MODEL RAK-18/25/35/50PPB
Set to "ultra-Lo","Silent","Lo","Med","Hi","ultra-Hi" or "stop" depending on the room
temperature, time and heat exchanger temperature. Set to "stop" if the heat exchanger
temperature is "DNZKOF" during Thermo OFF.(When reach at "DNZKON", fan speed set
to "ultra-Lo" again.)
Set to "ultra-Lo","Silent","Lo","Med","Hi","ultra-Hi" or "stop" depending on the room
temperature, time and heat exchanger temperature. Set to "stop" if the heat exchanger
temperature is "DNZKOF" during Thermo OFF.(When reach at "DNZKON", fan speed set
to "ultra-Lo" again.)
Set to"ultra-Hi"
Set to "ultra-Lo","Silent","Lo","Med","Hi","ultra-Hi" or "stop" depending on the room
temperature, time and heat exchanger temperature. Set to "stop" if the heat exchanger
temperature is "DNZKOF" during Thermo OFF.(When reach at "DNZKON", fan speed set
to "ultra-Lo" again.)
Set to "ultra-Lo","Silent","Lo","Med","Hi","ultra-Hi" or "stop" depending on the room
temperature, time and heat exchanger temperature. Set to "stop" if the heat exchanger
temperature is "DNZKOF" during Thermo OFF.(When reach at "DNZKON", fan speed set
to "ultra-Lo" again.) The fan speed is controlled by the heat exchanger temperature; the
overload control is executed as in the following diagram:
button
button
button
button
“ultra-Lo”
Operates at “Lo” regardless of the room temperature.
Runs at “ultra-Lo” when thermo is off.
Operates at “Silent” regardless of the room temperature.
Runs at “ultra-Lo” when thermo is off.
Operates at “Med” regardless of the room temperature.
Runs at “ultra-Lo” when thermo is off.
1. Runs at “Hi” until room temperature reaches to
“setting temperature-SFTDSC” after operation is
started.
2. Runs at “ultra-Lo” when thermo is off.
button
button
button
button
button
button
button
PDCIN2
PDCOF2
"Med","Lo""Silent"
×108%
"Med","Lo""Silent"
When the compressor is running at maximum
speed
during hot-dash or when recovered from
defrosting.
In modes other than left
Heat exchanger temperature
DASUPHH
DASUPH
DASDNH
DASDNH
NORUPS
NORUPL
NORUPH
NORDPH
NORDNL
NORDNS
Ultra-High
High
Med
Low
Silent
"
0
9
"
0
9
DASUPL
DASUPS
DNZKON
DASDNL
DASDNS
DNZKOF
Fan speed UP/DOWN delay time
Fan speed UP/DOWN delay time
56
60
62
558
59
61
63
Setting temperature
Room temperature
ON
Thermo judgment
Compressor
(Compressor stopped
forcibly for 3 minutes)
Hi
Med
Lo
3
ON
OFF
SFTDSC
OFTMPC
0.66℃
FCAUT_L
FCAUT_H
Summary of Contents for RAC-18WPB
Page 50: ...WIRING DIAGRAM RA RAC 18 25 35WPB K 18 25 35 50PPB RAC 5 WPB 0 50 ...
Page 52: ...CIRCUIT DIAGRAM MODEL RAK 18 25 35 50PPB 52 WIRED REMOTE CONTROL SEND POWER FOR CLEANNESS ...
Page 53: ...MODEL RA C 18 25 35 WPB 53 ...
Page 54: ...MODEL RAC 50WPB 54 ...
Page 67: ...MODEL RAK 18 25PPB RAC 18 25WPB INDOOR UNIT INDOOR UNIT 67 ...
Page 81: ...L N 300 330 Main parts L N C021 C022 37 5 420V RAC 18 25 35WPB 81 1 5 ...
Page 85: ...5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 85 ...
Page 87: ...2A Fuse DC300 330V 7 7 1 87 ...
Page 88: ...2A DC300 330V 88 ...
Page 89: ...L N 300 330 L N 50WPB 89 ...
Page 90: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 90 ...
Page 94: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 94 ...
Page 96: ...2A Fuse DC300 330V 7 1 7 96 ...
Page 97: ...2A DC300 330V 97 ...
Page 108: ...108 109 ...
Page 110: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18 25 35WP B 110 ...
Page 111: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50WP B 111 ...
Page 131: ...57 131 ...
Page 132: ...Please set the DIP switch No 6 to ON accordingly Refe to page r 78 132 ...
Page 133: ...78 133 ...
Page 134: ...134 ...