6 MAINTENANCE
6-8
z
Case 4 -- all of the input points are turned on and off irregularly:
Check item
Remedial action
External input voltage too low
Apply rated input voltage to the digital
input module.
Not the above
Replace the digital input module with a
new one.
z
Case 5 -- a particular input point(s) are not turned off:
Check item
Remedial action
External-equipment abnormality
Adjust the external equipment.
Not the above
Replace the digital input module with a
new one.
6.2.4 Troubleshooting a digital output module
z
Case 1 -- none of the load points is turned on:
Check item
Remedial action
Power supply module’s POWER ON LED not lit
Troubleshoot the power supply module
according to the instructions given in
Subsection 6.2.1.
Remote I/O station module’s RI/O LED not lit
Troubleshoot the remote I/O station
module according to the instructions given
in Subsection 6.2.2.
Power not supplied to the load
Suppy power to the load.
Applied load voltage other than the rated voltage
Apply the rated voltage to the load.
None of the above
Replace the digital input module with a
new one.
z
Case 2 -- a particular load point(s) are not turned on:
Check item
Remedial action
Operation
indicator
LED
condition
Not
lit
Load’s on-state duration too
short
Correct the program.
Program I/O address error
Lit
External wire breakage
Check the external wiring.
Loosened terminal screw
Apply additional tightening to the screw.
Incorrect external wiring
Corrent the external wiring.
None of the above
Replace the digital input module with a
new one.
Summary of Contents for HSC-2100
Page 1: ......
Page 2: ......
Page 24: ...1 GENERAL INFORMATION ...
Page 38: ...2 SPECIFICATIONS OF INDIVIDUAL MODULES ...
Page 78: ...3 INSTALLATION AND MODULE MOUNTING ...
Page 92: ...4 WIRING ...
Page 101: ...This Page Intentionally Left Blank ...
Page 102: ...5 MAKING USE OF MODULES ...
Page 150: ...6 MAINTENANCE ...
Page 163: ...This Page Intentionally Left Blank ...
Page 164: ...7 APPENDIX ...