Damped oscillation – DC supply connection
EN 61000-4-12
IEEE C37.90.1
line/ground
—
—
—
2.5 kV
EN 61000-4-12
IEEE C37.90.1
line/line
—
—
—
1 kV
Damped oscillation – data line
EN 61000-4-12
IEEE C37.90.1
line/ground
—
—
—
2.5 kV
EN 61000-4-12
line/line
—
—
—
±1 kV
Pulse magnetic field
EN 61000-4-9
—
—
300 A/m
—
Stability
Standard applications
Navy applications Railway
applications
(trackside)
Substation applications
IEC 60068-2-6, test Fc
Vibration
5 Hz ... 8.4 Hz with 0.14 in
(3.5 mm) amplitude
2 Hz ... 13.2 Hz
with 0.04 in (1 mm)
amplitude
—
2 Hz ... 9 Hz with 0.11 in (3 mm)
amplitude
8.4 Hz ... 150 Hz with 1 g
—
13.2 Hz ... 200 Hz
with 0.7 g
—
—
—
9 Hz ... 200 Hz with 1 g
200 Hz ... 500 Hz with 1.5 g
IEC 60068-2-27, test Ea Shock
15 g at 11 ms
—
—
10 g at 11 ms
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications