10. PIPING WORK AND REFRIGERANT CHARGE
10.3 Air tight test
Do use nitrogen when performing air-tight test.
Connect the gauge manifold using charging hoses with a nitrogen cylinder to the check joints of
the liquid line and the gas line stop valves. Perform the air-tight test. Don't open the gas line stop
valves. Apply nitrogen gas pressure of 4.15MPa.Check for any gas leakage at the flare nut
connections, or brazed parts by gas leak detector or foaming agent. Gas pressure does not
decrease is OK. After the air tight test, release nitrogen gas.
10.4 Additional refrigerant charge
Although refrigerant has been charged into this unit, additional refrigerant charge is required
according to piping length.
•
The additional refrigerant precharge quantity should be determined and charged into the system
according to the following procedure.
•
Record the additional refrigerant quantity in order to facilitate maintenance and servicing activities.
Refrigerant charge before shipment (W0 (kg))
W0 is the outdoor unit refrigerant charge before shipment
;
Xg is additional refrigerant outdoor unit needed to charge according to piping length
during installation.
0-15m
over 15m
12K/
14K
950
0g
18K
1070
0g
21K/AMW3-24U4RFA
1450
0g
0-20m
over 20m
27K
2200g
0g
36K
2200g
0g
Model
Refrigerant precharged
before shipment(W0(g))
Total refrigerant pipe length
Xg = 12g / m × (Total pipe length(m) -20)
Refrigerant precharged
before shipment(W0(g))
Model
Total refrigerant pipe length
Xg = 12g / m × (Total pipe length(m) -15)
AMW3-24U4RAA
1800
0g
0-25m
over 25m
0g
Model
Refrigerant precharged
before shipment (W0(g))
Total refrigerant pipe length
Xg = 12g / m × (Total pipe length(m) -25)
42K
3000g
45
Summary of Contents for 2AMW-42U4RRA
Page 10: ...1 GENERAL Type Capacity Btu h View 1 to 5 indoor units 42K 6 ...
Page 15: ...3 OUTLINES AND DIMENSIONS 21K AMW3 24U4RFA Unit mm 11 ...
Page 16: ...3 OUTLINES AND DIMENSIONS AMW3 24U4RAA Unit mm 414 380 12 ...
Page 17: ...3 OUTLINES AND DIMENSIONS 27K Unit mm 414 380 13 ...
Page 18: ...3 3 O OU UT TL LI IN NE ES S A AN ND D D DI IM ME EN NS SI IO ON NS S Unit mm 42K 14 ...
Page 29: ...7 REFRIGERANT CYCLE 7 Refrigerant cycle 12K 14K 18K 21K 24K 25 ...
Page 32: ...8 WIRING DIAGRAM Electric wiring diagram 1982504 D 21K AMW3 24U4RFA 28 ...
Page 33: ...8 WIRING DIAGRAM AMW3 24U4RAA Electric wiring diagram 1957327 B 29 ...
Page 34: ...8 WIRING DIAGRAM 27K 36K 30 ...