Examples for Node-RED
145/263
8. Defining signal names for modules:
Ø
In the column
Tag
of the list
IO items
, click
send_001
(index
001
named
16 send byte (inputs)
).
Ø
Overwrite the available
Tag
name with the following new
Tag
name:
toController
.
Ø
In the column
Tag
of the list
IO items
, click
receive_001
(index
002
named
16 receive byte (outputs)
).
Ø
Overwrite the available
Tag
name with the following new
Tag
name:
fromController
.
Ê
The new
Tag
name which is part of the entire signal name is now
displayed for each module.
9. Defining signals for module 1:
Ø
Select
001: 16 send byte (inputs)
in the configuration tree.
Ê
The signal configuration page with information on module 001 will be
displayed.
Ø
Mark the available signal in the signal list.
Ø
Click
Delete selected items
.
Ø
Click
Add new signals
.
Ê
The
Add new signals
dialog box will be displayed.
Ø
Select the data type:
Signed16
.
Ø
Select the quantity: 8.
Ø
Under tag name base enter
Temperature
.
Ø
Click
Ok
.
Ê
Column
Tag
displays
Temperature_1
to
Temperature_8
. If required,
you can adapt the signal names in the column
Tag
.
Edge Gateway | NIOT-E-TIB100-GB-RE (Remote)
DOC170501UM04EN | Revision 4 | English | 2018-08 | Released | Public
© Hilscher 2017 – 2018