Adhesive Anchoring Systems

3.2.6 HIT-HY 70 Hybrid for Masonry Construction

218   Hilti, Inc. (US) 1-800-879-8000  |  www.us.hilti.com  I  en español 1-800-879-5000  I  Hilti (Canada) Corp. 1-800-363-4458  I  www.hilti.ca  I  Anchor Fastening Technical Guide 2016

Table 6 - HIT-HY 70 allowable adhesive bond tension loads for HIS-N inserts in the face of grout-filled  

concrete masonry walls

1, 2, 3, 4, 5, 6, 7,8

Thread 

size

Effective 

embedment  

in. (mm)

11

Tension 

lb (kN)

Spacing

9

Edge distance

10

Critical 

s

cr

 

in. (mm)

Minimum 

s

min

 

in. (mm)

Load 

reduction 

factor @ s

min

6

Critical 

c

cr

 

in. (mm)

Minimum 

c

min

 

in. (mm)

Load 

reduction 

factor @ c

min

12

3/8-16 UNC

4-3/8

(111)

2,075

(9.2)

17

(431.8)

4

(102)

0.55

12

(304.8)

4

(102)

0.82

1/2-13 UNC

5

(127)

2,710

(12.1)

20

(508)

0.55

20

(508)

0.63

Table 7 - HIT-HY 70 allowable adhesive bond shear loads for HIS-N inserts in the face of grout-filled  

concrete masonry walls

1, 2, 3, 4, 5, 6, 7,8

Thread 

size

Effective 

embedment  

in. (mm)

11

Shear 

lb (kN)

Spacing

9

Edge distance

10

Critical 

s

cr

 

in. (mm)

Minimum 

s

min

 

in. (mm)

Load 

reduction 

factor @ 

s

min

6

Critical 

c

cr

 

in. (mm)

Minimum, 

c

min

 

in. (mm)

Load reduction factor  

@ c

min

12

Load 

perpendicular 

to edge

Load 

parallel to 

edge

3/8-16 UNC

4-3/8

(111)

1,100

(4.9)

17

(431.8)

4

(102)

0.74

12

(304.8)

4

(102)

0.72

1.00

1/2-13 UNC

5

(127)

2,065

(9.2)

20

(508)

0.71

20

(508)

0.40

0.87

1  All values are for anchors installed in fully grouted concrete masonry with minimum masonry prism strength of 1,500 psi. Concrete masonry units shall be lightweight, 

medium-weight or heavy-weight conforming to ASTM C90. Allowable loads are calculated using a safety factor of 5.

2  Anchors may be installed in any location in the face of the masonry wall including cell, web, and mortar joints. Anchors are limited to one per masonry cell.
3  

Linear interpolation of load values between minimum spacing (s

min

) and critical spacing (s

cr

) and between minimum edge distance (c

min

) and critical edge distance (c

cr

)  

is permitted.

4  Concrete masonry thickness must be equal to or greater than 1.5 times the anchor embedment depth. Exception: 5/8-and 3/4-in. anchors (No. 5 and No. 6 bars) may 

be installed in minimum nominally 8-inch-thick concrete masonry.

5  When using the basic load combinations in accordance with IBC Section 1605.3.1, tabulated allowable loads must not be increased for seismic or wind loading. 

When using the alternative basic load combinations in IBC Section 1605.3.2 that include seismic or wind loads, tabulated allowable loads may be increased by 33-1/3 

percent, or the alternative basic load combinations may be reduced by a factor of 0.75.

6  Allowable loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in table 4.

7  Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with figure 12.

8  For combined loading: (T

applied 

/ T

allowable

)

+ (V

applied 

/ V

allowable

)

n

 ≤ 1 

 

where n=5/3 for 3/8- and 1/2-inch diameters (No. 3 and No. 4 rebar) and n=1 for 5/8- and 3/4-inch diameter or No. 5 and No. 6 rebar.

9  The critical spacing, s

cr

, is the anchor spacing where full load values may be used. The minimum spacing, s

min

, is the minimum anchor spacing for which values are 

available and installation is recommended. Spacing is measured from the center of one anchor to the center of an adjacent anchor.

10  The critical edge distance, c

cr

, is the edge distance where full load values may be used. The minimum edge distance, c

min

, is the minimum edge distance for which 

values are available and installation is recommended. Edge distance is measured from the center of the anchor to the closest edge.

11   Embedment depth is measured from the outside face of the concrete masonry unit.

12  Load reduction factors are multiplicative, both spacing and edge distance load reduction factors must be considered. 

Load values for anchors installed at less than s

cr

 and c

cr

 must be multiplied by the appropriate load reduction factor based on actual edge distance (c) and spacing (s).

d

o

h

o

h

ef

screw

engagement

length

Figure 3 - HIT-HY 70 specifications 

for HIS-N inserts in grout-filled 

masonry walls 

Figure 4 — Allowable anchor installation locations 

in the face of grout-filled concrete block

 

4" Minimum

edge distance

Critical edge distance

(See load tables)  

 

Adhesive

anchor

4" Minimum

edge distance 

Critical edge

distance

(See load tables)

A

A

c

1

c

2

2

1

A-A

Installation in

this area for

full allowable

load capacity

Installation in

this area for

reduced allowable

load capacity

Summary of Contents for Hit-hY 70

Page 1: ...luding data development product specifications general suitability installation corrosion and spacing and edge distance guidelines US http submittals us hilti com PTGVol2 CA http submittals us hilti com PTGVol2CA To consult directly with a team member regarding our anchor fastening products contact Hilti s team of technical support specialists between the hours of 7 00am 6 00pm CST US 877 749 6337...

Page 2: ...ds steel internally threaded inserts combi inserts reinforcing bars plastic mesh screen tubes for installation only in unreinforced masonry URM hollow concrete block and hollow brick walls and the HIT HY 70 Adhesive For clay tile terracotta and masonry applications that are not specifically addressed in this Technical Guide please contact Hilti Technical Services Guide Specifications Master Format...

Page 3: ...sonry cell 3 Linear interpolation of load values between minimum spacing smin and critical spacing scr and between minimum edge distance cmin and critical edge distance ccr is permitted 4 Concrete masonry thickness must be equal to or greater than 1 5 times the anchor embedment depth EXCEPTION the 5 8 inch and the 3 4 inch diameter anchors No 5 and No 6 bars may be installed in minimum nominally 8...

Page 4: ...nforcing bars in the top of grout filled concrete masonry walls1 2 3 4 5 6 Nominal anchor diameter or rebar size Effective embedment in mm Edge distance in mm 7 8 Minimum end distance in mm Tension lb kN Shear load lb kN 9 Load parallel to edge of masonry wall Load perpendicular to edge of masonry wall 1 2 4 1 2 114 1 3 4 44 5 8 203 1 165 5 2 815 3 6 345 1 5 4 101 6 1 625 7 2 1 445 6 4 505 2 3 5 8...

Page 5: ...onry 5 When using the basic load combinations in accordance with IBC Section 1605 3 1 tabulated allowable loads must not be increased for seismic or wind loading When using the alternative basic load combinations in IBC Section 1605 3 2 that include seismic or wind loads tabulated allowable loads may be increased by 33 1 3 percent or the alternative basic load combinations may be reduced by a fact...

Page 6: ...concrete block wall A maximum of two anchors for each cell of the hollow ungrouted concrete block is allowed 3 Anchors are not recognized for resisting earthquake forces For short term loading due to wind forces the allowable loads shall not be increased 4 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with figure 12 5 Tabulated embedment depth i...

Page 7: ...combined loading Tapplied Tallowable Vapplied Vallowable 1 Table 10 HIT HY 70 allowable adhesive bond loads for threaded rods in the face of hollow brick1 2 3 4 5 10 Nominal anchor diameter Effective embedment Tension Minimum edge distance cmin Load reduction factor cmin Shear Edge distance6 Critical ccr Minimum cmin Load reduction factor cmin in mm 6 lb kN 7 8 in mm 9 lb kN 7 8 in mm in mm 1 4 3 ...

Page 8: ...onfigurations on site testing is required to determine the actual performance of the anchor Allowable loads are calculated using a safety factor of 5 2 Tabulated embedment depth is limited by the length of the plastic HIT SC 16x50 mm screens See figure 11 3 The required concrete thickness is the thickness for which values are available and installation is recommended Anchors shall be installed alo...

Page 9: ... 30 min 20 min 10 min 7 min 4 min 2 min 1 min 5 6 10 11 20 21 30 31 40 41 42 50 51 68 69 86 87 104 10 min 10 min 7 min 4 min 2 min 1 min 23 32 33 41 42 50 51 68 69 86 87 104 5 0 1 5 6 10 11 20 21 30 31 40 3 2 6 4 Installation instructions Installation Instructions For Use IFU are included with each product package They can also be viewed or downloaded online at www us hilti com US and www hilti ca...

Page 10: ...hollow concrete block Threaded Rod Mesh Sleeve Approximate fastenings per foil pack1 Rod Size 5 8 Grade Embedment in Qty Nominal Bit Dia in Mesh Sleeve per Fastening 11 1 fl oz 330 ml 16 9 fl oz 500 ml Plastic Sleeve for 14 screw 2 20 1 2 1 HIT S 12 I 25 40 HAS B 1 4 x 3 2 20 1 2 1 SC 12x50 25 40 HAS B 1 4 x 4 1 2 3 1 8 20 1 2 1 SC 12x85 16 26 HAS B 5 16 x 3 2 20 5 8 1 SC 16x50 16 26 HAS B 5 16 x ...

Page 11: ... 2 In hollow material use with HIT SC 22 x 50 10 7 8 13 Internally Threaded HIT IC 1 2 3 x 3 16 In hollow material use with HIT SC 22 x 85 10 7 8 13 HIT Combi Insert HIT S 12 I Plastic sleeve for 14 screw 20 1 2 Multi wythe brick walls Threaded Rod Mesh Sleeve Approximate fastenings per foil pack1 Rod Size 5 8 Grade Embedment in Qty Bit Diameter in Mesh Sleeve per Fastening 11 1 fl oz 330 ml 16 9 ...

Reviews: