CHECKING THE REFRIGERATING CYCLE
2.96
{
30.14
}
2.62
{
26.72
}
2.31
{
23.58
}
2.03
{
20.73
}
1.78
{
18.14
}
1.55
{
15.79
}
1.34
{
13.66
}
1.15
{
11.74
}
0.98
{
10.02
}
0.83
{
8.48
}
0.70
{
7.10
}
0.58
{
5.89
}
0.47
{
4.81
}
Outdoor air
temperature
(℃)
50
45
40
35
30
25
20
15
10
5
0
-5
-10
(R410A)
The values above are the theoretical ones.
Lo
Hi
Connect U,V,W phase leads to the
power module again and operate the
air conditioner.
Is the self-diagnosis lamp mode as
shown on the right?
Stop to operate and check the gas
pressure in balancing mode.
●
Checking the power module.
The compressor is defective. Replace it
and seal refrigerant.
If the compressor checker for an
inverter type air conditioner is
available, re-check using it.
Gas leaks.
Repair and seal refrigerant.
Perform a final check of operation.
YES
Gas leaking
Lighting mode
Blinks
2 times
Blinks
3 times
Blinks
4 times
Blinks
5 times
Blinks
6 times
Blinks
8 times
LD301
Approx. 10 seconds
Compressor
Blinking
Off
Time until the
lamp lights
Possible
malfunctioning
part
Approx.
10
seconds
Approx.
10
seconds
Within
approx.
30
minutes
Gas
leakage
Compressor
Self
・
diagnosis Lamp
Outdoor
unit
Manifold
valve
When the
self-diagnosis lamp
lights in the same
condition as above.
Normal
(JUDGING BETWEEN GAS LEAKAGE AND COMPRESSOR DEFECTIVE)
Mpa(G){
kgf/cm
2
(G)
}
Charge port pressure
95
Summary of Contents for RAC-50FPA
Page 2: ...DANGER 2 ...
Page 32: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD 2 E 5 R A R r e l l o r t n o c e t o m e R 32 ...
Page 33: ...A P R 0 5 F A R L E D O M 33 ...
Page 34: ...MODEL RAC 50FPA 34 ...
Page 39: ...39 ...
Page 41: ...41 ...
Page 44: ...44 ...
Page 57: ...10 10 10 10 R921 R924 R642 R544 R542 R610 R922 DSW1 DSW1 R923 R541 R543 57 93 ...
Page 59: ... 9 9 RQWURO 3 0LFURFRPSXWHU 59 ...
Page 62: ...62 ...
Page 63: ...5 Electric expansion valve circuit 22 23 24 25 12 13 14 15 5 4 3 2 34 32 30 29 RED 63 ...
Page 64: ...3 15A Fuse Switching power source 64 ...
Page 65: ...3 15A 3 15A DC260 360V 65 ...
Page 72: ...7528 6 227 1 RA 50FPA C 72 ...
Page 74: ...74 ...
Page 75: ...7528 6 227 1 1 7 7 0 5 03 1 6 1 0 1 1 2 RAF 50RPA 7 75 ...
Page 77: ...77 78 ...
Page 78: ...78 ...
Page 85: ... 1 7 287 225 81 7 75 3 576 MODEL RAC 50FPA 85 ...
Page 87: ...9 V 3 V 3 Q L D 0 3 U R R G W X R H F D O S H 5 V 3 9 87 ...
Page 90: ... 1 7 5 027 21752 5 90 ...
Page 91: ...91 36 ...
Page 92: ...Please set the DIP switch No 6 to ON accordingly Refe to page 57 r 92 ...
Page 93: ...93 57 ...
Page 94: ...94 ...
Page 97: ...38 39 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAF 50RPA 97 ...
Page 98: ...MODEL RAF 50RPA 98 HWRAF 50NX2 A14 HBOARD AS ...