DNP V3.00
26
7.4.2 Binary Output Status Points
The following table lists both the Binary Output Status Points (Object 10).
Binary Output Status Points
Object Number:
10
Request Function Codes supported:
1 (read)
Default Variation reported
when variation 0 requested:
2 (Binary Output Status)
Control Relay Output Blocks
Object Number:
12
Request Function Codes supported:
3 (select), 4 (operate)
5 (direct operate), 6 (direct operate, noack)
Point
Index
Name/Description Methods
0
Equalize Mode
Latch On, Latch Off
(0 = float; 1 = equalize)
1
Manual Timer Method
Latch On
(1 = enabled)
2
Manual Equalize Method
Latch On
(1 = enabled)
3
Auto-Equalize Timer Method
Latch On
(1 = enabled)
4
HVDC Shutdown Enable
Latch On, Latch Off
(1 = enabled)
5
Battery Type
Latch On, Latch Off
(0 = lead; 1 = NiCD)
- --
NOTICE
- --
Only one (1) equalize method can be on at a time. The equalize method
cannot be turned off. By turning on one (1) of the equalize methods (point index 1, 2, or 3)
the charger will automatically turn off the other two (2) equalize methods.