2.6 Model LWI460 Input Module (48 VDC Input, 16 Points)
Item Specification
Input points
16
Insulation method
Photocoupler
Rated input voltage
48 VDC
Rated input current
Approx. 10 mA
Input voltage range
40 to 56 VDC
ON voltage / current
40 VDC or higher / 8 mA or more
OFF voltage / current
8 VDC or lower / 1.5 mA or less
Input impedance
Approx. 48 k
Ω
Response
time
OFF
→
ON
15 ms or less
ON
→
OFF
20 ms or less
Internal
consumption
current
12 VDC
0 mA
5 VDC
4 mA + 2 mA × n, where n is the number of points in
ON state.
Points per common
8
Insulation withstand voltage
1,500 VAC, 1 minute (between external terminal and
ground)
External
wiring
Connection
20-point terminal block connector (Connector screw
type: M3)
Applicable
cable size
0.5 to 1.25 mm
2
Tightening
torque
0.6 to 0.8 N·m
Maximum
wiring
length
200 m
Operation indication
LED (lit when the module is powered on)
Mass 380
g
1
2
3
4
5
6
7
8
9
20
19
18
17
16
15
14
13
12
11
10
C0
0
1
2
3
4
5
6
7
C1
C2
8
9
A
B
C
D
E
F
C3
LWI460 DI
D.INPUT
DC48V
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
HITACHI
C
ontr
ol c
irc
uit
Contacts
0
7
9
C0
1
2
10 C1
Fuse
48 VDC
8
F
19
C2
11
12
20 C3
Summary of Contents for HSC-2100
Page 1: ......
Page 2: ......
Page 24: ...1 GENERAL INFORMATION ...
Page 38: ...2 SPECIFICATIONS OF INDIVIDUAL MODULES ...
Page 78: ...3 INSTALLATION AND MODULE MOUNTING ...
Page 92: ...4 WIRING ...
Page 101: ...This Page Intentionally Left Blank ...
Page 102: ...5 MAKING USE OF MODULES ...
Page 150: ...6 MAINTENANCE ...
Page 163: ...This Page Intentionally Left Blank ...
Page 164: ...7 APPENDIX ...