3. Latch-type reversing valve control circuit
・
This model comes equipped with a latch-type
reversing valve.
・
The latch-type reversing valve is so designed
that its valve is "slid" in a specified direction
according to a specific operation mode, thereby
switching freezing channels and retaining the
built-in permanent magnet.
・
The latch-type reversing valve control circuit is
so designed that, in response to an operation
command from the indoor microcomputer, the
reversing valve coil receives a current in a
specified direction according to a specific
operation mode, thereby sliding the valve.
・
The product is energized twice at increments
of 1 second as illustrated in Fig. 3-1, starting
immediately before compressor startup.
・
During forcible cooling, the product is energized
twice at increments of 1 second as illustrated in
Fig. 3-1, starting immediately after the forcible
freezing switch is turned on.
・
When stopped, the product holds the valve in
the position where it was before stoppage.
Fig. 3-1
1
2
3
4
Reversing valve
R441
DB1
Cooling/heating
switchover relay
(RL1)
Reversing valve relay
(RL2)
CN2
VH−2P
(
2P lacking
)
AC220V-230V
12V
12V
HIC
IC2
Reversing valve ON
Reversing valve cooling/
heating switchover
Cooling Lo
Heating Hi
Microcomputer
Forcible cooling
switch (test switch)
※
Timing for voltage measurement
1s
1s
1s
Reversing valve
Compressor
ON
OFF
Start
Stop
Red
Cooling/heating
relay coil
Reversing valve
relay coil
Fig. 3-2
・
Before conducting an energization check of the reversing valve, detach the connector CN2, measure the resistance at both
ends of the connector, and ensure that it is within the range [400
Ω
±
100
Ω
]. Check for energization only when the above
test proves the product to be normal. If it is abnormal, it should be a lead wire break or a reversing valve failure.
・
Voltage when measured with a tester while the reversing valve is energized (at the timing for voltage measurement)
※
Hold down the "test switch" of the outdoor electrical parts for at least 1 second.
Energization begins 1 second after the "test switch" is pressed.
Tester type
Analog tester
Connect pin
①
of the CN2 to the positive terminal of the tester.
Connect pin
④
of the CN2 of the negative terminal of the tester.
The pointer will swing in reverse direction.
The tester will display a large negative value, go back to 0 V,
and then display a negative large value.
Digital tester
Connect pin
④
of the CN2 to the positive terminal
of the tester.
Connect pin
①
of the CN2 to the negative terminal
of the tester.
The pointer will keep swinging up to about 150 V DC,
goes back to 0 V, and then swing back to about 150 V
DC.
The pointer will momentarily display a high value, go
back to 0 V, and then display a large value again.
・
When the voltage is measured with a tester with the timing for voltage measurement, and if the pointer swings as illustrated
in the above table, then the product should be normal. (There are dispersions with testers. Moreover, a digital tester often
results in its reading being illegible. An analog tester is therefore recommended.)
※
The product is energized only twice a second. Missing the timings will therefore result in failure to measure normal operations.
※
If the reversing valve proper is normal, it will synchronize with the timing for voltage measurement and the reversing valve
itself will click twice. If this click is heard, the reversing valve should be functioning normally.
※
If the energization check shows an abnormality, the electrical parts should be out of order.
29
28
36
35
11
10
6
7
61
Summary of Contents for RAC-50FPA
Page 2: ...DANGER 2 ...
Page 32: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD 2 E 5 R A R r e l l o r t n o c e t o m e R 32 ...
Page 33: ...A P R 0 5 F A R L E D O M 33 ...
Page 34: ...MODEL RAC 50FPA 34 ...
Page 39: ...39 ...
Page 41: ...41 ...
Page 44: ...44 ...
Page 57: ...10 10 10 10 R921 R924 R642 R544 R542 R610 R922 DSW1 DSW1 R923 R541 R543 57 93 ...
Page 59: ... 9 9 RQWURO 3 0LFURFRPSXWHU 59 ...
Page 62: ...62 ...
Page 63: ...5 Electric expansion valve circuit 22 23 24 25 12 13 14 15 5 4 3 2 34 32 30 29 RED 63 ...
Page 64: ...3 15A Fuse Switching power source 64 ...
Page 65: ...3 15A 3 15A DC260 360V 65 ...
Page 72: ...7528 6 227 1 RA 50FPA C 72 ...
Page 74: ...74 ...
Page 75: ...7528 6 227 1 1 7 7 0 5 03 1 6 1 0 1 1 2 RAF 50RPA 7 75 ...
Page 77: ...77 78 ...
Page 78: ...78 ...
Page 85: ... 1 7 287 225 81 7 75 3 576 MODEL RAC 50FPA 85 ...
Page 87: ...9 V 3 V 3 Q L D 0 3 U R R G W X R H F D O S H 5 V 3 9 87 ...
Page 90: ... 1 7 5 027 21752 5 90 ...
Page 91: ...91 36 ...
Page 92: ...Please set the DIP switch No 6 to ON accordingly Refe to page 57 r 92 ...
Page 93: ...93 57 ...
Page 94: ...94 ...
Page 97: ...38 39 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAF 50RPA 97 ...
Page 98: ...MODEL RAF 50RPA 98 HWRAF 50NX2 A14 HBOARD AS ...