– 74 –
•
The voltage specification of the power circuit is as follows.
<Check points>
Output
Voltage
Main load
Measuring points
Potential failure modes
spec.
+
–
12V
11-13V
MAIN P.W.B. (CN3, CN4)
R701 (“12V” display)
R006 (“0V” display)
The unit won’t operate
C21 (“12V” display)
J27, J30
MAIN P.W.B. error
5V
4.5-6V
MAIN P.W.B. (CN3, CN4)
D30 anode (“5V” display) R006 (“0V” display)
The unit won’t operate
J25
J27, J30
MAIN P.W.B. error
B-12V
11-16V
Expansion valve
R25 (“B-12V” display)
R25 (“B-0V” display)
LD301 blinks 5 times;
Expansion valve error
15V
14-17V
DC fan motor (CN24)
C06+ side
C06- side
LD301 blinks 3 times,
MAIN P.W.B. (CN3, CN4)
35V
33.5-38V
Indoor unit electrical parts
D20 cathode
J5, j17
Indoor unit won’t operate
(Terminal C,D)
(“C-35V” display)
Terminal D (red line)
Reversing valve (CN2)
Terminal C (blown line)
•
Check each voltage. If each voltage meets the voltage specification above, the power circuit is normal.
•
If any error is found after checking, remove all loads and recheck each voltage.
If no error is found in this step, the power circuit is normal. Check the removed loads.
If any error is found in this step, the power circuit has any failure. Replace the power P.W.B.
* A short-circuited load may cause an output error not only in the load but also in the others. Be sure to
check all outputs of the loads.
* Be sure to wait 15 minutes or more in order to discharge all the remaining voltage in the circuit to
connect/disconnect the wiring, other wise, the components may be damaged.
•
The failures of the loads are as follows.
Failed
output
35V
15V
12V, 5V
Criterion
Connect the cable correctly.
Remove the connection cable and measure the
voltage. If the voltage is correct, check the electrical
parts for the indoor unit.
Remove the CN2 and measure the voltage. If the
voltage is correct, check the reversing valve.
Remove the CN24 and measure the voltage.
(connect the CN3.) If the voltage is correct, check
the DC fan motor.
Also, check the main P.W.B 1 A fuse for blow out in
this step.
Remove the CN3 and CN4 and meaure the voltage.
If the voltage is correct, check the main P.W.B.
Remove the CN3 and CN4 and meaure the voltage.
If the voltage is correct, check the main P.W.B.
Possible causes
Reversed connection of the cable.
Electrical part for the indoor unit has
a failure.
Short-circuited reversing valve
DC fan motor error
Main P.W.B. error
Main P.W.B. error
RAS_25_35_AW_055-086
2003.12.31, 10:59 AM
74
Summary of Contents for RAC-25YH4
Page 7: ... 5 RAS_25_35_AW_001 024 2003 12 31 10 43 AM 5 ...
Page 31: ... 29 RAS_25_35_AW_029 030_A3 2003 12 31 10 48 AM 29 ...
Page 32: ...RAS_25_35_AW_029 030_A3 2003 12 31 10 48 AM 30 ...
Page 34: ...RAS_25_35_AW_031 032 2003 12 31 10 49 AM 32 ...
Page 35: ... 33 RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 33 ...
Page 36: ...RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 34 ...
Page 37: ... 35 RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 35 ...
Page 38: ...RAS_25_35_AW_033 036_A2 2003 12 31 10 51 AM 36 ...
Page 42: ...RAS_25_35_AW_037 040 2003 12 31 10 53 AM 40 ...
Page 44: ...RAS_25_35_AW_041 042_A3 2003 12 31 10 54 AM 42 ...
Page 45: ... 43 button RAS_25_35_AW_043 044_A3 2003 12 31 10 55 AM 43 ...
Page 46: ...RAS_25_35_AW_043 044_A3 2003 12 31 10 55 AM 44 ...
Page 48: ...RAS_25_35_AW_045 046 2003 12 31 10 55 AM 46 ...
Page 50: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 48 ...
Page 52: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 50 ...
Page 54: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 52 ...
Page 56: ...RAS_25_35_AW_047 054_A3 2003 12 31 10 57 AM 54 ...
Page 68: ... 66 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 66 ...
Page 69: ... 67 Fig 3 4 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 67 ...
Page 70: ... 68 RAS_25_35_AW_055 086 2003 12 31 10 59 AM 68 ...