F3 DIO 8/8 01
3 Product Description
HI 800 179 E Rev. 2.00
Page 11 of 52
3 Product
Description
The safety-related
F3 DIO 8/8 01
remote I/O is a compact system in a metal housing with
8 digital inputs, 8 digital DO+ outputs (L- ground), 2 digital DO- outputs (S+ ground) and 2
pulsed outputs. The digital outputs DO4+, DO8+, DO4- and DO8- can also be connected as
2-pole connections.
The remote I/O is available in various model variants for SILworX and ELOP II Factory, see
Table 4.
Remote I/Os are connected to individual HIMax or HIMatrix controllers via safe
ethernet
. They
are used to extend the I/O level, but are not able to run any user program by themselves.
The remote I/O is suitable for mounting in Ex-zone 2, see Chapter 4.1.5.
The device is TÜV-certified for safety-related applications up to SIL 3 (IEC 61508, IEC 61511
and IEC 62061), Cat. 4 and PL e (EN ISO 13849-1) and SIL 4 (EN 50126, EN 50128 and
EN 50129).
Further safety standards, application standards and test standards are specified in the
certificates available on the HIMA website.
3.1
Safety Function
The remote I/O is equipped with safety-related digital inputs and outputs. The input values on
the inputs are safely transmitted to the connected controller via safe
ethernet
. The outputs are
safely assigned their values by the connected controller via safe
ethernet
.
3.1.1
Safety-Related Digital Inputs
The remote I/O is equipped with 8 digital inputs. The state (HIGH, LOW) of each input is
signaled by an individual LED.
Mechanical contacts without own power supply or signal power source can be connected to the
inputs. Potential-free mechanical contacts without own power supply are fed via an internal
short-circuit-proof 24 V power source (LS+). Each of them supply a group of 4 mechanical
contacts. Figure 1 shows how the connection is performed.
With signal voltage sources, the corresponding ground must be connected to the input (L-), see
Figure 1.
DI 1
LS
+
DI 4
DI 3
DI 2
DI 1
L-
DI 4
DI 3
DI 2
Connection of potential-free mechanical
contacts
Connection of signal power sources
Figure 1: Connections to Safety-Related Digital Inputs
For the external wiring and the connection of sensors, apply the de-energized-to-trip principle.
Thus, if a fault occurs, the input signals adopt a de-energized, safe state (low level).
If an external wire is not monitored, an open-circuit is considered as safe low level.