The refrigerating machine oil is
easily affected by moisture. Use
caution to prevent water from
entering the cycle.
The difference in height between
the indoor and outdoor unit
should be kept below 10m.
The connecting pipe, no matter
big or small, should all be
insulated with insulation pipe and
then wrapped with vinyl tape.
(The insulator will deteriorate if
it is not wrapped with tape).
The connection of insulated drain
hose.
Inner diameter 16mm
Please use insulated drain hose for
the indoor piping (commercial
product)
Maximum pipe length 30m
Minimum pipe length 3m
Figure showing the installation of lndoor and Outdoor unit
MODEL RAC-50FX
E
above 200mm
above
200mm
give clearance
as wide as
possible
above 300mm
above 700mm
above 150mm
8
Summary of Contents for RAC-25FXE
Page 2: ... DANGER 2 ...
Page 6: ...SPECIFICATIONS 3 RAC 25 35FXE RAC 50FXE 1200g 6 ...
Page 13: ...WIRING DIAGRAM MODEL RAC 25 35F XE 13 ...
Page 14: ...WIRING DIAGRAM RAC 50FXE L E D O M 14 ...
Page 15: ...M基板BOM 中继端子台基板用部品 HIC基板BOM MODEL RAC 25 35F XE 15 ...
Page 16: ...MODEL RAC 50FXE 16 ...
Page 25: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 10 11 12 74 70 75 25 ...
Page 27: ...2A Fuse DC300 330V 7 1 7 27 ...
Page 28: ...2A DC300 330V 60 100 28 ...
Page 29: ...L N 300 330 L N 50FXE 29 ...
Page 30: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 30 ...
Page 34: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 10 11 12 74 70 75 34 ...
Page 36: ...2A Fuse DC300 330V 7 1 7 36 ...
Page 37: ...2A DC300 330V 30 60 37 ...
Page 45: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25 35F X E 45 ...
Page 46: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50FXE 46 ...
Page 60: ...JCH WH RAC 50FXE RAC 2 5FXE RAC 3 5FXE NO 0128E 60 ...