MTEC.6715.GB-C-1 Operation and maintenance manual HMA BT series English
HMA BT
,QGXVWULDOGHKXPLGL¿HUV
4.8 Location and minimum technical clearances
The unit has to be installed such that maintenance and repair is possible. The warranty does not cover costs for the
provision of lifting apparatus, platforms or other lifting systems required to perform repairs during warranty period.
The installation site should be chosen in accordance with EN 378-1 and 378-3 standards. When choosing the
installation site, all risks caused by accidental refrigerant leakage should be taken into consideration.
&RQGHQVDWHGUDLQLQJFRQQHFWLRQV
The connection of the condensate discharge has to be made with a rigid pipe. On the condensate discharge pipe it must be installed a
syphon with a minimum height equal to the suction pressure of the fan.
7KHFRQGHQVDWHGUDLQOLQHVKRXOGKDYHDZDWHUWUDSZKLFKPD\KDYHPLQLPXPÀ\LQJKHLJKWHTXDOWRWKHVXFWLRQRI
the fan, in any case never less than 35 mm.
Discharge pipe
H1
= 20 mm
H2
ǻ3PP
Ǽ3
= pressure difference
inside the unit in mm water
column
10 Pa
§
1 mm water column
7KHVLSKRQPXVWEH¿OOHGZLWKZDWHUEHIRUHVWDUWLQJWKHXQLW