– 92 –
1. Switch OFF main power supply.
2. Short circuit between JW001 and JW002.
3. Switch ON main power supply – LD302 will blink 1 time.
4. (Within 3 minutes) Press Test/Service Switch for 1 second or more.
5. Self-diagnosis result will be shown – LD303 will ON (LIT) and LD301 will be blinking. Then refer to diagnosis
table 2.
6. Switch OFF main power supply. Then release back JW001 and JW002 to original condition (no short
circuit condition).
*
If step No. 6 is not carried out, the system will not operate properly until 3 minutes has lapsed after
restore the power supply.
In case of service person forgot to release JW001 and JW002 to original condition;
Case 1:
If main power supply continuously ON, outdoor microcomputer will keep showing diagnosis result (LD303 will
ON and LD301 will blinks).
Case 2:
If main power supply OFF at once, then switch ON again:
a) Outdoor microcomputer will wait the self check command (by pressing test/service switch) within 3 minutes
(LD302 blinks 1 time).
If test/service signal input is not received, unit will return to normal operation mode after this 3 minutes has
lapsed. (LD302 OFF and LD301 blinks 1 time).
Case 3:
If main power supply OFF at once, then switch ON again and on indoor unit by remote control;
a) Indoor unit will receive remote control signal and send signal to outdoor unit. For the first 3 minutes, outdoor
micro-computer will ignore this indoor signal (LD302 blinks 1 time).
b) After 3 minutes has lapsed (LD302 OFF and LD301 blinks 1 time), unit will return to normal operation mode.
Summary of Contents for RAC-70YH7
Page 35: ... 35 CIRCUIT DIAGRAM Remote Control ...
Page 36: ... 37 CIRCUIT DIAGRAM MODEL RAS 70YH7 ...
Page 37: ... 39 CIRCUIT DIAGRAM MODEL RAC 70YH7 ...
Page 39: ... 42 MODEL RAC 70YH7 P W B MAIN ...
Page 40: ... 43 P W B IPM BOARD P W B NF BOARD ...
Page 42: ... 45 51 53 53 55 57 49 29 66 23 25 25 25 25 ...
Page 46: ... 53 ...
Page 56: ... 66 220 240 220 240 3 15A RAC 70YH7 ...
Page 57: ... 67 AC220 240V DC260 360V ...
Page 58: ... 68 C001 C007 C015 C016 C026 C027 L004 L005 J25 J25 J25 J23 J58 J25 ...
Page 60: ... 70 ...
Page 61: ... 71 ...
Page 62: ... 72 3 15A Fuse ...
Page 63: ... 73 3 15A 3 15A DC260 360V ...
Page 66: ... 76 ...
Page 67: ... 77 ...
Page 68: ... 78 TROUBLE SHOOTING ...
Page 69: ... 79 DISCHARGE PROCEDURE AND METHOD TO STOP ENERGIZE THE POWER CIRCUIT ...
Page 70: ... 80 ...
Page 75: ... 85 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 80: ... 90 AC220 240V AC240V P W Bs P W Bs Replace outdoor P W B Main P W Bs ...
Page 81: ... 91 Replace outdoor P W B Main Replace fan motor Replace outdoor P W B Main ...
Page 83: ... 93 ...
Page 84: ... 94 ...
Page 86: ... 96 CHECKING THE REMOTE CONTROLLER ...
Page 92: ...PM NO 0465E Printed in Malaysia RAS 70YH7 RAC 70YH7 ...