ATTENTION: All the maintenance operation must be done by TRAINED PEOPLE only.
ATTENTION: Before every operation of servicing on the unit, be sure that the electric supply is
disconnected
ATTENZIONE: Inside the unit some moving components are present. Be very careful when operating in
their surroundings even if the electric supply is disconnected.
ATTENTION: The top shell and discharge line of compressor are usually at high temperature level. Be
very careful when operating in their surroundings.
ATTENTION: Aluminium coil fins are very sharp and can cause serious wounds. Be very careful when
operating in their surroundings
ATTENTION: After servicing operation close the unit with cover panels, fixing them with locking screws.
CONDENSATE DRAINING CONNECTIONS
Condensate draining should
be done with a rubber pipe
fixed into the condensate
draining connection located
on the right hand side of the
unit. On the condensate
discharge pipe it must be
installed a syphon with a
minimum height equal to the
suction pressure of the fan.
The diameter of the
condensate discharge
connection is reported in the
dimensional drawings.
DUCT CONNECTIONS
All the units are provided with a centrifugal fan that can be ducted. If supply only should be ducted, a flanged connection with overall
dimensions larger than discharge hole located on the top of the unit should be used (please refer to unit dimensional drawing). In
case also the suction side should be ducted it is necessary to connect the return duct with a flange having the same dimensions of
the filter frame (See next picture).
WARNING: In case of ducted installations it is very important to check that the airflow is close to the
nominal value with a maximum tolerance of +/-15%. Airflow outside these limits can compromise the
correct operation.
WARNING: When ductworks are connected it is IMPORTANT to check if the airspeed through the
evaporator is around 1,5÷ 2 m/s. This parameter allow the unit to operate with the maximum efficiency;
so an airspeed over than 2 m/s should never been exceeded.
Summary of Contents for SRH Series
Page 1: ...SWIMMING POOLS DEHUMIDIFIERS SRH SERIES TECNICAL MANUAL ...
Page 2: ...SRH Swimming Pools Dehumidifiers MTSRHGB 2 REV 072008 ...
Page 3: ...SRH Swimming Pools Dehumidifiers MTSRHGB 3 REV 072008 ...
Page 4: ...SRH Swimming Pools Dehumidifiers MTSRHGB 4 REV 072008 ...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......