal low pressure sensor 31 System Incorrect capacity setting of outdoor and indoor units Incorrect capacity setting of combination excessive or insufficient indoor unit total capacity 35 Incorrect setting of indoor unit no Duplication of indoor unit No in the same refrigerant cycle 36 Incorrect indoor unit combination Indoor...

Page 29: ... indoor unit connection number setting More than 17 indoor units are connected to single refrigerant system non H Link II system Note If there s any transmission abnormality connector loss loose incorrect wiring and disconnection between indoor unit and remote controller remote control operation indicator will flash once every 2 seconds 4 Finally please deliver the guarantee operation manual and i...

Page 30: ...ge Gas Temperature Td Liquid Pipe Temperature Te 8 Check Pressure Discharge Pressure Pd MPa Suction Pressure Ps MPa 9 Check Voltage Rated Voltage V Operating Voltage L1 L2 V L1 L3 V L2 L3 V Starting Voltage V Phase Imbalance 10 Check Compressor Input Running Current Input kW Running Current A 11 Is the refrigerant charge adequate 12 Do the operation control devices operate correctly 13 Do the safe...

Page 31: ...31 MEMO ...

Page 32: ...32 66MP1373 Printed in Philippines ...

Reviews: