7. Temperature Detection Circuit
The Over heat thermistor circuit detects the temperature at the surface of the compressor head, the Defrost.
thermistor circuit detects the defrosting operation temperature.
A thermistor is a negative resistor element which has the characteristics that the higher (lower) the temperature,
the lower (higher) the resistance.
When the compressor is heated, the resistance of the Over heat thermistor becomes low and voltage to a
pin (62) of microcomputer is increased.
Microcomputer compares the voltage at pin (62) with the internal set value, if it is exceeded the set value
microcomputer judges that the compressor is overheated and stops operation.
When frost forms on the outdoor heat exchanger, the temperature at the exchanger drops abruptly. Therefore
the resistance of the Defrost. thermistor becomes high and the voltage at pin (63) of microcomputer drops.
If this voltage becomes lower than the set value stored inside, the microcomputer starts defrosting control.
During defrosting operation the microcomputer transfers the defrosting condition command to the indoor
microcomputer via the circuit interface.
The microcomputer always reads the outdoor temperature via a thermistor (microcomputer pin (64) ), an
transfers it to the indoor unit, thus controlling the compressor rotation speed according to the value set at the
EEPROM in the indoor unit, and switching the operation status (outdoor fan on/off, etc.) in the dehumidifying
mode.
The following shows the typical values of outdoor temperature in relation to the voltage:
<Reference>
When the thermistor is open, in open status, or is disconnected, microcomputer pins (62) (64) are
approx. 0V; when the thermistor is shorted, they are approx. 5 V, and LD301 blinks seven times.
However, an error is detected only when the OH thermistor is shorted; in such a case, the blinking mode
is entered 12 minutes after the compressor starts operation.
Fig. 7-1
Table 7-1
MAIN P.W.B.
R303 Voltage(V)
Outdoor temperature (
°
C)
C304
C303
C302
RAS_25_35_AW_055-086
2003.12.31, 10:59 AM
79
Summary of Contents for RAC-25YH4
Page 7: ... 5 RAS_25_35_AW_001 024 2003 12 31 10 43 AM 5 ...
Page 31: ... 29 RAS_25_35_AW_029 030_A3 2003 12 31 10 48 AM 29 ...
Page 32: ...RAS_25_35_AW_029 030_A3 2003 12 31 10 48 AM 30 ...
Page 34: ...RAS_25_35_AW_031 032 2003 12 31 10 49 AM 32 ...
Page 35: ... 33 RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 33 ...
Page 36: ...RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 34 ...
Page 37: ... 35 RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 35 ...
Page 38: ...RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 36 ...
Page 42: ...RAS_25_35_AW_037 040 2003 12 31 10 53 AM 40 ...
Page 44: ...RAS_25_35_AW_041 042_A3 2003 12 31 10 54 AM 42 ...
Page 45: ... 43 button RAS_25_35_AW_043 044_A3 2003 12 31 10 55 AM 43 ...
Page 46: ...RAS_25_35_AW_043 044_A3 2003 12 31 10 55 AM 44 ...
Page 48: ...RAS_25_35_AW_045 046 2003 12 31 10 55 AM 46 ...
Page 50: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 48 ...
Page 52: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 50 ...
Page 54: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 52 ...
Page 56: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 54 ...
Page 68: ... 66 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 66 ...
Page 69: ... 67 Fig 3 4 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 67 ...
Page 70: ... 68 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 68 ...