– 97 –
CHECKING THE REFRIGERATING CYCLE
1.
Troubleshooting procedure (No operation, No heating, No cooling)
Connect U,V,W phase leads to the
power module again and operate the
air conditioner.
Gas leaks.
Repair and seal refrigerant.
Is the self-diagnosis lamp mode as
shown on the right?
YES
Gas leaking
(less than 4kg/cm
2
G)
(less than 0.39 MPaG)
Normal
(0.39-0.98 MPaG)
(4-10 kg/cm
2
G)
Perform a final check of operation.
When the
self-diagnosis lamp
lights in the same
condition as above.
The compressor is defective. Replace it
and seal refrigerant.
If the compressor checker for an
inverter type air conditioner is
available, re-check using it.
( )
(JUDGING BETWEEN GAS LEAKAGE AND
COMPRESSOR DEFECTIVE)
Blinking
off
Time until the
lamp lights
Approx. 10 seconds
Approx.
10
seconds
Approx.
10
seconds
Within
Approx.
30
seconds
Compressor
Compressor
Gas
leakage
Possible
malfunctioning
part
LD301
Self-
diagnosis lamp
Lighting mode
Blinks
2 times
Blinks
3 times
Blinks
4 times
Blinks
5 times
Blinks
6 times
Blinks
8times
Stop to operate and check the gas
pressure in balancing mode.
Checking the system power module
Summary of Contents for RAC-70YH7
Page 35: ... 35 CIRCUIT DIAGRAM Remote Control ...
Page 36: ... 37 CIRCUIT DIAGRAM MODEL RAS 70YH7 ...
Page 37: ... 39 CIRCUIT DIAGRAM MODEL RAC 70YH7 ...
Page 39: ... 42 MODEL RAC 70YH7 P W B MAIN ...
Page 40: ... 43 P W B IPM BOARD P W B NF BOARD ...
Page 42: ... 45 51 53 53 55 57 49 29 66 23 25 25 25 25 ...
Page 46: ... 53 ...
Page 56: ... 66 220 240 220 240 3 15A RAC 70YH7 ...
Page 57: ... 67 AC220 240V DC260 360V ...
Page 58: ... 68 C001 C007 C015 C016 C026 C027 L004 L005 J25 J25 J25 J23 J58 J25 ...
Page 60: ... 70 ...
Page 61: ... 71 ...
Page 62: ... 72 3 15A Fuse ...
Page 63: ... 73 3 15A 3 15A DC260 360V ...
Page 66: ... 76 ...
Page 67: ... 77 ...
Page 68: ... 78 TROUBLE SHOOTING ...
Page 69: ... 79 DISCHARGE PROCEDURE AND METHOD TO STOP ENERGIZE THE POWER CIRCUIT ...
Page 70: ... 80 ...
Page 75: ... 85 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 80: ... 90 AC220 240V AC240V P W Bs P W Bs Replace outdoor P W B Main P W Bs ...
Page 81: ... 91 Replace outdoor P W B Main Replace fan motor Replace outdoor P W B Main ...
Page 83: ... 93 ...
Page 84: ... 94 ...
Page 86: ... 96 CHECKING THE REMOTE CONTROLLER ...
Page 92: ...PM NO 0465E Printed in Malaysia RAS 70YH7 RAC 70YH7 ...