Part
Optional function
Indivi
dual
settin
g
Settings
Condition
setting
Description
E4
Pre-cooling / pre-heating
period
O
KPI:
This function delays start-up of the
ventilation unit with energy / heat recovery
00
Standard
01
30 minutes
02
60 minutes
Econofresh kit
00
Standard
02
CO
2
sensor
E5
Not used
O
00
Not used
–
01
Used as setting
for conditions
00
E6
Fan operating time after
stoppage of the indoor unit
in cooling mode
O
00
Not available
This prevents condensation from
accumulating in the unit by keeping the fan
running after it is switched off.
01
60 minutes
02
120 minutes
E7
Not used
O
00
Not used
–
01
Used as setting
for conditions
00
E8
Fan operating control after
stoppage of the indoor unit
in heating mode
O
00
Not available
This function reduces the unit fan speed to
prevent cold draughts.
01
Available
E9
Not used
O
00
Not used
–
01
Used as setting
for conditions
00
EA
Not used
O
00
Not used
–
01
Used as setting
for conditions
00
Eb
Fan operating control after
stoppage of the indoor unit
in cooling mode
O
00
Not available
This function reduces the unit fan speed to
reduce the spreading of smells and
humidity.
01
Low
02
Slow
EC
Forced stoppage in cooling
mode
O
00
Not available
This function is used to force stoppage
when cooling is complete.
01
Available
Ed
Not used
O
00
Not used
–
01
Used as setting
for conditions
00
EE
Automatic fan speed
control
O
00
Not available
This function limits the operating of the unit
by automatically controlling the fan speed
when the room temperature is close to the
set temperature.
01
Available
6 Optional functions
202
SMGB0063 rev. 1 - 10/2010
Summary of Contents for Econofresh
Page 2: ......
Page 4: ...Index ii SMGB0063 rev 1 10 2010 ...
Page 12: ...Index x SMGB0063 rev 1 10 2010 ...
Page 24: ...1 General information 12 SMGB0063 rev 1 10 2010 ...
Page 88: ...2 Unit installation 76 SMGB0063 rev 1 10 2010 ...
Page 169: ... KPI 3002H2E heat recovery unit 4 Electrical wiring 157 SMGB0063 rev 1 10 2010 4 ...
Page 170: ...4 Electrical wiring 158 SMGB0063 rev 1 10 2010 ...
Page 192: ...5 Control system 180 SMGB0063 rev 1 10 2010 ...
Page 234: ...6 Optional functions 222 SMGB0063 rev 1 10 2010 ...
Page 252: ...9 1 RCD 1 0 3 0 FSN2 9 Spare parts 240 SMGB0063 rev 1 10 2010 ...
Page 254: ...9 2 RCD 4 0 5 0 FSN2 9 Spare parts 242 SMGB0063 rev 1 10 2010 ...
Page 256: ...9 3 RPC 4 0 6 0 FSN2E 9 Spare parts 244 SMGB0063 rev 1 10 2010 ...
Page 258: ...9 4 RPI 0 8 1 5 FSNE 9 Spare parts 246 SMGB0063 rev 1 10 2010 ...
Page 260: ...9 5 RPI 8 0 10 0 FSN2E 9 Spare parts 248 SMGB0063 rev 1 10 2010 ...
Page 262: ...9 6 RPIM 0 8 1 5 FSNE DU 9 Spare parts 250 SMGB0063 rev 1 10 2010 ...
Page 264: ...9 7 RPK 1 0 1 5 FSN2E 9 Spare parts 252 SMGB0063 rev 1 10 2010 ...
Page 268: ...9 9 RPK 2 0 FSN2E 9 Spare parts 256 SMGB0063 rev 1 10 2010 ...
Page 270: ...9 10 RPK 2 5 4 0 FSN2E 9 Spare parts 258 SMGB0063 rev 1 10 2010 ...
Page 272: ...9 11 RPF 1 0 2 5 FSN2E 9 Spare parts 260 SMGB0063 rev 1 10 2010 ...
Page 274: ...9 12 RPFI 1 0 2 5 FSN2E 9 Spare parts 262 SMGB0063 rev 1 10 2010 ...
Page 276: ...9 Spare parts 264 SMGB0063 rev 1 10 2010 ...
Page 407: ......