1. Failure phenomenon: The power will not become turned on.
>
Situation
@ǂ
Neither initialization, remote control, nor any other step works on the vane position at power-on.
[ Estimated failure
locations ]
·
3.15 A fuse blown out
·
Control power circuit
·
Connector loose, wire break
>
Cautions
@
>
Diagnosis flow
@
Initiating troubleshooting
Is a voltage of
2
0 V applied between WR2-WR4?
ǂǂǂǂǂǂǂǂǂ
Is the CN16 securely connected?
Replace the "indoor electrical parts".
Replace the "indoor electrical parts".
Replace the "3.15 A fuse".
Replace the "varistor (VA001)".
Abnormal
Is the power supply voltage normal?
Has the varistor VA001 not become burned?
Normal power supply voltage: AC 230 V
Estimated cause of fuse blowout
·
Abnormally high voltage applied to the power supply
·
Indoor fan motor out of order
·
Power circuit out of order
·
Before work, check the power supply voltage. An abnormal voltage may be being supplied in
some rare occasions due to a defect in the indoor wiring (a wire break in the neutral wire of the
single-phase 3-wire power supply).
·
If the 3.15 A fuse has blown out, eliminate the cause of the fuse blowout. Otherwise, there will occur
another fuse blowout.
·
If the 3.15 A fuse has blown out due to an abnormally high voltage to the power supply, the varistor
(VA001) will deteriorate and become destroyed as well.
·
On a repair service visit due to the failure phenomenon of "The power will not become turned on",
take a "3
A fuse" and a "varistor" with you.
Get the indoor wiring back to its
normal condition, then conduct
a final check.
Normal
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Replace the 3.15 A fuse, disconnect the CN2
(indoor fan motor), and conduct an operation
check. Has the product worked?
Replace the "indoor fan motor".
Another fuse blowout
Disconnect the CN2 and check for continuity
between the "red" and "black" wires of the
indoor fan motor by using a tester. Is it short-
circuited?
Apply the black lead of the tester to the red
lead of the motor. Apply the red lead of the
tester to the black lead of the motor.
Replace the "indoor electrical
parts".
Replace the "indoor fan motor".
Replace the "indoor electrical
parts".
Reconnect the connector correctly.
3
AC
.15
Is DC 5 V applied to both ends of the C106?
81
Summary of Contents for RAC-18WPD
Page 2: ... DANGER 2 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 26: ...26 ...
Page 28: ...Contact your sales agent immediately if the following phenomena should occur Notes 28 ...
Page 31: ...WIRING DIAGRAM RAK 15QPD RAK 18RPD RAK 25RPD RAK 35RPD RAK 42RPD RAK 50RPD 31 ...
Page 33: ...CIRCUIT DIAGRAM MODEL RAK 15QPD 33 ...
Page 34: ...CIRCUIT DIAGRAM MODEL RAK 18 25 35 42 50RPD 34 ...
Page 57: ...10 10 10 10 10 DSW1 57 ...
Page 61: ...RL1 RL1 RL2 61 ...
Page 70: ...68 70 ...
Page 73: ...37 and page 38 73 ...
Page 75: ...57 75 ...
Page 76: ...76 ...
Page 77: ... 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 䇭䇭 B C E F 㺢 F 䌖 B GH E H C J E 77 ...
Page 78: ... 䇭䇭 G FK 㺢 F L M C B C M C E C B H C E B M C E C B M C 78 ...
Page 93: ...RAK 15QPD RAK 18RP RAK 25RP D D RAK 35RP RAK 42RP D D RAK RPD 50 JCH WH NO 0108E 93 ...