[ Situation ] The compressor will not run (the same state as the thermometer turned off), the product receives remote control
signals normally. The self-diagnosis lamp (LD301) of the outdoor unit blinks once or becomes turned off.
[ Estimated failure locations ]
·
Room temperature thermistor, heat exchanger thermistor
Microcomputer peripheral circuit
[ Diagnosis flow ]
Initiating troubleshooting
3. Failure phenomenon: The compressor will not run.
Is the "timer lamp" (orange) of the indoor unit
blinking?
Yes
Yes
Yes
No
No
No
Check for failures according to the self-
diagnosis display.
Did the self-diagnosis lamp (LD301) of the outdoor
unit blink once or become turned off?
Check for failures according to the self-
diagnosis display.
Remove the connector (CN4) of the room
temperature thermistor and heat exchanger
thermistor and measure the thermistor resistance.
Did the reading roughly agree with the resistance
values indicated in the right-hand figure?
Replace the "room temperature and heat
exchanger thermistors".
Thermistor characteristics (resistance)
Ther
mistor resistance
Thermistor temperature
Replace the "indoor electrical parts".
·
85
Summary of Contents for RAC-18WPD
Page 2: ... DANGER 2 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 26: ...26 ...
Page 28: ...Contact your sales agent immediately if the following phenomena should occur Notes 28 ...
Page 31: ...WIRING DIAGRAM RAK 15QPD RAK 18RPD RAK 25RPD RAK 35RPD RAK 42RPD RAK 50RPD 31 ...
Page 33: ...CIRCUIT DIAGRAM MODEL RAK 15QPD 33 ...
Page 34: ...CIRCUIT DIAGRAM MODEL RAK 18 25 35 42 50RPD 34 ...
Page 57: ...10 10 10 10 10 DSW1 57 ...
Page 61: ...RL1 RL1 RL2 61 ...
Page 70: ...68 70 ...
Page 73: ...37 and page 38 73 ...
Page 75: ...57 75 ...
Page 76: ...76 ...
Page 77: ... 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 B C E F 㺢 F 䌖 B GH E H C J E 77 ...
Page 78: ... 䇭䇭 G FK 㺢 F L M C B C M C E C B H C E B M C E C B M C 78 ...
Page 93: ...RAK 15QPD RAK 18RP RAK 25RP D D RAK 35RP RAK 42RP D D RAK RPD 50 JCH WH NO 0108E 93 ...