3.1 Gas refrigerant pipe selection
3.1.1 Gas refrigerant pipe selection
N O T E
Consult the corresponding Technical Catalogue for outdoor units from the UTOPIA or SET FREE Series.
¿
Pipe size selection
Select the pipe size in line with the following instructions:
1
Between the outdoor unit and the branch pipe (multikit): select the same pipe connection size as for the outdoor unit.
2
Between the branch pipe (multikit) and the indoor unit: select the same pipe connection size as for the indoor unit.
C A U T I O N
•
Do not use gas refrigerant pipe sizes other than those indicated in the corresponding Technical Catalogue for
outdoor units. The diameter of the gas refrigerant pipes depends directly on the power of the outdoor unit.
•
If larger diameter gas refrigerant pipes are used, the circuit lubrication oil tends to separate from the gas
carrying it. The compressor will be seriously damaged due to a lack of lubrication.
•
If smaller diameter gas refrigerant pipes are used, the gas or liquid refrigerant will have serious difficulties in
circulating. System performance will be affected. The compressor will run under more severe conditions than
foreseen and will be damaged in a short space of time.
¿
Multikit or distributor selection
N O T E
•
Pipe connection sizes on outdoor units, indoor units and the multikit or distributor vary depending on the
system. Consult the Service Manual for the UTOPIA or SET FREE Series.
•
The sizes of the indoor and outdoor units are different. Adjust the flare adapter (accessory) to the indoor pipe
connection.
3 Piping work and
refrigerant charge
78
SMGB0063 rev. 1 - 10/2010
Summary of Contents for Econofresh
Page 2: ......
Page 4: ...Index ii SMGB0063 rev 1 10 2010 ...
Page 12: ...Index x SMGB0063 rev 1 10 2010 ...
Page 24: ...1 General information 12 SMGB0063 rev 1 10 2010 ...
Page 88: ...2 Unit installation 76 SMGB0063 rev 1 10 2010 ...
Page 169: ... KPI 3002H2E heat recovery unit 4 Electrical wiring 157 SMGB0063 rev 1 10 2010 4 ...
Page 170: ...4 Electrical wiring 158 SMGB0063 rev 1 10 2010 ...
Page 192: ...5 Control system 180 SMGB0063 rev 1 10 2010 ...
Page 234: ...6 Optional functions 222 SMGB0063 rev 1 10 2010 ...
Page 252: ...9 1 RCD 1 0 3 0 FSN2 9 Spare parts 240 SMGB0063 rev 1 10 2010 ...
Page 254: ...9 2 RCD 4 0 5 0 FSN2 9 Spare parts 242 SMGB0063 rev 1 10 2010 ...
Page 256: ...9 3 RPC 4 0 6 0 FSN2E 9 Spare parts 244 SMGB0063 rev 1 10 2010 ...
Page 258: ...9 4 RPI 0 8 1 5 FSNE 9 Spare parts 246 SMGB0063 rev 1 10 2010 ...
Page 260: ...9 5 RPI 8 0 10 0 FSN2E 9 Spare parts 248 SMGB0063 rev 1 10 2010 ...
Page 262: ...9 6 RPIM 0 8 1 5 FSNE DU 9 Spare parts 250 SMGB0063 rev 1 10 2010 ...
Page 264: ...9 7 RPK 1 0 1 5 FSN2E 9 Spare parts 252 SMGB0063 rev 1 10 2010 ...
Page 268: ...9 9 RPK 2 0 FSN2E 9 Spare parts 256 SMGB0063 rev 1 10 2010 ...
Page 270: ...9 10 RPK 2 5 4 0 FSN2E 9 Spare parts 258 SMGB0063 rev 1 10 2010 ...
Page 272: ...9 11 RPF 1 0 2 5 FSN2E 9 Spare parts 260 SMGB0063 rev 1 10 2010 ...
Page 274: ...9 12 RPFI 1 0 2 5 FSN2E 9 Spare parts 262 SMGB0063 rev 1 10 2010 ...
Page 276: ...9 Spare parts 264 SMGB0063 rev 1 10 2010 ...
Page 407: ......