The LD301 blinks 12 times
Fan lock stopped
The LD301 blinks 11 times.
Fan stopped due to a strong wind
It is a pause due to a strong wind. As the wind
weakens, the product will start again.
The product detected an abnormality in the
outdoor fan and stopped its operation. Possible
causes include a pause due to a strong wind,
foreign matter in the fan, abnormality in the fan
motor, and abnormality in the drive circuit.
Check if the fan is clear of foreign
matter and abnormalities.
Remove all foreign matter.
If the fan is abnormal, replace the
fan.
Is the wind too strong?
Check if the product can restart all
right. (It takes several minutes for
it to start again.)
This is not a sign of a failure in the
outdoor fan motor or outdoor electrical
parts.
After restarting,
the product will
run continuously.
It stops
Check the outdoor fan motor. (For details, see
the page on the outdoor fan motor or the
instruction plate on the lid of the electrical
parts.) Is the outdoor fan motor abnormal?
Fan motor
abnormal
Replace the outdoor fan motor.
Fan motor normal
Replace the outdoor electrical
parts (in the case of an
abnormality in the drive circuit of the
outdoor fan).
Check the fan motor for loose
connectors.
Insert the connector.
Yes
Yes
The LD301 blinks 14 times
Change the outdoor ele. unit.
The creepage breaker have already set?
Yes
Q601,Q602 have malfunction
No
No
Abnormal
Does the compressor insulation OK?
Change the compressor and then
check the outdoor ele. unit .
Abnormal
Abnormal
Normal
Normal
Normal
Change the outdoor ele. unit.
Q601,Q602 abnormal
No
Yes
Active voltage abnormal
52
Summary of Contents for RAC-25FXE
Page 2: ... DANGER 2 ...
Page 6: ...SPECIFICATIONS 3 RAC 25 35FXE RAC 50FXE 1200g 6 ...
Page 13: ...WIRING DIAGRAM MODEL RAC 25 35F XE 13 ...
Page 14: ...WIRING DIAGRAM RAC 50FXE L E D O M 14 ...
Page 15: ...M基板BOM 中继端子台基板用部品 HIC基板BOM MODEL RAC 25 35F XE 15 ...
Page 16: ...MODEL RAC 50FXE 16 ...
Page 25: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 10 11 12 74 70 75 25 ...
Page 27: ...2A Fuse DC300 330V 7 1 7 27 ...
Page 28: ...2A DC300 330V 60 100 28 ...
Page 29: ...L N 300 330 L N 50FXE 29 ...
Page 30: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 30 ...
Page 34: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 10 11 12 74 70 75 34 ...
Page 36: ...2A Fuse DC300 330V 7 1 7 36 ...
Page 37: ...2A DC300 330V 30 60 37 ...
Page 45: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25 35F X E 45 ...
Page 46: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50FXE 46 ...
Page 60: ...JCH WH RAC 50FXE RAC 2 5FXE RAC 3 5FXE NO 0128E 60 ...