When power is supplied, the microcomputer reads the data in IC401 (E
2
PROM) and sets the preheating
activation value and the rating and maximum speed of the compressor, etc. to their initial values.
Data of self-diagnosis mode is stored in IC401; data will not be erased even when power is turned off.
Fig. 6-1
Microcomputer
External ROM
SCL
SDA
0V
0V
0V
5V
5V
5V
C401
IC401 (E
2
PROM)
R404
R403
82
81
1
2
3
4
8
7
6
5
}
The temporary switch is used to operate the air conditioner temporarily when the wireless remote control
is lost or faulty.
The air conditioner operates in the previous mode at the previously set temperature. However, when the
power switch is set to OFF, it starts automatic operation.
Fig. 7-1
TEMPORARY SW
MICROCOMPUTER
R629
SW211
Temporary
switch
0V
0V
C642
R734
54
5V
6. Initial Setting Circuit (IC401)
7. Temporary Switch Circuit
R301
5V
R305
C302
90
1
2
3
4
5
0
0 10 20 30 40
8. Room Temperature Thermistor Circuit
A room temperature thermistor circuit is shown in Fig. 8-1.
According to room temperature, the voltage of point becomes as it is shown in Fig.8-2.
Microcomputer
Room Temperature
Thermistor
V
oltage of point
(V)
(
℃
)
Room temperature
Room
temperature input
Fig. 8-1
Fig. 8-2
◯
A
0V
0V
5V
2
0
1
0
10 20 30 40
3
4
5
-10
R302
C303
R306
91
9. Heat Exchanger Thermistor Circuit
Heat exchanger temperature is noticed inside the room
(1) Preheating
(2) Low-temperature defrosts at cooling
and
dehumidification operation time.
(3) Not working of reversing valve or detection of opening of heat exchange thermistor is controlled.
According to heat exchange temperature, the voltage of point becomes as it is shown in Fig. 9-2.
Heat exchanger
thermistor
Microcomputer
Heat exchanger
input
Fig. 9-1
Fig. 9-2
V
oltage of point (V)
℃
Heat temperature ( )
◯
A
56
Summary of Contents for RAC-50FPA
Page 2: ...DANGER 2 ...
Page 32: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD 2 E 5 R A R r e l l o r t n o c e t o m e R 32 ...
Page 33: ...A P R 0 5 F A R L E D O M 33 ...
Page 34: ...MODEL RAC 50FPA 34 ...
Page 39: ...39 ...
Page 41: ...41 ...
Page 44: ...44 ...
Page 57: ...10 10 10 10 R921 R924 R642 R544 R542 R610 R922 DSW1 DSW1 R923 R541 R543 57 93 ...
Page 59: ... 9 9 RQWURO 3 0LFURFRPSXWHU 59 ...
Page 62: ...62 ...
Page 63: ...5 Electric expansion valve circuit 22 23 24 25 12 13 14 15 5 4 3 2 34 32 30 29 RED 63 ...
Page 64: ...3 15A Fuse Switching power source 64 ...
Page 65: ...3 15A 3 15A DC260 360V 65 ...
Page 72: ...7528 6 227 1 RA 50FPA C 72 ...
Page 74: ...74 ...
Page 75: ...7528 6 227 1 1 7 7 0 5 03 1 6 1 0 1 1 2 RAF 50RPA 7 75 ...
Page 77: ...77 78 ...
Page 78: ...78 ...
Page 85: ... 1 7 287 225 81 7 75 3 576 MODEL RAC 50FPA 85 ...
Page 87: ...9 V 3 V 3 Q L D 0 3 U R R G W X R H F D O S H 5 V 3 9 87 ...
Page 90: ... 1 7 5 027 21752 5 90 ...
Page 91: ...91 36 ...
Page 92: ...Please set the DIP switch No 6 to ON accordingly Refe to page 57 r 92 ...
Page 93: ...93 57 ...
Page 94: ...94 ...
Page 97: ...38 39 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAF 50RPA 97 ...
Page 98: ...MODEL RAF 50RPA 98 HWRAF 50NX2 A14 HBOARD AS ...