– 84 –
1. Turn OFF the Power supply to the outdoor unit.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering
iron of 30 to 75W for 15 seconds or more to P2 and N1 terminals on system power module, in order to
discharge voltage in smoothing capacitor.
3. Remove receptable of red/gray lead wire connected to system power module from diode stack before
performing operation chech of each circuit.
Caution
●
Voltage of about 300-330V is charged between both ends of smoothing capacitors
●
During continuity check for each part of circuit in indoor unit electrical parts, disconnect red/gray
lead wire connected from diode stack to system power module (SPM2) to prevent secondary
trouble. (Be sure to discharge smoothing capacitor)
Do not use a soldering iron with
transformer: If one is used, thermal fuse
inside transformer will be blown
DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
WARNING
As shown above, apply soldering iron to metal
parts (receptable) inside the sleeve
corresponding to P1 and N1 terminals of
system power module: Do this with smoothing
capacitors kept connected. By removing red/
gray lead wire from diode stack, power supply
can be shut off. (corresponding to + and –
terminals of system power module)
N1
P1
Soldering
iron
System power module
Summary of Contents for RAC-50DH7
Page 30: ... 29 CIRCUIT DIAGRAM Wired Remote Control ...
Page 31: ... 31 CIRCUIT DIAGRAM MODEL RAD 50DH7A RAD 60DH7A RAD 70DH7A ...
Page 32: ... 33 CIRCUIT DIAGRAM MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Page 35: ... 39 51 53 53 55 57 49 29 66 Heating ...
Page 76: ... 86 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Page 79: ... 89 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 82: ... 92 CHECKING THE REMOTE CONTROLLER ...
Page 87: ... 97 16 ...