– 67 –
CAUTION
Remote control is disabled while the Timer lamp is
fl
ashing.
To check operation, turn off the power switch and turn it on again.
Timer-Lamp, break-down checking in blinking sign.
Check the break-down factor from the frequency of timer-lamp blinking.
No.
Mode of Timer-Lamp blinking
Indication Factor
Estimated Break-Down Part
4-way valve not working
Inside temperature is low in
heating operation time or inside
temperature is high in cooling
operation time.
(1) 4-way valve is not working.
(2) Heat-exchanger thermistor is
in disconnection.
(Only heating time)
Force cooling operation
Unit is under forcible operation
or under balancing after forcible
operation.
Check force cooling switch at
indoor electrical.
IC 401 Data read wrongly
In case that data read from IC401
is wrong.
IC401 data is not in order.
Heat exchanger thermistor
error
Heat exchanger thermistor open
or short-circuit detected.
(1) Thermistor
(2) Indoor - control circuit board.
Room thermistor error
Room thermistor error open or
short-circuit detected.
(1) Thermistor
(2) Indoor - control circuit board.
1
2
3
4
5
6
( – – 0.5 second on, 0.5 second off.)
– – –– 15 times
– – – 14 times
– – – 13 times
– – – – – – – 2 times
– – – – – – – – 1 time
!
DC Fan motor - over current
of electricity
Indoor - DC Fan motor has over
current of electricity.
(1) Indoor - Fan is locked.
(2) Indoor - Fan motor damage.
(3) Indoor - control circuit board.
– – – 10 times
Summary of Contents for RAC-08LH1
Page 33: ... 31 MODEL RAC 08LH1 RAC 10LH1 RAC 14LH1 ...
Page 37: ... 35 WIRING DIAGRAM MODEL RAS 14LH2 14LH2 B RAC 14LH1 RAS 63CHA1 RAC 63CHA1 ...
Page 45: ... 49 MODEL RAS 14LH2 RAS 14LH2 B RAC 14LH1 ...
Page 53: ... 57 ...
Page 71: ... 75 PARTS LIST AND DIAGRAM OUTDOOR UNIT MODEL RAC 08LH1 ...
Page 73: ... 77 PARTS LIST AND DIAGRAM OUTDOOR UNIT MODEL RAC 10LH1 RAC 14LH1 ...