Notes on Use
Wiring
When using the instrument in the case, drill
ventilation holes.
Drill ventilation holes or install a ventilation fan to
prevent heat buildup.
• When the clamp sensor is opened, do not
allow the metal part of the clamp to touch
any exposed metal, or to short between
two lines, and do not use over bare
conductors.
• U INPUT terminals 1 to 3 share the N
terminal and inputs to the terminals are not
insulated from each other. Beware of
electric shock and short-circuiting.
• The CLAMP SENSOR INPUT terminals
are not insulated from the U INPUT
terminals. Beware of electric shock and
short- circuiting.
• A qualified electrician shall perform the
wiring to prevent electric shock.
• Avoid live-line electrical work to prevent
electric shock, module malfunction due to
short-circuiting or opening of the CT
secondary side, overheating, and fire.
• When tightening the screws, confirm that
all screws are securely tightened. A loose
screw may result in module errors or the
generation of high voltage on the CT
secondary side, which may cause fire or
electric shock.