13
底座
前後框
回油彎折高度
200mm以上
回油彎折高度
200mm以上
回油彎折高度
200mm以上
300mm以下
300mm以下
連接至室內機
連接至室內機
300mm以下
Liquid
Piping
Q’ty
1 1
Type
E-NP692S E-NP902S
Gas
Piping
Q’ty 1
1
Liquid
Piping
Q’ty
1 1
(2) Caution about Outdoor Unit Installation
1.
Align the outdoor units and locate large capacity Master (A) on the indoor unit side. Piping length between Piping
Connection Kit 1 and each outdoor unit should be less than 10m.
2.
Place the piping connection kit lower than the outdoor unit piping connection.
In case that the piping connection kit is placed higher than the outdoor unit piping connection, keep 300mm (max.)
between the piping connection kit and the bottom of the outdoor unit. Also, provide an oil trap (min.200mm) between the
piping connection kit and the outdoor unit.
分歧管
室外機
各室外機間高度差
連接至室內機
L
L
Piping Length
:
LA
≦
LB
≦
LC
≦
10m
Master
(A)
Slave
(B)
Slave
(C)
L
HP
:
Master (A)
≧
Slave (B)
≧
Slave (C)
0.1m 以
Indoor Unit Side
Piping
Connection
Kit
Keep the pipes straight at least 0.5m
after piping connection kits.
Max. Lift Difference
between Outdoor
Unit =
0.1m
Master
(A)
Slave
(B)
Slave
(C)
Indoor Unit Side
Indoor Unit Side
Oil Trap
Min. 200mm
Max.300mm Max.300mm
Max.300mm
Base
Bottom of
Outdoor Unit
Oil Trap
Min. 200mm
Oil Trap
Min. 200mm