43
5.1 Basic Specifications
Power range
Active Power Measurement
Active Energy Measurement
Current
Voltage
/Wiring
1.000 A 5.000 A 50.00 A 100.0 A 200.0 A 500.0 A 1.000 kA
100.0 V
1P2W
100.0
W
500.0
W
5.000
kW
10.00
kW
20.00
kW
50.00
kW
100.0
kW
1P3W
3P3W
200.0
kW
1.000
kW
10.00
kW
20.00
kW
40.00
kW
100.0
kW
200.0
kW
3P4W
300.0
W
1.500
kW
15.00
kW
30.00
kW
60.00
kW
150.0
kW
300.0
kW
200.0 V
1P2W
200.0
W
1.000
kW
10.00
kW
20.00
kW
40.00
kW
100.0
kW
200.0
kW
1P3W
3P3W
400.0
W
2.000
kW
20.00
kW
40.00
kW
80.00
kW
200.0
kW
400.0
kW
3P4W
600.0
W
3.000
kW
30.00
kW
60.00
kW
120.0
kW
300.0
kW
600.0
kW
• The range table lists the full scales of voltage and current mea-
surement ranges.
• When the VT (PT) ratio and CT ratio are set, the ranges will be
multiplied by (VT (PT) ratio × CT ratio).
• The number of digits of a measurement to display depends on
the PC application used.
Measurement
Range
Effective Power P Voltage range × Current
range
Measurement
Accuracy
±1.5%f.s.+Clamp sensor accuracy
Polarity
Consumption: No sign
Regeneration: "-"
Measurement
Range
Active energy within interval Wh + consumed
component only
Totalization
Accuracy
±1.6% f.s. ± clamp sensor accuracy
(Note that f.s. is voltage range × current
range.)
Summary of Contents for 2331-20
Page 1: ...INSTRUCTION MANUAL POWER METER 2331 20 MODULE ...
Page 2: ......
Page 26: ...1 4 Dimension Diagrams 22 ...
Page 28: ...2 1 Setting the Module ID 24 ...
Page 44: ...4 2 Insulation of Internal Circuit 40 ...
Page 54: ...5 3 General Specifications 50 ...
Page 56: ...6 2 Service 52 ...
Page 57: ......
Page 58: ......