[ Situation ] The compressor will not run (the same state as the thermometer turned off), the product receives remote control
signals normally. The self-diagnosis lamp (LD301) of the outdoor unit blinks once or becomes turned off.
[ Estimated failure locations ]
Room temperature thermistor, heat exchanger thermistor
Microcomputer peripheral circuit
[ Diagnosis flow ]
Initiating troubleshooting
3. Failure phenomenon: The compressor will not run.
Is the "timer lamp" (orange) of the indoor unit
blinking?
Yes
Yes
Yes
No
No
No
Check for failures according to the self-
diagnosis display.
Did the self-diagnosis lamp (LD301) of the outdoor
unit blink once or become turned off?
Check for failures according to the self-
diagnosis display.
Remove the connector (CN4) of the room
temperature thermistor and heat exchanger
thermistor and measure the thermistor resistance.
Did the reading roughly agree with the resistance
values indicated in the right-hand figure?
Replace the "room temperature and heat
exchanger thermistors".
Thermistor characteristics (resistance)
Ther
mistor resistance
Thermistor temperature
Replace the "indoor electrical parts".
·
·
- 83 -
Summary of Contents for RAK-18QXB
Page 2: ... DANGER 2 ...
Page 24: ... 24 ...
Page 25: ... 25 ...
Page 26: ... 26 ...
Page 27: ... 27 ...
Page 28: ... 28 ...
Page 31: ...WIRING DIAGRAM RAK 18QXB RAK 25RXB RAK 35RXB RAK 50RXB 31 ...
Page 33: ...CIRCUIT DIAGRAM MODEL RAK 18QXB POWER FOR CLEANNESS 33 ...
Page 34: ...CIRCUIT DIAGRAM MODEL RAK 25RXB RAK 35RXB RAK 50RXB POWER FOR CLEANNESS 34 ...
Page 68: ...69 68 ...
Page 71: ...3 and page 38 7 71 ...
Page 73: ...57 73 ...
Page 74: ... 74 ...
Page 92: ...RAK 18QXB RAK 25RxXB HHAW NO 0088E 1 RAK 35RXB RAK 50RXB 92 ...