Hitachi RAC-S10H2 Installation Manual Download Page 2

< S695: 

A

 >

•  Please mount the Outdoor unit of stable ground to prevent vibration and increase
 of 

noise 

level.

Decide the location for piping after sorting out the different types of pipe available.

• When removing side cover, please pull the handle after undoing the hook by pulling

it downward. Reinstall the side cover in the reverse order of the removal.

CONDENSED WATER DISPOSAL OF OUTDOOR UNIT

• There is holes on the base of Outdoor unit for condensed water to exhaust.
• In order to flow condensed water to the drain, the unit is installed on a stand or a

block so that the unit is 100mm above the ground as shown figure.  Join the drain
pipe to one hole.

• Cover the drain hole with a bush. To install the bush, put it on the drain hole as

shown in the figure and press the both sides of the bush to fit into the hole.
After installation, check whether the drain pipe and bush cling to the base firmly.

• Install the outdoor unit horizontally and make sure that condensate drains away.
• In case of using in chilly area

Especially, in case that there are many snows by very cold in chilly area, condensed
water freezes on the base and may result not to drain.  In this case, please remove
the bush and the drain pipe at the bottom of unit.  (Left and center near discharge
portion of air, each 1 place).  It becomes smooth drain.
Ensure that the distance from the drain hole to the ground is 250 mm or more.

OUTDOOR UNIT

 CAUTION

• Do not touch the suction

port, bottom surface, or
aluminum fin of the outdoor
unit.
Failure to do so may cause
an injury.

 CAUTION

• Remove burr and jagged edge will cause leakage.
• Point the side to be trimmed downwards during trimming to prevent copper

chips from entering the pipe.

• Before flaring, please put on the flare nut.

Outer                           A (mm) Rigid Flaring Tool

Diameter (¯ )

For R410A tool

For R22 tool

6.35 (1/4")

0 - 0.5

1.0

9.52 (3/8")

0 - 0.5

1.0

2

Pipe Connection

 CAUTION

• In case of removing flare nut of a indoor unit, first remove

a nut of small diameter side, or a seal cap of big diameter
side will fly out. Free from water into the piping when
working.

• Be sure to tighten the flare nut to the specified torque with

a torque wrench.
If the flare nut is overtightened, the nut may be split after a
long period has passed, and may cause a refrigerant  leak.

• Please be careful when bending the copper pipe.
• Screw in manually while adjusting the center. After that, use a torque wrench to

tighten the connection.

INSTALLATION OF REFRIGERATING PIPES AND AIR REMOV

A

L

Small diameter side

6.35 (1/4")

13.7 – 18.6 (140 – 190)

Large diameter side

9.52 (3/8")

34.3 – 44.1 (350 – 450)

Small diameter side

6.35 (1/4")

19.6 – 24.5 (200 – 250)

Large diameter side

9.52 (3/8")

19.6 – 24.5 (200 – 250)

Valve core cap

12.3 – 15.7 (125 – 160)

Outer diameter

of pipe (ø)

Torque N·m

(kgf·cm)

Valve
head cap

3

Remove of Air From The Pipe And Gas Leakage Inspection

AIR REMOVAL

Procedures of using Vacuum Pump for Air Removal

As shown in right figure, remove the cap
of valve core.  Then, connect the charge
hose. Remove the cap of valve head.
Connect the vacuum pump adapter to the
vacuum pump and connect the charge
hose to the adapter.

1

Fully tighter the "Hi" shuttle of the manifold
valve and completely unscrew the "Lo"
shuttle. Run the vacuum pump for about
10-15 minutes, then completely tighten the
"Lo" shuttle and switch off the vacuum
pump.
• Loosen the spindle of the service valve

with small diameter by 1/4 turn and
tighten the spindle immediately after 5
to 6 seconds.

• Remove the charging hose from the

service valve.

2

Completely unscrew the spindle of the
service valve (at 2 places) in anticlockwise
direction to allow the flow of refrigerant
(using Hexagonal Wrench key).

3

Tighten the cap of valve head. Check the
cap's periphery if there is any gas leakage.
The task is then completed.

4

Gas leakage inspection

Please use gas leakage detector to check if leakage
occurs at connection of Flare nut as shown on the
right.

If gas leakage occurs, further tighten the connection
to stop leakage.

1

Preparation of Pipe

• Use a pipe cutter to cut the copper pipe and remove burr.

CONNECTION OF POWER CORD

WARNING

If you cannot attach the side plate due to the connection cord, please
press the connecting cord in the direction to the front panel to fix it.

Be sure that the hooks of the side cover fixed in certainly. Otherwise water
leakage may occur and this causes short circuit or faults.

The connecting cord should not touch to service valve and pipes. (it
becomes high temperature in heating operation.)

Wiring of the Outdoor Unit

•  Please remove the side cover for wire connection.

Checking for the electric source and the voltage range

• Before installation, the power source must be checked and necessary wiring work must

be completed. To make the wiring capacity proper, use the wire gauge list below for the
wiring from house distribution fuse box to the outdoor unit in consideration of the blocked
rotor current.

IMPORTANT

Wire length

Wire gauge

up to   6m

1.6mm

2

up to 15m

2.5mm

2

up to 20m

4.0mm

2

• Investigate the power supply capacity and other

electrical conditions at the installing location.
Depending on the model of room air conditioner to be
installed, request the customer to make arrangements
for the necessary electrical work etc.
The electrical work includes the wiring work up the
outdoor unit. In localities where electrical conditions
are poor, use of a voltage regulation is recommended.

• Install outdoor for the room air conditioner within the

reaching range of the line cord.

IMPORTANT

Fuse Capacity

16A time delay fuse

• Pull at the 

1

 and 

2

 in the directions as shown by

arrows to remove the cover.

Wiring of The Indoor Unit

• For wire connection of the Indoor unit, you need to remove the front cover

under the body of the unit and terminal cover.

, the low cover

• Remove the cover from the terminal base and screw the cable.

 WARNING

• The naked part of the wire core should be 10mm fix it to the terminal tightly. Then

try to pull the individual wire to check if the contact is tight. Improper insertion may
burn the terminal.

• Be sure to use only wire specified for the use of air-conditioner.
• Please refer to the manual for wire connection and the wiring technique should

meet the standard of the electrical installation.

• There is an AC voltage drop between the LN terminal if the power is on. Therefore,

be sure to remove the plug from its socket.

 WARNING

• Leave some space in the connecting cord for maintenance

purpose and be sure to secure it with the cord band.

• Secure the connecting cord along the coated part of the wire

using the cord band. Do not exert pressure on the wire as this
may cause overheating or fire.

WARNING

• THIS APPLIANCE MUST BE

EARTHED.

Procedures of Wiring

Detail of cutting the connecting cord

FINAL ST

A

GE OF INST

ALLA

TION

1

Power Source And Operation Test

Power Source

 WARNING

• Never remodel the power plug nor extend the long-distance

cord.

• Keep additional length for the power cord and do not render

the plug under external force as this may cause poor contact.

• Do not fix the power cord with U-shape nail.
• The power cable easily generates heat. Do not bring the

cable together with a wire or vinyl tie.

Operation test

• Please ensure that the air conditioner is in normal operating

condition during the operation test.

• Explain to your customer the proper operation procedures as

described in the user' s manual.

• If the indoor unit won't operate, check the cable for correct

connection.

• Turn on the lamp in the room where the indoor unit is installed

and check the remote controller for normal operation.

2

Installation of Remote Controller

• The remote controller can be placed in its holder which is fixed

on wall or beam.

• To operate the remote controller at its holder, please ensure that

the unit can receive signal transmitted from the controller at the
place where the holder is to be fixed. The unit will beep when
signal is received from the remote controller. The signal
transmission is weaken by the fluorescent light. Therefore, during
the installation of the remote control holder, please switch on
the light, even during day time, to determine the mounting location
of the holder.

The controller must be hooked onto the hook at the lower part
of the holder. Push in the remote controller in the direction as
shown in figure below.

Force-cooling operation

• When the service switch

of the outdoor unit is
pressed for 1 or more
seconds, the force-
cooling operation starts.
Use this mode when
performing the failure
diagnosis or collecting
refrigerant into the
outdoor unit.

 CAUTION

• Do not operate the unit for more than 5 minutes

while the spindle of the service valve is closed.

How to remove the front cover

1

Remove the front panel

Please remove and attach the front panel by both hands.

How to Attach the Front Cover

1

Check that the drain pan is securely attached.

2

After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
the front cover to lock the claws.

3

Tighten the two screws.

After opening the front panel by both hands.

1

Undo the right arm while pushing it inside.

2

Slide the front panel to right as shown in figure. Then remove
while pulling it to front.

2

Remove the filters.

3

After removing two screws, pull the center of the front cover
towards you and release the claws.

4

Pull the side faces (lower sections) of the front cover towards
you as shown in the figure and remove the cover.

• Push up the [PUSH] sections at the bottom of the indoor unit and

pull the bottom plate towards you. Then the claws are released
from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)

HOW TO REMOVE INDOOR UNIT

After completing the service switch
operation, be sure to keep the
switch pressed for one or more
seconds and stop the force-cooling
operation.

For more details, refer to the Installation Manual for Cold Area.

Pull downward

Please face this side (suction side)
of the unit to the wall.

Please remove side cover
when connecting the piping
and connecting cord.

0

 DRAIN PIPE

9

 BUSH

DRAIN HOLE

above
100mm

Push

Push

BASE

DRAIN HOLE

9

 BUSH

Outer diameter: 16 mm or more

Copper pipe

Trimming tool

A

Die

Die

Copper pipe

• Please use

exclusive tool for
refrigerant R410.

Torque
wrench

Flare nut

Wrench

When the meter reaches -101KPa
(-76cmHg) during pumping fully
tighten the shuttle.

Meter showing
pressure

Closed

R410A
Manifold
valve

Vacuum

pump

Valve

Charge
hose

Vacuum
pump
adapter

When pumping starts, slightly
loosen the flare nut to check of
air sucked in. Then tighten the
flare nut.

The body of service
valve

Cap of
valve core

Hexagonal
wrench Key

Cap of valve
head

Cap of valve
head

Valve

cover

Earth terminal

After remove the screw
and terminal cover, and
put the connecting cords
and fix the terminal cover
with screw.

Earth

Terminal cover

Connecting cord

Screw

ø1.6 or 

ø2.0

Indoor Unit

Outdoor Unit

Connecting Cord

30mm

10mm

10mm

70mm

10mm

50mm

10mm

50mm

Green + Yellow

Green + Yellow

Green + Yellow

Strip wires

Indoor Unit

Outdoor Unit

Remote controller

Screw (2 pieces)

Holder for Remote
Controller

Service switch (If the switch is
pressed for one or more seconds, the
force-cooling operation starts. If the
switch is pressed for additional one or
more seconds, the operation stops.)

Screw

Cover

4

Install the filter.

5

Slide the shafts of the right and left arms on the front panel
along the steps to insert the shafts into the holes till they stop.
After checking that the shafts are securely inserted, close the
panel.

[Push] mark positions

AC 220-230V
1ø 50Hz

Step

Shaft

Hole

L(A) N(B) C D

D
C

Method to remove the low cover

Summary of Contents for RAC-S10H2

Page 1: ...t 2 300 mm or more from the floor Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood Do not install at a location where there is flammable gas steam oil and smoke The location must be convenient for water drainage Place the Outdoor unit and its connecting cord at least 1 m away from the antenna or signal line of television radio or telephone This is to avoid ...

Page 2: ... the body of the unit and terminal cover the low cover Remove the cover from the terminal base and screw the cable WARNING The naked part of the wire core should be 10mm fix it to the terminal tightly Then try to pull the individual wire to check if the contact is tight Improper insertion may burn the terminal Be sure to use only wire specified for the use of air conditioner Please refer to the ma...

Page 3: ... máxima del tubo 20 m más de 50 mm si se instala en un balcón UNIDAD INTERIOR 1 Perforación de la pared e instalación del soporte de pared y la tubería de protección PRECAUCIÓN El drenaje del depósito de agua de la unidad interior se puede hacer por la izquierda Por lo tanto el soporte de pared debe fijarse horizontalmente o ligeramente inclinado hacia el lado de la manguera de drenaje De lo contr...

Page 4: ... en la que está instalada la unidad interior y compruebe que el mando a distancia funciona correctamente Remoción de la cubierta frontal Inserción de la cubierta frontal Mando a distancia Tornillo 2 piezas Soporte del mando a distancia ÚLTIMA ETAPA DE LA INSTALACIÓN 1 Fuente de alimentación y prueba de funcionamiento ADVERTENCIA No manipule la clavija del cable de alimentación ni extienda el cable...

Page 5: ... Utilizzare il flessibile di scarico isolato per la tubazione interna prodotto commerciale oltre 100mm oltre 300mm oltre 50mm lasciare la massima distanza possibile oltre 200mm Assicurarsi di sigillare completamente qualsiasi pertura con il mastice Lunghezza massima tubo 20 m UNITÀ INTERNA 1 Installazione di sospensore foratura del muro e tubo di protezione CAUTELA Il drenaggio del contenitore del...

Page 6: ...o anteriore verso di sé come mostrato nella figura e rimuovere il coperchio Asta Telecomando Vite 2 pezzi Supporto per il telecomando Valvola Foro Reggispinta CAUTELA Non toccare il bocchettone di aspirazione la superficie inferiore o l aletta di alluminio dell unità esterna In caso contrario potrebbero verificarsi lesioni personali 9 BOCCOLA 9 BOCCOLA Spinta Spinta FORD DI SCARICO Diametro estern...

Page 7: ... ñ ñ ñ ñ ÂÍ ÚÙ Ì Ù 9 0 ÂÚÈ Ï Ì ÓÔÓÙ È ÛÙË Û ÛÎÂ Û ÙË Â͈ÙÂÚÈÎ ÌÔÓ Â ÂÚ ÙˆÛË ÙÚÔÊÔ ÔÛ fi ÙËÓ ÂÛˆÙÂÚÈÎ ÌÔÓ ÙÚ ÍÙ ÙÔ Î ÏÒ ÈÔ ÚÂ Ì ÙÔ fi ÙË ı ÛË ÙÔ ÛÙË ÂÍÈ ÛÙËÓ ÚÈÛÙÂÚ ÏÂ Ú ÙË ÂÛˆÙÂÚÈÎ ÌÔÓ ˆÏËÓÒÛÂÈ Ì ΠÙ ı ÓÛË ÚÔ Ù Ûˆ fi ÚÈÛÙÂÚ À Ú Ô Ó 6  ÈÙÚ fiÌÂÓ ΠÙ ı ÓÛÂÈ ÁÈ ÙÈ ÛˆÏËÓÒÛÂÈ ÚÔ Ù Ûˆ ÚÔ Ù Ûˆ fi ÚÈÛÙÂÚ ÔÚÈ fiÓÙÈ fi ÂÍÈ ÔÚÈ fiÓÙÈ fi ÚÈÛÙÂÚ Î Ù ÎfiÚ Ê ÚÔ Ù Î Ùˆ fi ÂÍÈ Î Ù ÎfiÚ Ê ÚÔ Ù Î Ùˆ fi ÚÈÛÙÂÚ ÈÎfiÓ ÁÈ ÙËÓ ...

Page 8: ...ÔÏÔÁÈÎ ÂÚÁ Û Â Ô Ú ÂÈ Ó ÂÎÙÂÏ ÛÂÈ Ô ÂÏ ÙË ÂÚÈÏ Ì ÓÔ Ó ÙÈ ÂÚÁ Û Â Ì ÚÈ ÙËÓ Â͈ÙÂÚÈÎ ÌÔÓ Ÿ Ô Ë ÚÔ ÂÓ Â Ó È ÛÙ ıÂÚ Û ÓÈÛÙ Ù È Ë Ú ÛË Ú ıÌÈÛÙ Ù ÛË ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ Ú ÂÈ Ó Á ÓÂÈ Û ÛËÌÂ Ô Ô Ó Êı ÓÂÈ ÙÔ Î ÏÒ ÈÔ ÙË ÁÚ ÌÌ ªËÓ ÔÛ Ó ÚÌÔÏÔÁ Ù ÙÔ ÛÌ ÙÔ Î Ïˆ Ô ÚÂ Ì ÙÔ Î È ÌËÓ ÙÂÓÙÒÓÂÙ ÙÔ Ì ÎÚ Î ÏÒ ÈÔ Ê ÛÙ ÚÎÂÙfi Ì ÎÔ ÛÙÔ Î ÏÒ ÈÔ Î È ÌËÓ ÛΠ٠ÂÛË ÛÙÔ ÛÌ ÁÈ Ù Ùfi Ì ÔÚÂ Ó Ô ËÁ ÛÂÈ ÛÂ Î Î Â Ê ªËÓ ÛÙ...

Page 9: ...uit commercial Plus de 100mm Plus de 300mm Plus de 50mm distance de dégagement maximale souhaitée Plus de 200mm Veiller à boucher complètement tous les espaces au mastic Longueur maximale du tuyau 20 m APPAREIL D INTÉRIEUR 1 Installation de la plaque de fixation percée du mur et pose de la gaine de protection ATTENTION Vous pouvez vidanger le conteneur d eau de l appareil intérieur par la gauche P...

Page 10: ...ne parvenez pas à fixer le panneau latéral en raison du câble de connexion enfoncez ce dernier dans le sens du panneau avant Veillez à ce que les crochets du panneau latéral soient fermement fixés sinon une fuite d eau peut survenir et occasionner un court circuit ou des pannes Le câble de connexion ne doit pas toucher la vanne de service ni les tuyaux Il chauffe en cours de fonctionnement Vérific...

Reviews: