Setting Defrosting Inhibit Period
DFTIM_OT P5
DFTIM_OT P0
DFTIM_OTP 10
Time
Outdoor temperature
– 1 0
– 5˚C
0 ˚C
Notes:
(1) The first inhibit time after operation start is set to DFTIM_FST.
(2) From the second time onwards, the inhibit time is set according to the time required for
defrosting.
Reverse cycle operation time [DEFCOL] : DEFTIM_COL is set.
Reverse cycle operation time < [DEFCOL] : The time corresponding to outdoor tempera-
ture is set.
≧
63
Silent button
WSZMAX/CSZMAX
Compresson
speed
Indoor
fan
Outdoor
fan
8,WUD+L
+L
0HG
/RZ
/RZ
6LOHQW
6
8OWUD/R
SILENT
Notes:
Can’t set POWERFUL and SILENT at the same time.
Summary of Contents for RAC-18WPB
Page 50: ...WIRING DIAGRAM RA RAC 18 25 35WPB K 18 25 35 50PPB RAC 5 WPB 0 50 ...
Page 52: ...CIRCUIT DIAGRAM MODEL RAK 18 25 35 50PPB 52 WIRED REMOTE CONTROL SEND POWER FOR CLEANNESS ...
Page 53: ...MODEL RA C 18 25 35 WPB 53 ...
Page 54: ...MODEL RAC 50WPB 54 ...
Page 67: ...MODEL RAK 18 25PPB RAC 18 25WPB INDOOR UNIT INDOOR UNIT 67 ...
Page 81: ...L N 300 330 Main parts L N C021 C022 37 5 420V RAC 18 25 35WPB 81 1 5 ...
Page 85: ...5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 85 ...
Page 87: ...2A Fuse DC300 330V 7 7 1 87 ...
Page 88: ...2A DC300 330V 88 ...
Page 89: ...L N 300 330 L N 50WPB 89 ...
Page 90: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 90 ...
Page 94: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 94 ...
Page 96: ...2A Fuse DC300 330V 7 1 7 96 ...
Page 97: ...2A DC300 330V 97 ...
Page 108: ...108 109 ...
Page 110: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18 25 35WP B 110 ...
Page 111: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50WP B 111 ...
Page 131: ...57 131 ...
Page 132: ...Please set the DIP switch No 6 to ON accordingly Refe to page r 78 132 ...
Page 133: ...78 133 ...
Page 134: ...134 ...